GE DS3800XAIC1C1C

¥999.00

The DS3800XAIC1C1C is a high-reliability, configurable variant of the GE Mark IV analog I/O extender board within the DS3800XAIC series. It provides 16 analog inputs and 8 analog outputs with per-channel configurability for maximum flexibility in mixed-signal environments. This variant features enhanced 16-bit ADC resolutionimproved isolation (2500V)extended temperature range (–40°C to +85°C) , conformal coating, and updated firmware (1C1C) with advanced diagnostics. It is designed for critical applications requiring both flexibility and ruggedness. It works alongside boards such as the DS3800NVIA1G1CDS3800NVIA1G1D, and DS3800NVOC to provide comprehensive analog signal handling.

Category:

Description

Key Parameters

  • Analog Input Channels: 16 differential or 32 single-ended (software-configurable)

  • Analog Input Types: 0–10V, ±10V, 4–20mA (per-channel jumper-selectable)

  • Analog Output Channels: 8 independent (0–10V, ±10V, or 4–20mA)

  • Resolution: 16-bit ADC (inputs – improved over 14-bit standard), 12-bit DAC (outputs)

  • Accuracy: ±0.05% of full scale (inputs – improved), ±0.2% of full scale (outputs)

  • Isolation: 2500V RMS channel-to-backplane (enhanced)

  • Diagnostics: Per-channel LED status, over-range/under-range detection, open-circuit detection, output short-circuit detectionself-calibration on power-up

  • EMI/RFI Filtering: Enhanced input filters for improved noise rejection

  • Temp Range: –40°C to +85°C (extended)

  • Power Supply: +5V, ±15V from VME backplane

  • Physical: 6U VME single-slot board

  • Key Variant Features: 16-bit ADC, per-channel configurability, 2500V isolation, extended temp range, self-calibration, conformal coating, firmware rev 1C1C


Advantages

  • Per-channel configurability – each of the 16 inputs can be independently set for voltage or current, providing maximum flexibility for mixed-signal applications.

  • High precision – 16-bit ADC resolution (vs. 14-bit on standard DS3800XAIC) delivers ±0.05% accuracy for critical measurements.

  • Superior isolation – 2500V RMS isolation protects the backplane from field-side surges and transients.

  • Extended temperature range – operates from –40°C to +85°C, suitable for harsh outdoor, offshore, or unheated cabinet installations.

  • Self-calibration – automatic calibration at power-up compensates for temperature drift and component aging.

  • Enhanced diagnostics – includes output short-circuit detection and per-channel LEDs for rapid troubleshooting.

  • Conformal coating – protects against moisture, salt spray, and airborne contaminants.

  • Drop-in compatible – direct replacement for standard DS3800XAIC with no wiring changes.


Applications

  • Mixed signal environments – the General Electric DS3800XAIC1C1C is ideal for installations with a variety of sensor types (voltage, current, thermocouple via transmitters) that require individual channel configuration.

  • Critical turbine monitoring – provides precise, flexible inputs for temperature, pressure, flow, and position transmitters in gas and steam turbines.

  • Offshore platforms – the extended temperature range and conformal coating make it suitable for saltwater environments.

  • Harsh industrial environments – chemical plants, desert installations, and pulp & paper mills benefit from the ruggedized design.

  • Valve position feedback – monitors multiple LVDT or potentiometer feedback signals with individual configuration.

  • Retrofits – adds diagnostic capabilities and higher precision to legacy Mark IV systems.


vs Competitors & Previous Variants

Feature DS3800XAIC1C1C Standard DS3800XAIC Standard DS3800XAIA Generic VME Board
Input resolution 16-bit 14-bit 14-bit 12–14-bit
Accuracy ±0.05% ±0.1% ±0.1% ±0.2–0.5%
Configurability Per-channel Per-channel Per-channel Fixed or per-channel
Isolation 2500V 1500V 1000V 500–1000V
Self-calibration Yes No No No
Output short detect Yes Yes No Rarely
Temp range –40°C to +85°C –30°C to +70°C –30°C to +70°C 0°C to +60°C
Conformal coating Yes Optional Optional Rarely
Firmware revision 1C1C Varies Varies N/A

Selection Tips

  • Mixed signal types – choose the DS3800XAIC1C1C when you have a mix of voltage and current sensors that cannot be grouped into banks; per-channel configurability provides maximum flexibility.

  • Harsh environments – select this variant for offshore, desert, or chemically aggressive sites where temperature extremes and corrosion are concerns.

  • High precision needs – use the General Electric DS3800XAIC1C1C for critical measurements requiring ±0.05% accuracy (e.g., exhaust temperature averaging, flow calculations).

  • Diagnostic requirements – the enhanced diagnostics (self-calibration, output short detection) make this board ideal for facilities with proactive maintenance programs.

  • Jumper documentation – each input channel has its own jumper for voltage/current selection; record all jumper positions before removal for easy reinstallation.

  • Spare strategy – keep one DS3800XAIC1C1C per 10 installed units; its flexibility and ruggedness make it a versatile and critical spare.

  • Calibration – although self-calibrating, perform a verification check with a precision calibrator on critical channels during commissioning.


Critical Precautions

  • Jumper configuration – each of the 16 input channels on the DS3800XAIC1C1C requires its own jumper setting. Document all positions before board removal; incorrect settings will produce erroneous readings.

  • Over-voltage on inputs – never apply voltage above ±30V to any analog input; this can damage the 16-bit ADC front-end.

  • Output short circuit – while the DS3800XAIC1C1C has short-circuit detection, repeated shorts can degrade output accuracy. Clear faults promptly and inspect field wiring.

  • Ground loops – use single-point grounding for field transmitters to avoid common-mode voltage exceeding ±10V on inputs.

  • Wiring separation – keep analog signal wiring away from AC power lines and high-voltage cables to prevent noise coupling.

  • Self-calibration – allow the General Electric DS3800XAIC1C1C to complete its power-up self-calibration cycle (approximately 5 seconds) before relying on measurements.

  • Calibration intervals – schedule periodic verification checks every 6–12 months to maintain ±0.05% accuracy, especially for critical 4–20mA loops.

  • ESD handling – always use a grounded wrist strap; the high-precision 16-bit ADC is particularly ESD-sensitive.

  • Humidity – avoid condensation; conformal coating protects against moisture, but extreme humidity can still affect high-impedance input circuits.

  • Firmware compatibility – confirm the main processor firmware version supports the DS3800XAIC1C1C; the 16-bit resolution and self-calibration may require a software update.

  • Hot-swap – never insert or remove the DS3800XAIC1C1C while the rack is powered; this can cause bus errors or component damage.

A-B 1492-FB1M30