Description
Key Parameters
-
Output Channels: 16 independent form-C (SPDT) relay outputs
-
Relay Type: Hermetically sealed (gas-filled) for contamination-free operation
-
Contact Material: Gold-plated (optimized for dry-circuit and power loads)
-
Contact Rating: 5A at 250V AC / 30V DC (resistive); 0.1A at 5V DC (dry-circuit)
-
Coil Voltage: 24V DC from backplane
-
Isolation: 2500V RMS coil-to-contact, 1500V RMS channel-to-channel
-
Diagnostics: Coil status LED per channel, fuse status indication
-
Mechanical Life: >50 million operations
-
Electrical Life: >200,000 operations at rated load
-
Temp Range: –40°C to +85°C (extended)
-
Power Supply: +5V (logic), +24V (relay coils) from backplane
-
Physical: 6U VME single-slot board
-
Key Variant Features: Hermetically sealed relays, extended temp range, gold-plated contacts, enhanced coil suppression, conformal coating
Advantages
-
Hermetically sealed relays – the DS3800NVRC1C1C uses gas-filled relays that are immune to dust, humidity, and corrosive atmospheres, making them ideal for offshore, desert, or chemical environments.
-
Gold-plated contacts – ensures reliable operation for both high-current and low-current (dry-circuit) applications; no contact oxidation over time.
-
Extended temperature range – operates reliably from –40°C to +85°C, surpassing standard Mark IV boards.
-
Enhanced coil suppression – internal flyback diodes and snubbers reduce voltage spikes, extending relay and driver life significantly.
-
Conformal coating – the PCB is coated to protect against moisture, salt spray, and airborne contaminants.
-
Full isolation – channel-to-channel and coil-to-contact isolation prevents noise coupling and ground loops.
-
Fused outputs – each channel has a replaceable fuse to protect against field wiring shorts.
Applications
-
Critical turbine trip circuits – drives emergency stop solenoid valves for fuel, steam, and lube oil in safety-critical applications (SIL-2 rated).
-
Offshore platforms – the General Electric DS3800NVRC1C1C is specifically suited for saltwater environments where corrosion is a concern.
-
Desert installations – sealed relays prevent sand and dust ingress.
-
Alarm annunciation – activates panel lamps, horns, and DCS alarm inputs (including dry-contact PLC inputs).
-
Generator breaker control – initiates trip and close commands with high reliability.
-
Harsh industrial environments – chemical plants, pulp and paper mills, and cement factories benefit from the sealed relay design.
vs Competitors & Previous Variants
| Feature | DS3800NVRC1C1C | Standard DS3800NVRC | Generic VME Relay Board |
|---|---|---|---|
| Relay type | Hermetically sealed | Standard open-frame | Standard open-frame |
| Contact material | Gold-plated | Standard silver | Standard silver/tin |
| Dry-circuit capability | Yes | No (oxidation risk) | No |
| Temp range | –40°C to +85°C | –30°C to +70°C | 0°C to +60°C |
| Conformal coating | Yes | Optional | Rarely |
| Mechanical life | >50M cycles | >10M cycles | 5–10M cycles |
| Coil suppression | Enhanced (dual-stage) | Standard | External required |
| Fused outputs | Yes (per channel) | Yes | No |
Selection Tips
-
Harsh environments – choose the DS3800NVRC1C1C over the standard DS3800NVRC or DS3800NVRC1A if your site has high humidity, salt spray, dust, or corrosive gases.
-
Critical safety circuits – for SIL-2 rated trip circuits, the hermetically sealed relays of the General Electric DS3800NVRC1C1C provide the highest reliability and contact stability.
-
Dry-circuit applications – the gold-plated contacts are ideal for low-current signals (e.g., 5V DC logic inputs to PLCs or DCS).
-
Load verification – confirm the inrush current of solenoid valves does not exceed the 5A rating of the DS3800NVRC1C1C; use an external contactor for higher loads.
-
Fail-safe wiring – use the NC contact for critical trip circuits so that the valve actuates on power loss or board removal.
-
Fuse replacement – stock spare fuses (specification: 5A slow-blow, 250V) for each DS3800NVRC1C1C installed.
-
Spare strategy – keep one DS3800NVRC1C1C per 8–10 installed units; the sealed relays have a longer life, reducing spare requirements.
Critical Precautions
-
Inductive loads – despite enhanced internal suppression, always install a flyback diode (for DC loads) or RC snubber (for AC loads) across solenoid coils for additional protection of the DS3800NVRC1C1C contacts.
-
Fuse rating – do not exceed the specified 5A fuse rating; using a higher-rated fuse can result in PCB trace damage during a short circuit.
-
Wiring inspection – check for shorts in field wiring before energizing the DS3800NVRC1C1C; a short can blow the fuse or weld the contacts.
-
Gold contact sensitivity – do not use contact cleaners or lubricants on the relay contacts; the gold plating is thin and can be easily damaged.
-
Sealed relay integrity – do not attempt to open or repair the hermetically sealed relays; replace the entire General Electric DS3800NVRC1C1C if a relay fails.
-
Hot-swap – never insert or remove the DS3800NVRC1C1C while the rack is powered; relay coils may latch unexpectedly and cause unintended trips.
-
Grounding – use separate grounding for the relay common and the logic ground to avoid noise coupling into the backplane.
-
Storage – store spare DS3800NVRC1C1C boards in anti-static bags in a dry, temperature-controlled environment; although sealed relays are protected, other PCB components are still sensitive.

SCHNEIDER 140XTS00200
A-B 1756-BA2
A-B 1756-BA2


Reviews