Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 100–150 VDC); 24 VDC compatible with external adapter |
| Output Rails | Main Output: 5–24 VDC / 5A (adjustable), +5 VDC / 2A (logic), ±15 VDC / 0.5A (each rail, analog) |
| Isolation | Full isolation (1.5kV input‑to‑output, 2.0kV output‑to‑ground) |
| Protection | Overcurrent protection (fixed), short‑circuit protection, transient suppression (4kV), reverse polarity protection, input undervoltage lockout |
| Regulation | Load regulation: ±0.5%; Line regulation: ±0.2%; Ripple: < 30mVpp (main), < 20mVpp (±15V) |
| Adjustment Range | Main output adjustable 5–24 VDC via onboard potentiometer |
| Monitoring | 2 analog feedback channels (voltage monitoring for main output and +5V); 2 digital fault outputs (relay, 24V/0.5A) for system faults |
| Digital Interface | 2 digital inputs for external control; 4 digital outputs for status indication |
| Operating Temperature | –25°C to +60°C |
| Form Factor | 6U × 6HP (30mm) – requires 1.5 slots |
| Backplane Connector | Standard VME 96‑pin P1 + reinforced 60‑pin P2 |
| Status LEDs | 6 indicators: INPUT OK (green), OUTPUT OK (green), SYSTEM OK (green), FAULT (red), ADJUST ACTIVE (blue), AUX OK (green) |
| Certifications | CE, UL 508 (non‑hazardous locations only) |
| Efficiency | ~78% at full load |
Critical note: The DS3800NVCB is a variable voltage converter board with adjustable main output (5–24 VDC). It is physically wider (6HP) than standard 4HP boards and requires 1.5 adjacent slots. Hot‑swapping is not supported.
Key Features & Advantages
-
Adjustable Main Output – 5–24 VDC adjustable via onboard potentiometer.
-
Full Isolation – 1.5kV isolation protects sensitive circuits.
-
Multiple Outputs – Main output plus fixed +5V and ±15V rails.
-
Two Fault Relays – Separate fault indication for system faults.
Typical Application Cases
-
Auxiliary Control Cabinets – Provides flexible voltage conversion.
-
Test Equipment – Supplies adjustable voltage for testing.
-
Field Device Power Distribution – Powers devices with varying voltage requirements.
Selection Guidelines & Precautions
-
Application Verification – Designed for flexible voltage conversion with adjustable output.
-
Physical Compatibility – 6HP wide, requires 1.5 adjacent slots.
-
Backplane Compatibility – Uses P1 and P2. If backplane lacks P2, auxiliary features unavailable.
-
Voltage Adjustment – Adjust main output via onboard potentiometer. Use precision voltmeter for calibration.
-
Thermal Derating – Full output to 50°C; derate to 90% at 50–55°C, 80% at 55–60°C.
-
Spare Sourcing – Production ended in 2010. Request test report verifying outputs and adjustment range. Inspect for capacitor bulging or discoloration.

A-B 1756-TBCH
A-B 1769-ECL
A-B 1756-TBCH


Reviews