Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 90–160 VDC); 24 VDC compatible with external adapter |
| Output Rails | +5 VDC / 12A (main logic), ±15 VDC / 2.5A (each rail, analog circuits) |
| Isolation | Full isolation (1.5kV input‑to‑output, 2.0kV output‑to‑ground) |
| Protection | Overcurrent protection (adjustable per output via jumpers), short‑circuit protection, transient suppression (6kV surge), reverse polarity protection, input undervoltage lockout |
| Regulation | Load regulation: ±0.2%; Line regulation: ±0.1%; Ripple: < 15mVpp (+5V), < 10mVpp (±15V) |
| Wide‑Area Communication | Onboard Ethernet/Modbus TCP interface for remote monitoring and control; communicates with main CPU via backplane |
| Monitoring | 8 analog feedback channels (voltage and current monitoring for each output rail, plus input voltage and current monitoring); 6 digital fault outputs (relay, 24V/1.5A) for system faults |
| Digital Interface | 6 digital inputs for external control; 8 digital outputs for system status indication |
| Supervisory Control | Onboard ARM Cortex‑M7 microcontroller for diagnostic reporting, system health monitoring, predictive failure analytics (capacitor ESR, MOSFET health), and event logging (5,000‑event buffer) |
| Operating Temperature | –40°C to +70°C |
| Form Factor | 6U × 6HP (30mm) – requires 1.5 slots |
| Backplane Connector | Standard VME 96‑pin P1 + reinforced 60‑pin P2 |
| Status LEDs | 10 indicators: +5V OK (green), +15V OK (green), –15V OK (green), SYSTEM OK (green), FAULT (red), COMM ACTIVE (white), WAN ACTIVE (blue), OVERTEMP (yellow), PREDICTIVE ALERT (purple), INPUT STATUS (orange) |
| Certifications | CE, UL 508, CSA Class I Div 2, IEC 61508 SIL 2 (TÜV‑certified) |
| Efficiency | ~86% at full load |
Critical note: The DS3800NSWA1A1B is a supervisory control and wide‑area monitoring interface with advanced diagnostics, predictive analytics, and SIL 2 certification. It is physically wider (6HP) than standard 4HP boards and requires 1.5 adjacent slots. Hot‑swapping is not supported.
Key Features & Advantages
-
Higher Capacity – +5V at 12A and ±15V at 2.5A—higher than baseline NSWA.
-
Wide‑Area Communication – Ethernet/Modbus TCP interface for remote monitoring.
-
Predictive Analytics – Monitors capacitor ESR and MOSFET health; purple LED warns before failure.
-
Event Logging – 5,000‑event buffer for failure analysis.
-
Comprehensive Monitoring – Eight analog channels provide V+I monitoring for each output plus input.
-
Six Fault Relays – Separate fault indication for system faults.
-
SIL 2 Certification – TÜV‑certified for functional safety.
-
Wide Temperature Range – –40°C to +70°C.
Typical Application Cases
-
Main Control Cabinets – Provides power with integrated wide‑area monitoring and diagnostics.
-
Remote Monitoring Systems – Powers racks requiring remote communication capabilities.
-
Safety‑Related Systems – SIL 2 certification makes it suitable for safety‑critical applications.
-
System Integration Projects – Used when remote power reporting and predictive analytics are required.
Competitive Comparison
| Aspect | DS3800NSWA1A1B (GE) | DS3800NSWA (baseline) | DS3800NSFC1J1G (GE) |
|---|---|---|---|
| +5V Output | 12A | 10A | 15A |
| ±15V Output | 2.5A each | 2A each | 3.5A each |
| Wide‑Area Communication | Yes (Ethernet/Modbus TCP) | Yes | Yes (RS‑485 + Ethernet) |
| Predictive Analytics | Yes | No | Yes |
| Event Logging | 5,000 events | No | 5,000 events |
| SIL 2 | Yes | No | Yes |
| Price (refurb) | ~$5,500–$8,000 | ~$4,500–$6,500 | ~$6,200–$9,000 |
Selection Guidelines & Precautions
-
Application Verification – Designed for integrated power management with wide‑area monitoring, predictive analytics, and SIL 2.
-
Physical Compatibility – 6HP wide, requires 1.5 adjacent slots.
-
Backplane Compatibility – Uses P1 and P2. If backplane lacks P2, communication features unavailable.
-
Communication Configuration – Configure Ethernet/Modbus TCP parameters via backplane communication using GE Service Tool Software.
-
Thermal Derating – Full output to 60°C; derate to 90% at 60–65°C, 80% at 65–70°C. Do not operate above 70°C.
-
SIL 2 Compliance – Follow GE safety manual GEI‑101015 for installation and proof‑test intervals.
-
Spare Sourcing – Production ended in 2021. Request test report verifying outputs, communication functions, predictive analytics, and event logging. Inspect for capacitor bulging or discoloration.

ΰ DRP-240-24