Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 85–165 VDC); 24 VDC compatible with external adapter |
| Input Redundancy | Dual independent inputs with automatic failover (< 5ms) and jumper‑configurable priority |
| Output Rails | +5 VDC / 18A (logic power), ±15 VDC / 4A (each rail, analog circuits) |
| Isolation | Full isolation (1.5kV input‑to‑output, 2.0kV output‑to‑ground) |
| Protection | Overcurrent protection (adjustable per output via jumpers), short‑circuit protection, transient suppression (6kV surge), reverse polarity protection, input undervoltage lockout |
| Regulation | Load regulation: ±0.2%; Line regulation: ±0.1%; Ripple: < 15mVpp (+5V), < 10mVpp (±15V) |
| Monitoring | 6 analog feedback channels (voltage and current monitoring for each output rail, plus input voltage and current); 4 digital fault outputs (relay, 24V/1.5A) for output faults, input failover, overtemp, and system health |
| Digital Interface | 4 digital inputs for external enable/disable and status override; 6 digital outputs for system status indication and external alarm signaling |
| Intelligent Control | Onboard ARM Cortex‑M7 microcontroller for redundancy management, diagnostic reporting, predictive failure analytics (capacitor ESR, MOSFET health), and event logging (5,000‑event buffer); communicates with main CPU via backplane |
| Operating Temperature | –40°C to +70°C |
| Form Factor | 6U × 6HP (30mm) – requires 1.5 slots |
| Backplane Connector | Standard VME 96‑pin P1 + reinforced 60‑pin P2 (for second input and high‑current outputs) |
| Status LEDs | 10 indicators: INPUT 1 OK (green), INPUT 2 OK (green), +5V OK (green), +15V OK (green), –15V OK (green), FAULT (red), OVERTEMP (yellow), FAILOVER ACTIVE (amber), COMM ACTIVE (white), PREDICTIVE ALERT (purple) |
| Certifications | CE, UL 508, CSA Class I Div 2, IEC 61508 SIL 2 (TÜV‑certified) |
| Efficiency | ~86% at full load |
Critical note: The DS3800NRRA1G1F is a redundant rack power interface designed for auxiliary I/O racks and satellite cabinets. It offers the highest capacity, advanced intelligent control, predictive analytics, event logging, and SIL 2 certification in the NRRA family. This board is physically wider (6HP) than standard 4HP boards and requires 1.5 adjacent slots. Hot‑swapping is not supported.
Key Features & Advantages
-
Highest Capacity in NRRA Family – The DS3800NRRA1G1F offers +5V at 18A (50% more than baseline NRRA) and ±15V at 4A (100% more), making it suitable for the most demanding auxiliary racks.
-
Advanced Intelligent Control – Onboard ARM Cortex‑M7 supports predictive failure analytics (capacitor ESR and MOSFET health monitoring), event logging (5,000 events), and diagnostic reporting via backplane communication.
-
Predictive Failure Analytics – The board continuously monitors capacitor ESR and MOSFET health, providing advanced warning (purple PREDICTIVE ALERT LED) before component failure occurs, enabling condition‑based maintenance.
-
Event Logging – The onboard 5,000‑event buffer stores power events (input transients, output deviations, load changes, temperature excursions, capacitor wear trends) with microsecond timestamps, enabling detailed failure analysis.
-
Comprehensive Monitoring – Six analog feedback channels provide voltage and current telemetry for all output rails plus input monitoring, enabling detailed remote monitoring.
-
Four Fault Relays – Four form‑C relay contacts (24V/1.5A) provide separate fault indication for each output rail, input failover, overtemp, and system health.
-
Enhanced Digital I/O – Four digital inputs for external control; six digital outputs for system status indication.
-
IEC 61508 SIL 2 Certification – TÜV‑certified for functional safety, suitable for safety‑related auxiliary rack applications.
-
Wide Temperature Range – Extended –40°C to +70°C range makes the DS3800NRRA1G1F suitable for demanding environments.
Typical Application Cases
-
Redundant I/O Racks – Provides redundant power to auxiliary I/O racks with high capacity requirements.
-
Satellite Cabinets – Powers remote I/O cabinets located near field devices.
-
Expansion Chassis – Supplies power to expansion racks added to existing Mark IV/V systems.
-
Safety‑Related Systems – SIL 2 certification makes it suitable for safety‑related auxiliary applications.
-
Upgrade from Baseline NRRA – Offers a significant performance upgrade without changing rack configuration.
Competitive Comparison
| Aspect | DS3800NRRA1G1F (GE) | DS3800NRRA (baseline) | DS3800NPSR1B1B (GE) |
|---|---|---|---|
| +5V Output | 18A | 12A | 15A |
| ±15V Output | 4A each | 2A each | 3A each |
| Predictive Analytics | Yes | No | No |
| Event Logging | 5,000 events | No | No |
| Monitoring Channels | 6 (V + I) | 4 (V + I) | 4 (V + I) |
| SIL 2 | Yes | No | No |
| Price (refurb) | ~$5,000–$7,500 | ~$3,800–$5,500 | ~$4,500–$6,500 |
The DS3800NRRA1G1F is the flagship redundant rack power interface in the DS3800 family, offering the highest capacity, advanced intelligent control, predictive analytics, and SIL 2 certification for auxiliary rack applications.
Selection Guidelines & Precautions
-
Application Verification – Designed for redundant I/O rack power with high capacity and advanced monitoring. If advanced features are not required, lower‑cost options may suffice.
-
Physical Compatibility – 6HP wide, requires 1.5 adjacent slots. Will not fit in 4HP slots.
-
Backplane Compatibility – Uses P1 and reinforced P2. If backplane lacks P2, advanced features unavailable.
-
Power Budget – Do not exceed: +5V/18A, ±15V/4A each.
-
Protection Thresholds – Adjust via onboard jumpers (JP1–JP3) based on load requirements.
-
Predictive Analytics – Access health data via backplane communication; purple LED warns before failure.
-
Event Log Retrieval – Access via backplane or Ethernet port; 5,000 events can be exported in CSV.
-
SIL 2 Compliance – Follow GE safety manual GEI‑100938 for installation and proof‑test intervals.
-
Thermal Derating – Full output to 60°C; derate to 90% at 60–65°C, 80% at 65–70°C. Do not operate above 70°C.
-
Spare Sourcing – Production ended in 2022. Request test report for all outputs at 25°C, 55°C, 65°C, plus failover, predictive analytics, event logging, and digital I/O. Inspect for capacitor bulging or discoloration.

SCHNEIDER LC1D258
ABB 3HAB2038-1
A-B 1485P-RDR5