Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 85–165 VDC); 24 VDC compatible with external adapter |
| Input Redundancy | Dual independent inputs with automatic failover (< 5ms) and jumper‑configurable priority |
| Output Rails | +24 VDC / 12A (field power), ±15 VDC / 2A (each rail, analog field circuits), +5 VDC / 4A (logic/communication) |
| Isolation | Full isolation (1.5kV input‑to‑output, 2.0kV output‑to‑ground) |
| Protection | Individual overcurrent protection per output (adjustable via jumpers), short‑circuit protection, transient suppression (6kV surge), reverse polarity protection, input undervoltage lockout |
| Regulation | Load regulation: ±0.2%; Line regulation: ±0.1%; Ripple: < 20mVpp (+24V), < 10mVpp (±15V), < 15mVpp (+5V) |
| Monitoring | 6 analog feedback channels (voltage and current monitoring for each output rail); 4 digital fault outputs (relay, 24V/1.5A) for individual output faults, input failover, overtemp, and system health |
| Digital Interface | 4 digital inputs for external enable/disable and status override; 6 digital outputs for output status indication |
| Operating Temperature | –30°C to +65°C |
| Form Factor | 6U × 6HP (30mm) – requires 1.5 slots |
| Backplane Connector | Standard VME 96‑pin P1 + reinforced 60‑pin P2 (for second input and high‑current outputs) |
| Status LEDs | 10 indicators: INPUT 1 OK (green), INPUT 2 OK (green), +24V OK (green), +15V OK (green), –15V OK (green), +5V OK (green), FAULT (red), OVERTEMP (yellow), FAILOVER ACTIVE (amber), COMM ACTIVE (white) |
| Certifications | CE, UL 508, CSA Class I Div 2 |
| Efficiency | ~85% at full load |
Critical note: The DS3800NRFA1E1D is a redundant field power interface designed for critical field device power distribution. It offers higher capacity, advanced fault monitoring, and comprehensive diagnostics compared to the baseline NRFA. This board is physically wider (6HP) than standard 4HP boards and requires 1.5 adjacent slots. Hot‑swapping is not supported.
Key Features & Advantages
-
Higher Capacity than Baseline NRFA – The DS3800NRFA1E1D offers increased current ratings: +24V at 12A (50% more), ±15V at 2A (100% more), and +5V at 4A (100% more) compared to baseline NRFA.
-
Advanced Input Redundancy – The DS3800NRFA1E1D accepts two independent DC inputs with jumper‑configurable priority (Input 1 or Input 2 selectable as primary). Automatic failover occurs within < 5ms on input loss.
-
Individual Overcurrent Protection – Each output (+24V, +15V, –15V, +5V) has independent overcurrent protection with adjustable thresholds via onboard jumpers, preventing a fault on one output from affecting others.
-
Comprehensive Monitoring – Six analog feedback channels provide voltage and current telemetry for all output rails, enabling detailed remote monitoring of field power health and load conditions.
-
Four Fault Relays – Four form‑C relay contacts (24V/1.5A) provide separate fault indication for output faults, input failover events, overtemperature, and system health, enabling flexible alarm configuration with plant DCS.
-
Enhanced Digital I/O – Four digital inputs for external control and status override; six digital outputs for output status indication and external alarm signaling.
-
Full Isolation – 1.5kV isolation protects sensitive control circuits from field device transients and ground loops.
-
Enhanced Surge Protection – Upgraded input protection withstands 6kV surges (IEC 61000‑4‑5), improving resilience against lightning‑induced transients in remote installations.
-
Wide Temperature Range – Extended –30°C to +65°C range and CSA Div 2 certification make the DS3800NRFA1E1D suitable for demanding environments.
Typical Application Cases
-
Critical Solenoid Valve Power – Provides redundant, conditioned power to safety shutdown solenoids, trip valves, and purge valves in gas and steam turbine systems.
-
Actuator Control Panels – Powers electric actuators for inlet guide vanes, bleed valves, and turbine bypass controls with individual overcurrent protection for each actuator.
-
Field Transmitter Power – Supplies power to pressure transmitters, temperature sensors, and positioners in critical measurement loops requiring high availability.
-
Redundant Field Device Cabinets – Installed in auxiliary panels where field device power continuity is essential for turbine operation.
-
Offshore Platforms with Dual Battery Banks – Dual input capability supports connection to two independent battery banks, ensuring power continuity during battery maintenance.
-
Upgrade from Baseline NRFA – When an older NRFA board fails, the DS3800NRFA1E1D offers a significant performance upgrade (higher capacity, more monitoring, enhanced diagnostics) without changing rack configuration.
Competitive Comparison
| Aspect | DS3800NRFA1E1D (GE) | DS3800NRFA (baseline) | DS3800NPSL1A1A (GE) |
|---|---|---|---|
| Primary Output | +24V / 12A | +24V / 8A | 125VDC / 5A |
| Input Redundancy | Yes (configurable priority) | Yes (fixed priority) | No |
| Individual Output Protection | Yes (4 outputs) | Yes (3 outputs) | No |
| Monitoring Channels | 6 (V + I) | 4 (V + I) | 1 (V only) |
| Fault Relays | 4 | 3 | 1 |
| Digital Outputs | 6 | 4 | 0 |
| Surge Protection | 6kV | 4kV | 4kV |
| Operating Temp | –30°C to +65°C | –25°C to +60°C | –25°C to +60°C |
| Efficiency | ~85% | ~83% | ~84% |
| Price (refurb) | ~$5,500–$7,800 | ~$4,500–$6,500 | ~$2,800–$4,200 |
The DS3800NRFA1E1D is the premier redundant field power interface in the DS3800 family, offering the highest capacity, most comprehensive monitoring, and advanced diagnostics for critical field device power applications.
Selection Guidelines & Precautions
-
Application Verification – The DS3800NRFA1E1D is designed for critical field device power distribution requiring redundant inputs and individual output protection. If your application does not require these advanced features, NPSL or generic power supplies may be more cost‑effective.
-
Physical Compatibility – The DS3800NRFA1E1D is 6HP wide, requiring 1.5 adjacent slots in your Mark IV/V rack. It will not fit in standard 4HP slots and requires an adjacent empty half‑slot position.
-
Backplane Compatibility – Uses both P1 and reinforced P2 connectors. The second DC input and additional digital I/O are provided through the P2 connector. If your backplane lacks P2 (pre‑2005 racks), the redundant input feature and digital I/O will be unavailable.
-
Input Priority Configuration – Configure primary/secondary priority via onboard jumpers (JP1‑JP2). The default setting uses Input 1 as primary and Input 2 as secondary. Jumper settings are clearly marked on the PCB silkscreen.
-
Protection Threshold Adjustment – Configure overcurrent thresholds via onboard jumpers (JP3–JP6) based on field device requirements. Factory defaults are 120% of rated current—adjust downward for sensitive devices or upward for devices with high inrush current.
-
Power Budget – Calculate total current draw:
-
+24V: max 12A
-
±15V: max 2A each
-
+5V: max 4A
Exceeding any output will trigger its individual overcurrent protection and latch that output off.
-
-
Grounding for Full Isolation – Use separate returns:
-
IN1_GND → Battery 1 negative
-
IN2_GND → Battery 2 negative
-
OUT_GND → Rack logic ground
Using a common ground for all defeats the isolation barrier and the purpose of redundancy.
-
-
Thermal Derating – Full output available up to 55°C:
-
55°C–60°C: derate all outputs to 90% of rated current
-
60°C–65°C: derate all outputs to 80% of rated current
-
Above 65°C: do not operate
-
-
Spare Sourcing – Production ended in 2018. When purchasing refurbished units, request a comprehensive test report verifying:
-
All outputs at rated current at 25°C and 55°C
-
Input failover functionality (< 5ms switching time)
-
Analog feedback accuracy
-
Relay and digital I/O functionality
-
Surge protection verification
Visually inspect for capacitor bulging, discoloration, or burned traces. The DS3800NRFA1E1D is the ultimate redundant field power solution—prioritize this for critical field device applications requiring maximum capacity, comprehensive monitoring, and advanced diagnostics.
-

SCHNEIDER GV3D22
SIEMENS 6ES7 291-8BA20-0XA0
A-B 1756-TBCH/A


Reviews