Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 100–150 VDC); 24 VDC compatible with external adapter |
| Output Rails | +5 VDC / 12A (main logic), ±15 VDC / 2.5A (each rail, analog circuits), +24 VDC / 1.5A (field/auxiliary) |
| Isolation | Full isolation (1.5kV input‑to‑output, 2.0kV output‑to‑ground) |
| Protection | Overcurrent protection (fixed), short‑circuit protection, transient suppression (4kV), reverse polarity protection, input undervoltage lockout |
| Regulation | Load regulation: ±0.3%; Line regulation: ±0.15%; Ripple: < 25mVpp (+5V), < 15mVpp (±15V) |
| Monitoring | 4 analog feedback channels (voltage and current monitoring for each output rail); 3 digital fault outputs (relay, 24V/1A) for output fault, overtemp, and input status alarms |
| Digital Interface | 2 digital inputs for remote control; 4 digital outputs for system status indication and external alarm signaling |
| Intelligent Control | Onboard microcontroller for power sequencing, load shedding, and diagnostic reporting; communicates with main CPU via backplane |
| Operating Temperature | –30°C to +65°C |
| Form Factor | 6U × 6HP (30mm) – requires 1.5 slots |
| Backplane Connector | Standard VME 96‑pin P1 + reinforced 60‑pin P2 (for additional I/O and high‑current outputs) |
| Status LEDs | 8 indicators: +5V OK (green), +15V OK (green), –15V OK (green), +24V OK (green), FAULT (red), OVTEMP (yellow), COMM ACTIVE (white), SYSTEM OK (green) |
| Certifications | CE, UL 508, CSA Class I Div 2 |
| Efficiency | ~85% at full load |
Critical note: The DS3800NPSY is a system‑level power management board that integrates power conversion with monitoring and control functions. It is physically wider (6HP) than standard 4HP boards and requires 1.5 adjacent slots. This board includes an onboard microcontroller for intelligent power management. Hot‑swapping is not supported.
Key Features & Advantages
-
Integrated Power Management – The DS3800NPSY combines power conversion with intelligent control via an onboard microcontroller. It supports power sequencing, load shedding, and diagnostic reporting directly to the main CPU.
-
Comprehensive Monitoring – Four analog feedback channels provide voltage and current telemetry for all output rails, enabling detailed power health monitoring and load analysis.
-
Multi‑Function Digital I/O – Two digital inputs allow remote control; four digital outputs provide system status indication and external alarm signaling, enabling full integration with plant DCS.
-
Three Fault Relays – Three form‑C relay contacts (24V/1A) provide separate fault indication for output faults, overtemperature, and input status, allowing flexible alarm configuration.
-
Full Isolation – 1.5kV isolation protects sensitive circuits from ground loops and transients.
-
Power Sequencing – The onboard controller can sequence output rails on startup to prevent inrush current issues and ensure proper system initialization.
-
Load Shedding – In the event of input undervoltage, the DS3800NPSY can shed non‑critical loads to maintain power to essential circuits.
-
Backplane Communication – Communicates with the main CPU via the backplane, allowing the CPU to read power supply status and issue control commands.
-
Wide Temperature Range – Extended –30°C to +65°C range and CSA Div 2 certification make the DS3800NPSY suitable for demanding environments.
Typical Application Cases
-
Advanced Main Control Cabinets – Installed in main racks where integrated power management and comprehensive monitoring are required.
-
High‑Reliability I/O Racks – Powers I/O racks with intelligent power control for critical process monitoring and control.
-
Frame 9E Gas Turbine Main Racks – Provides intelligent power management for high‑reliability control systems in large gas turbines.
-
System Integration Projects – Used when integrating Mark IV/V systems with modern DCS where comprehensive power status reporting is required.
-
Legacy Fleet Upgrades – Replaces simpler power boards with a more intelligent solution without changing rack configuration.
Competitive Comparison
| Aspect | DS3800NPSY (GE) | DS3800NPSR1B1B (GE) | DS3800NPSJ1B1C (GE) |
|---|---|---|---|
| Intelligent Control | Yes (microcontroller) | No | No |
| Power Sequencing | Yes | No | No |
| Load Shedding | Yes | No | No |
| +5V Output | 12A | 15A | 22A |
| ±15V Output | 2.5A each | 3A each | 4.5A each |
| Monitoring Channels | 4 (V + I) | 4 (V + I) | 4 (voltage only) |
| Digital Outputs | 4 | 2 | 2 |
| Fault Relays | 3 | 2 | None |
| Backplane Communication | Yes | No | No |
| Isolation | Full (1.5kV) | Full (1.5kV) | Full (1.5kV) |
| Form Factor | 6HP (1.5 slots) | 6HP (1.5 slots) | 8HP (2 slots) |
| Operating Temp | –30°C to +65°C | –30°C to +65°C | –40°C to +70°C |
| Price (refurb) | ~$4,800–$6,800 | ~$4,500–$6,500 | ~$5,500–$7,500 |
The DS3800NPSY is the most intelligent power board in the DS3800 family, offering integrated power management, comprehensive monitoring, and backplane communication in a compact 6HP form factor.
Selection Guidelines & Precautions
-
Application Verification – The DS3800NPSY is designed for integrated power management applications requiring intelligent control. If your application does not require sequencing, load shedding, or backplane communication, simpler boards (NPSJ, NPSR) may be more cost‑effective.
-
Physical Compatibility – The DS3800NPSY is 6HP wide, requiring 1.5 adjacent slots in your Mark IV/V rack. It will not fit in standard 4HP slots and requires an adjacent empty half‑slot position.
-
Backplane Compatibility – Uses both P1 and reinforced P2 connectors. The additional digital I/O and backplane communication are provided through the P2 connector. If your backplane lacks P2 (pre‑2005 racks), these advanced features will be unavailable.
-
Power Budget – Calculate total current draw:
-
+5V: max 12A
-
±15V: max 2.5A each
-
+24V: max 1.5A
Exceeding any output will trigger overcurrent protection and latch that output off.
-
-
Power Sequencing Configuration – The power sequencing parameters (rail order and delay times) are configured via the onboard DIP switches (SW1) or through backplane communication. Factory defaults sequence +5V first, then +15V/−15V, then +24V.
-
Load Shedding Settings – Configure load shedding thresholds via onboard jumpers (JP1‑JP3) to define which outputs are shed and at what input voltage level.
-
Grounding for Full Isolation – Use separate returns:
-
IN_GND → Battery negative
-
OUT_GND → Rack logic ground
-
24V_ISO_GND → Field device common
Using a common ground defeats the isolation barrier.
-
-
Thermal Derating – Full output available up to 55°C:
-
55°C–60°C: derate all outputs to 90% of rated current
-
60°C–65°C: derate all outputs to 80% of rated current
-
Above 65°C: do not operate
-
-
Spare Sourcing – Production ended in 2015. When purchasing refurbished units, request a load test report verifying all outputs at rated current, plus functional verification of power sequencing, load shedding, digital I/O, and backplane communication at 25°C and 55°C. Visually inspect for capacitor bulging, discoloration, or burned traces. The DS3800NPSY is the premier intelligent power management solution for Mark IV/V systems—prioritize this when integrated power control is required.

A-B 1756-TBCH
OMRON E3JM-DS70M4-G
A-B 1747-UIC


Reviews