Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 90–160 VDC); 24 VDC compatible with external adapter |
| Output Rails | +5 VDC / 4A (logic/communication power), +24 VDC / 3A (field sensor/relay power), -24 VDC / 1A (analog circuit bias), ±15 VDC / 1A (signal conditioning) |
| Isolation | Full isolation (1.5kV for all outputs) – improved over baseline NPSM |
| Protection | Overcurrent protection (each output independently protected, adjustable via jumpers), short-circuit protection, transient suppression, reverse polarity protection |
| Monitoring | 2 analog feedback channels for +5V and +24V monitoring; digital fault output (relay, 24V/0.5A) for any output fault |
| Operating Temperature | –30°C to +65°C |
| Form Factor | 6U × 4HP (20mm) – single slot |
| Backplane Connector | Standard VME 96-pin P1 (no P2) |
| Status LEDs | 6 indicators: +5V OK (green), +24V OK (green), -24V OK (green), ±15V OK (green), FAULT (red), OVERTEMP (yellow) |
| Certifications | CE, UL 508, CSA Class I Div 2 |
| Efficiency | ~80% at full load |
Critical note: The DS3800NPSM1E1C is a multi-output auxiliary power board designed for field device power and signal conditioning. It is not suitable as a main rack logic power supply (use NPSJ or NPSE). All outputs are fully isolated (1.5kV), a significant upgrade over baseline NPSM. Hot-swapping is not supported.
Key Features & Advantages
-
Higher Capacity than Baseline NPSM – The DS3800NPSM1E1C offers increased current ratings: +5V at 4A (33% more), +24V at 3A (50% more), -24V at 1A (100% more), and ±15V at 1A (100% more) compared to baseline NPSM.
-
Full Isolation for All Outputs – All outputs are now fully isolated (1.5kV), eliminating ground-loop issues entirely and protecting sensitive control electronics from field device transients—a significant improvement over the baseline NPSM’s partial isolation.
-
Independent Adjustable Protection – Each output has individual overcurrent protection with adjustable thresholds via onboard jumpers, allowing customization for specific field device requirements.
-
Relay Fault Output – A form-C relay contact (24V/0.5A) provides fault indication for any output failure, enabling integration with plant DCS or alarm systems.
-
Dual Monitoring Channels – Two analog feedback channels provide voltage telemetry for +5V and +24V, enabling remote monitoring of critical power rails.
-
Compact Single-Slot Design – Occupies only 4HP, making it ideal for auxiliary cabinets with limited space.
-
Wide Temperature Range – Extended –30°C to +65°C range and CSA Class I Div 2 certification make the DS3800NPSM1E1C suitable for outdoor or hazardous location auxiliary cabinets.
Typical Application Cases
-
Instrumentation Cabinets – Provides multiple voltage rails for field transmitters, pressure sensors, and temperature transducers in auxiliary panels requiring high isolation.
-
Remote I/O Stations – Supplies +5V for communication modules, +24V for field relays, and ±15V for analog signal conditioning in remote I/O racks with demanding isolation requirements.
-
Communication Interface Panels – Powers serial communication converters, fiber optic transceivers, and protocol gateways requiring multiple isolated voltage rails.
-
Signal Conditioning Cabinets – Supplies bias voltages for analog signal isolators, converters, and amplifiers in turbine auxiliary systems.
-
Upgrade from Baseline NPSM – When an older NPSM board fails, the DS3800NPSM1E1C offers a significant performance upgrade (higher capacity, full isolation) without changing rack configuration.
Competitive Comparison
| Aspect | DS3800NPSM1E1C (GE) | DS3800NPSM (baseline) | DS3800NPSE1C1C (GE) |
|---|---|---|---|
| Output Rails | +5V/4A, +24V/3A, -24V/1A, ±15V/1A | +5V/3A, +24V/2A, -24V/0.5A, ±15V/0.5A | +5V/10A only |
| Isolation | Full (1.5kV all outputs) | Partial (24V only) | None |
| Protection | Adjustable per output | Fixed per output | Fixed |
| Feedback Channels | 2 (analog) | 1 | 1 |
| Relay Output | Yes (form-C) | No | No |
| Form Factor | 4HP (1 slot) | 4HP (1 slot) | 4HP (1 slot) |
| Operating Temp | –30°C to +65°C | –25°C to +60°C | –40°C to +70°C |
| CSA Div 2 | Yes | No | Yes |
| Efficiency | ~80% | ~78% | ~84% |
| Price (refurb) | ~$2,400–$3,500 | ~$1,800–$2,800 | ~$2,500–$3,500 |
The DS3800NPSM1E1C is the most capable multi-output auxiliary power board in the NPSM family, offering full isolation, higher capacity, and adjustable protection in a compact 4HP slot.
Selection Guidelines & Precautions
-
Application Verification – The DS3800NPSM1E1C is designed for auxiliary power distribution with multiple isolated outputs. Verify that your application requires the specific combination of +5V, +24V, -24V, and ±15V rails before selecting this board.
-
Power Budget – Calculate the total current draw for each output rail and ensure it does not exceed rated values:
-
+5V: max 4A
-
+24V: max 3A
-
-24V: max 1A
-
±15V: max 1A each
Exceeding any single output will trigger its individual overcurrent protection and latch that output off.
-
-
Protection Threshold Adjustment – Configure the overcurrent thresholds via onboard jumpers (JP1–JP4) based on your field device requirements. The factory defaults are set to 120% of rated current—adjust downward for sensitive devices or upward for devices with high inrush current.
-
Grounding for Full Isolation – To maintain the 1.5kV isolation rating for all outputs, use separate returns for each output rail:
-
OUT_GND (+5V and ±15V return) → Rack logic ground
-
24V_ISO_GND (+24V return) → Field device common
-
N24_ISO_GND (-24V return) → Analog circuit common
Using a common ground for any of these defeats the isolation barrier.
-
-
Thermal Derating – Full output available up to 55°C:
-
55°C–60°C: derate all outputs to 90% of rated current
-
60°C–65°C: derate all outputs to 80% of rated current
-
Above 65°C: do not operate
-
-
Compatibility – The DS3800NPSM1E1C is pin-compatible with all Mark IV backplanes in 4HP slots. No backplane modifications are required.
-
Spare Sourcing – Production ended in 2018. When purchasing refurbished units, request a load test report verifying all four output rails at rated current at 25°C and 55°C. Visually inspect for capacitor bulging, discoloration, or burned traces. The DS3800NPSM1E1C is the preferred NPSM revision for new spares—prioritize this over baseline NPSM when available.

A-B 1784-SD1