GE DS3800NPCE1A1B

¥999.00

The DS3800NPCE1A1B is a revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage AC/DC applications with a solid-state-primary hybrid output configuration. The suffix “1A1B” indicates Revision A firmware with standard 12-bit ADC (±2°C accuracy), extended temperature components (-20°C to +65°C), 3A solid-state outputs5A mechanical relay outputs4 thermocouple input channels, and 2 tachometer input channels.

The DS3800NPCE1A1B is distinguished from the “NPCD” series by its extended temperature range (-20°C to +65°C) while maintaining the higher-current solid-state outputs (3A) and 5A relay outputs.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NPCE1A1B
Power Supply +5V DC @ 4.2A, +15V DC @ 0.8A, -15V DC @ 0.5A
Temperature Inputs 4 thermocouple channels (12-bit ADC, ±2°C accuracy)
SS Outputs 8 solid-state relays, 3A continuous @ 24–48VDC
Relay Outputs 4 mechanical relays, 5A continuous @ 115VAC/30VDC (surge 10A)
Tachometer Inputs 2 channels (up to 10 kHz)
Communication Mark V proprietary parallel backplane bus
Operating Temperature -20°C to +65°C
LED Indicators Power, SS Run (8x green), Relay Run (4x amber), Tach Fail (red x2), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Solid-State-Primary Hybrid + Tachometer Feedback: 8 solid-state DC outputs (3A) + 4 high-current relays (5A) + 2 tachometer inputs on a single board.

  • Higher Solid-State Current (3A): Supports larger DC fans compared to 2A boards.

  • Higher Relay Current (5A): Supports larger AC/DC auxiliary loads.

  • Extended Temperature Range: -20°C to +65°C supports moderately harsh environments.

  • Fan-Dense Design: 8 SS outputs + 4 relay outputs with only 4 temperature inputs.

  • Silent, Maintenance-Free Solid-State Outputs: Unlimited cycle life for DC fans.

  • Relay Auxiliary Outputs: 2500V galvanic isolation for AC/DC auxiliary loads.

  • Fan Speed Verification: Tachometer inputs allow CPU to confirm fan operation.


Typical Application Fields

  • Safety-Critical Fan-Dense Mixed Fan Systems: Where fan failure detection is mandatory.

  • Fan-Dense Mixed Fan Cabinets: Where larger DC fans and high-power AC/DC auxiliary devices coexist.

  • Unheated Shelters & Outdoor Enclosures: -20°C to +65°C range.

  • Moderately Harsh Environments: Where climate control is limited.


Comparison with Related Models

Feature DS3800NPCE1A1B DS3800NPCD DS3800NPAC DS3800NOAA1F1D
SS Outputs 8 × 3A 8 × 3A 8 × 2A 8 × 3A
Relay Outputs 4 × 5A 4 × 5A 4 × 5A 4 × 5A
T/C Inputs 4 4 4 4 + 8 = 12
Tach Inputs 2 channels 2 channels 2 channels 2 channels
ADC 12-bit (±2°C) 12-bit (±2°C) 12-bit (±2°C) 24-bit (±0.5°C)
Operating Temp -20°C to +65°C 0°C to +60°C 0°C to +60°C -40°C to +85°C
Predictive Maintenance No No No Yes
Firmware A A A F
Cost Medium-High Medium-High Medium Ultra-Premium

Selection Recommendations

  • Choose the DS3800NPCE1A1B if:

    • You need 8 solid-state DC outputs (3A) for larger main fans.

    • You also need 4 high-current mechanical relay outputs (5A) for auxiliary devices.

    • You require tachometer feedback for fan speed verification.

    • Your installation requires extended temperature range (-20°C to +65°C).

    • Your cabinet uses 4 temperature sensors for 12 total outputs (fan-dense configuration).

  • Choose the DS3800NPCD if: You need the same features but operate in a climate-controlled environment (0°C to +60°C).

  • Choose the DS3800NOAA1F1D if: You need RTD support, predictive maintenance, and extreme temperature range (-40°C to +85°C).


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • SS Voltage Limit: Do not exceed 48VDC—AC voltages cause catastrophic failure.

  • SS Current Limitation: Rated at 3A continuous. Verify fan current does not exceed this limit.

  • High-Voltage/Current Hazard (Relay): Relay outputs switch 115VAC/5A—lethal. Use proper insulation.

  • Relay Inductive Derating: For inductive loads, derate from 5A to 3.5A or use RC snubbers.

  • Missing T/C Channels: Only 4 thermocouple inputs (channels 1–4). Channels 5–8 are physically absent.

  • Tachometer Wiring: Use shielded twisted-pair cable. Connect shield to designated terminal—not at the fan end.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed—tachometer monitoring disabled in fallback mode.

  • Firmware Compatibility: The DS3800NPCE1A1B is compatible with all Mark V CPU firmware versions (v3.x and above). No specific CPU upgrade is needed.

ABB 3HAC044075-001
ABB 3HAC16831-1
GE IC200CHS022

Reviews

There are no reviews yet.

Be the first to review “GE DS3800NPCE1A1B”

Your email address will not be published. Required fields are marked *

Post comment