The DS3800NOCA1B1B is a revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage DC applications with a solid-state-primary hybrid output configuration. The suffix “1B1B” indicates Revision B firmware with enhanced 16-bit ADC (±1°C accuracy), extended temperature components (-20°C to +65°C), 2A solid-state outputs3A mechanical relay outputs, and 4 thermocouple input channels—with no tachometer feedback.

The DS3800NOCA1B1B is a direct upgrade from the base model, offering improved temperature accuracy (16-bit vs. 12-bit ADC), extended temperature range (-20°C to +65°C), and Revision B firmware enhancements.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NOCA1B1B
Power Supply +5V DC @ 3.6A, +15V DC @ 0.6A, -15V DC @ 0.4A
Temperature Inputs 4 thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy)
SS Outputs 8 solid-state relays, 2A continuous @ 24–48VDC
Relay Outputs 4 mechanical relays, 3A continuous @ 115VAC/30VDC (surge 5A)
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature -20°C to +65°C
LED Indicators Power, SS Run (8x green), Relay Run (4x amber), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Solid-State-Primary Hybrid Architecture: 8 solid-state DC outputs + 4 mechanical relays on a single board.

  • Fan-Dense Design: 8 SS outputs + 4 relay outputs with only 4 temperature inputs—optimized for single-zone cooling.

  • Improved Temperature Accuracy (16-bit ADC): ±1°C accuracy—double the precision of the base 12-bit (±2°C) model.

  • Extended Temperature Range: -20°C to +65°C supports moderately harsh environments.

  • Enhanced Cold-Junction Compensation (Revision B): Improved temperature measurement reliability.

  • Silent, Maintenance-Free Solid-State Outputs: Unlimited cycle life for DC fans.

  • Relay Auxiliary Outputs: 2500V galvanic isolation for AC/DC auxiliary loads.

  • Low EMI Emissions: Solid-state outputs minimize interference with sensitive cards.


Typical Application Fields

  • Fan-Dense Mixed Fan Cabinets: Where DC fans are primary with AC/DC auxiliary devices.

  • Unheated Shelters & Outdoor Enclosures: -20°C to +65°C range.

  • Moderately Harsh Environments: Where climate control is limited.


Comparison with Related Models

Feature DS3800NOCA1B1B DS3800NOCA (Base) DS3800NOAA DS3800NMSA1B1A
SS Outputs 8 × 2A 8 × 2A 8 × 2A 8 × 2A
Relay Outputs 4 × 3A 4 × 3A 4 × 3A 4 × 3A
T/C Inputs 4 4 4 8
Tach Inputs None None 2 channels None
ADC Resolution 16-bit (±1°C) 12-bit (±2°C) 12-bit (±2°C) 16-bit (±1°C)
Operating Temp -20°C to +65°C 0°C to +60°C 0°C to +60°C 0°C to +60°C
Firmware B A/B A/B B
Cost Medium Medium Medium Medium

Selection Recommendations

  • Choose the DS3800NOCA1B1B if:

    • You need 8 solid-state DC outputs (2A) for main fans.

    • You also need 4 mechanical relay outputs (AC/DC) for auxiliary devices.

    • You want improved temperature accuracy (±1°C).

    • Your installation requires extended temperature range (-20°C to +65°C).

    • Your cabinet uses 4 temperature sensors for 12 total outputs (fan-dense configuration).

    • You do not require tachometer feedback.

  • Choose the DS3800NOAA if: You need tachometer feedback with the same hybrid outputs.

  • Choose the DS3800NMSA1B1A if: You need 8 thermocouple inputs with the same hybrid outputs.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • SS Voltage Limit: Do not exceed 48VDC—AC voltages cause catastrophic failure.

  • High-Voltage/Current Hazard (Relay): Relay outputs switch 115VAC/3A—lethal. Use proper insulation.

  • Relay Inductive Derating: For inductive loads, derate from 3A to 2A or use RC snubbers.

  • Missing T/C Channels: Only 4 thermocouple inputs (channels 1–4). Channels 5–8 are physically absent.

  • No Tachometer Inputs: Do not connect speed sensors.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed.

  • Firmware Compatibility: Revision B firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x, the enhanced ADC accuracy may be partially disabled—confirm compatibility before purchasing.

ABB 3ADT 629 039 P0001
A-B 800T-D9D2
A-B 1489-M1D005