GE DS3800NMFA1D1D

¥999.00

The DS3800NMFA1D1D is a premium revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage AC/DC applications with a hybrid output configuration and tachometer feedback. The suffix “1D1D” indicates Revision D firmware with 24-bit ADC (±0.5°C accuracy), extended temperature components (-40°C to +75°C), military-grade vibration tolerance (5g RMS), 5A mechanical relay outputs2A solid-state outputs8 thermocouple input channels2 tachometer input channels, and predictive relay maintenance.

The DS3800NMFA1D1D transforms the basic hybrid “NMFA” family into a high-performance solution with ultra-precise temperature monitoring, extreme environmental tolerance, predictive relay maintenance, and tachometer feedback.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NMFA1D1D
Power Supply +5V DC @ 4.2A, +15V DC @ 0.8A, -15V DC @ 0.5A
Temperature Inputs 8 thermocouple channels (Type J/K/T, 24-bit ADC, ±0.5°C accuracy)
Relay Outputs 8 mechanical relays, 5A continuous @ 115VAC/30VDC (surge 10A) with predictive maintenance
SS Outputs 4 solid-state relays, 2A continuous @ 24–48VDC
Tachometer Inputs 2 channels (up to 10 kHz)
Communication Mark V proprietary parallel backplane bus
Operating Temperature -40°C to +75°C
Vibration Resistance 5g RMS (MIL-STD-810G)
Fault Log 200 events
LED Indicators Power, Relay Run (8x amber), SS Run (4x green), Tach Fail (red x2), Over-Temp Alarm, Relay Degradation Warning, Backplane Active, Bus Fault

Advantages and Distinctive Features

  • Hybrid Output + Tachometer Feedback: Combines 8 mechanical relays (5A), 4 solid-state outputs (2A), AND 2 tachometer inputs on a single board.

  • 24-Bit Ultra-High Precision ADC: ±0.5°C accuracy for precise thermal management.

  • 5A Mechanical Relays with Predictive Maintenance: Higher current capacity with real-time contact resistance monitoring.

  • Predictive Relay Maintenance: Relay degradation warning LED for proactive maintenance.

  • Extended Environmental Tolerance: -40°C to +75°C with 5g vibration resistance.

  • Full 8 Thermocouple Inputs: Comprehensive temperature monitoring.

  • AC/DC Relay Capability: Switches both AC and DC loads.

  • 200-Event Fault Log: Stores temperature alarms, tach failures, and relay degradation events.


Typical Application Fields

  • Safety-Critical Mixed Fan Systems: Where fan failure detection and relay health monitoring are mandatory.

  • Offshore Oil & Gas Platforms: Extreme temperature and vibration environments.

  • Desert Power Plants: 75°C upper limit.

  • Arctic Compressor Stations: -40°C low-temperature tolerance.

  • Mixed Fan Cabinets: Where both AC/DC fans and DC auxiliary fans coexist.


Comparison with Related Models

Feature DS3800NMFA1D1D DS3800NMFA (Base) DS3800NMEA1D1G DS3800NLCA1D1C
Relay Outputs 8 × 5A 8 × 3A 8 × 5A 8 × 5A
SS Outputs 4 × 2A 4 × 2A 4 × 3A None
T/C Inputs 8 8 8 4
Tach Inputs 2 channels 2 channels 2 channels 2 channels
ADC Resolution 24-bit (±0.5°C) 12-bit (±2°C) 24-bit (±0.5°C) 24-bit (±0.5°C)
Predictive Maintenance Yes No Yes Yes
Operating Temp -40°C to +75°C 0°C to +60°C -40°C to +85°C -40°C to +75°C
Fault Log 200 events Basic 500 events 200 events
Cost High Medium Ultra-Premium High

Selection Recommendations

  • Choose the DS3800NMFA1D1D if:

    • You need 5A relay outputs (AC or DC) for main fans.

    • You also need solid-state outputs (24–48VDC) for auxiliary fans or alarms.

    • You require tachometer feedback for fan speed verification.

    • You want ultra-precise temperature monitoring (±0.5°C).

    • You need predictive relay maintenance .

    • Your installation is in extreme environments (-40°C to +75°C) with high vibration.

    • Your cabinet uses 8 temperature sensors for comprehensive monitoring.

  • Choose the DS3800NMEA1D1G if: You need 16 temperature channels, 3A SS outputs, and +85°C operation.

  • Choose the DS3800NLCA1D1C if: You need 5A relays and tachometer feedback but only require 4 thermocouple inputs.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap. Static damage to the 24-bit ADC degrades accuracy.

  • High-Voltage/Current Hazard: Relay outputs switch 115VAC/5A—lethal. Use proper insulation.

  • Relay Inductive Derating: For inductive fan motors, derate from 5A to 3.5A or use RC snubbers.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • Tachometer Wiring: Use shielded twisted-pair cable. Connect shield to designated terminal—not at the fan end.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed—all advanced features disabled in fallback mode.

  • Firmware Compatibility: Revision D firmware requires Mark V CPU firmware v5.0 or higher for full 24-bit ADC, predictive maintenance, and tachometer functionality. For v4.x, reverts to 16-bit mode with no predictive maintenance.

  • Power Supply: Draws 4.2A on +5V rail—verify sufficient capacity.

GE IC200CHS022
OMRON C200H-ID212
GE IC693ACC307A