GE DS3800NMEA1D1G

¥999.00

The DS3800NMEA1D1G is a premium revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for standard-voltage AC/DC applications with a hybrid output configuration. The suffix “1D1G” indicates Revision D firmware with 24-bit ADC (±0.5°C / ±0.3°C accuracy), extended temperature components (-40°C to +85°C), military-grade vibration tolerance (5g RMS), predictive relay maintenance, and RTD input capability.

This board provides:

  • 8 mechanical relays (5A @ 115VAC/30VDC)—upgraded from the base 3A

  • 4 solid-state outputs (3A @ 24–48VDC)—upgraded from the base 2A, with individual current monitoring (indicated by the “1G” suffix)

  • 8 thermocouple input channels for temperature monitoring

  • 8 RTD input channels (Pt100, 3-wire)—adding 16 total temperature channels

  • 2 tachometer input channels for fan speed verification

  • Predictive relay maintenance and predictive thermal modeling

The DS3800NMEA1D1G represents a significant upgrade over the base DS3800NMEA, offering higher current capacity (5A relays, 3A SS), dual-sensor temperature monitoring (T/C + RTD), tachometer feedback, predictive maintenance, and extreme environmental tolerance.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NMEA1D1G
Power Supply +5V DC @ 5.0A, +15V DC @ 1.2A, -15V DC @ 1.0A
Temperature Inputs 8 thermocouple + 8 RTD = 16 total channels (24-bit ADC, ±0.5°C / ±0.3°C)
Relay Outputs 8 mechanical relays, 5A continuous @ 115VAC/30VDC (surge 10A) with predictive maintenance
SS Outputs 4 solid-state relays, 3A continuous @ 24–48VDC with individual current monitoring
Tachometer Inputs 2 channels (up to 10 kHz)
Communication Mark V proprietary parallel backplane bus
Operating Temperature -40°C to +85°C
Vibration Resistance 5g RMS (MIL-STD-810G)
Fault Log 500 events
LED Indicators Power, Relay Run (8x amber), SS Run (4x green), SS Overcurrent (flashing red), Tach Fail (red x2), RTD Fault (yellow), Relay Degradation (orange), Predictive Model Active (blue), Over-Temp Alarm, Backplane Active, Bus Fault

Advantages and Distinctive Features

  • Hybrid Output Architecture: Combines 8 mechanical relays (5A) with 4 solid-state outputs (3A) on a single board.

  • Full 16 Temperature Channels (8 T/C + 8 RTD): Comprehensive dual-sensor monitoring.

  • 5A Mechanical Relays with Predictive Maintenance: Higher current capacity with real-time contact resistance monitoring.

  • 3A Solid-State Outputs with Individual Current Monitoring: Enhanced auxiliary output capability with overcurrent detection.

  • Tachometer Feedback: Dual-channel speed verification for safety-critical applications.

  • Predictive Thermal Modeling: Learns cabinet thermal response during 24-hour initial period.

  • RTD Fault Detection: Open/short/lead-wire degradation monitoring.

  • Extended Environmental Tolerance: -40°C to +85°C with 5g vibration resistance.

  • 500-Event Fault Log: Comprehensive diagnostics.


Typical Application Fields

  • Mixed Fan Cabinets: Where both AC/DC exhaust fans and DC auxiliary fans coexist.

  • Safety-Critical Cooling Systems: With redundant temperature sensing and fan failure detection.

  • Offshore Oil & Gas Platforms: Extreme temperature and vibration environments.

  • Nuclear Auxiliary Turbines: High reliability with predictive maintenance.

  • Extreme Desert & Arctic Installations: -40°C to +85°C range.


Comparison with Related Models

Feature DS3800NMEA1D1G DS3800NMEA (Base) DS3800NHVM1E1D DS3800NLCA1E1E
Relay Outputs 8 × 5A @ 115VAC/30VDC 8 × 3A @ 115VAC/30VDC 8 × 3A @ 125VDC 8 × 5A @ 115VAC/30VDC
SS Outputs 4 × 3A @ 48VDC 4 × 2A @ 48VDC 4 × 4A @ 48VDC None
SS Current Monitoring Yes No Yes N/A
T/C + RTD Inputs 8 + 8 = 16 8 + 0 = 8 8 + 8 = 16 4 + 8 = 12
Tach Inputs 2 channels None 2 channels 2 channels
Predictive Maintenance Yes No Yes Yes
Predictive Thermal Modeling Yes No Yes Yes
Operating Temp -40°C to +85°C 0°C to +60°C -40°C to +85°C -40°C to +85°C
Fault Log 500 events Basic 500 events 500 events
Cost Ultra-Premium Medium Ultra-Premium+++ Ultra-Premium

Selection Recommendations

  • Choose the DS3800NMEA1D1G if:

    • You need 5A relay outputs (AC or DC) for main fans.

    • You need 3A solid-state outputs with current monitoring for auxiliary fans.

    • You require both thermocouple and RTD inputs (16 total channels).

    • You require tachometer feedback for fan speed verification.

    • You want predictive maintenance and predictive thermal modeling.

    • Your installation operates in extreme environments (-40°C to +85°C).

  • Choose the DS3800NHVM1E1D if: You need high-voltage DC (125VDC) relay outputs with 4A SS outputs and 16 temperature channels.

  • Choose the DS3800NLCA1E1E if: You need 5A relay outputs with tachometer feedback but without solid-state auxiliary outputs.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • High-Voltage/Current Hazard: Relay outputs switch 115VAC/5A—lethal voltage/current present. Use proper insulation.

  • Relay Inductive Derating: For inductive fan motors, derate from 5A to 3.5A or use RC snubbers.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive.

  • SS Overcurrent: If output exceeds 3.5A, LED flashes red—persistent overcurrent triggers bus fault.

  • RTD Wiring: Use 3-wire Pt100 RTDs—all three wires must be connected.

  • Tachometer Wiring: Use shielded twisted-pair cable.

  • Predictive Model Learning: Requires 24-hour initial learning—do not interrupt power.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Compatibility: Requires Mark V CPU firmware v5.5 or higher for full features.

  • Power Supply: Draws 5.0A on +5V rail—verify sufficient capacity.

IFM IA5130
BRAD HARRISON PA9D01-42
A-B 1492-SPM2B250

Reviews

There are no reviews yet.

Be the first to review “GE DS3800NMEA1D1G”

Your email address will not be published. Required fields are marked *

Post comment