GE DS3800NHVL1C1C

¥999.00

The DS3800NHVL1C1C is a premium revision of General Electric’s Mark V series Fan/Exhaust Control board, engineered for high-voltage DC applications with a hybrid output configuration and dual-sensor temperature monitoring. The suffix “1C1C” indicates Revision C firmware with 24-bit ADC (±0.5°C / ±0.3°C accuracy), extended temperature components (-40°C to +75°C), military-grade vibration tolerance (5g RMS), and predictive relay maintenance. Critically, the “1C” suffix also indicates thermocouple input channels reduced to 4 (instead of the standard 8), while retaining 8 RTD input channels for a total of 12 temperature channels.

This board provides:

  • 8 mechanical relays (2A @ 125VDC) for high-voltage exhaust fans

  • 4 solid-state outputs (3A @ 24–48VDC) for high-current auxiliary fans or alarms

  • 4 thermocouple input channels for temperature monitoring

  • 8 RTD input channels (Pt100, 3-wire) for high-precision temperature monitoring—adding 12 total temperature channels

  • 2 tachometer input channels for fan speed verification

The DS3800NHVL1C1C is optimized for fan-dense high-voltage cabinets where RTD sensors are preferred over thermocouples, or where fewer T/C points are required. The reduced thermocouple count (4 channels) reallocates hardware resources to enhance RTD signal conditioning and noise filtering.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NHVL1C1C
Power Supply +5V DC @ 4.8A, +15V DC @ 0.9A, -15V DC @ 0.7A
Temperature Inputs 4 thermocouple + 8 RTD = 12 total channels (24-bit ADC, ±0.5°C / ±0.3°C)
Relay Outputs 8 mechanical relays, 2A continuous @ 125VDC (surge 4A) with predictive maintenance
SS Outputs 4 solid-state relays, 3A continuous @ 24–48VDC
Tachometer Inputs 2 channels with enhanced filtering (up to 10 kHz)
Communication Mark V proprietary parallel backplane bus
Operating Temperature -40°C to +75°C
Vibration Resistance 5g RMS (MIL-STD-810G)
Fault Log 500 events
LED Indicators Power, Relay Run (8x amber), SS Run (4x green), Tach Fail (red x2), RTD Fault (yellow), Relay Degradation Warning (orange), Over-Temp Alarm, Backplane Active, Bus Fault

Advantages and Distinctive Features

  • Dual Temperature Sensor Support (4 T/C + 8 RTD): 12 total temperature channels—optimized for RTD-heavy applications.

  • 24-Bit Ultra-High Precision ADC: ±0.5°C for thermocouples, ±0.3°C for RTDs—the highest accuracy in the Mark V high-voltage lineup.

  • Predictive Relay Maintenance: Real-time contact resistance monitoring with relay degradation warning—critical for high-voltage DC applications.

  • Hybrid Output + Tachometer Feedback: Combines 8 high-voltage DC relay outputs, 4 high-current solid-state outputs, AND 2 tachometer inputs.

  • Higher Solid-State Current (3A): Supports larger 48VDC auxiliary fans.

  • Higher Relay Current (2A @ 125VDC): Supports more powerful 110–125VDC fans.

  • RTD Fault Detection: Continuous monitoring for open-circuit, short-circuit, or lead-wire degradation.

  • Extended Environmental Tolerance: -40°C to +75°C with 5g vibration resistance.

  • 500-Event Fault Log: Comprehensive diagnostics.


Typical Application Fields

  • RTD-Heavy High-Voltage Cabinets: Where RTD sensors are preferred over thermocouples, or where fewer T/C points are required.

  • Safety-Critical 125VDC Cooling Systems: With redundant RTD-based temperature monitoring.

  • Offshore Oil & Gas Platforms: Extreme temperature and vibration environments.

  • Nuclear Auxiliary Turbines: High reliability with RTD-based monitoring.

  • Arctic & Desert Installations: -40°C to +75°C range.

  • Legacy Turbine Installations: Where RTD sensors are the primary temperature measurement method.


Comparison with Related Models

Feature DS3800NHVL1C1C DS3800NHVL (Base) DS3800NHVK DS3800NHVJ
Relay Outputs 8 × 2A @ 125VDC 8 × 2A @ 125VDC 8 × 2A @ 125VDC 8 × 2A @ 125VDC
SS Outputs 4 × 3A @ 48VDC 4 × 3A @ 48VDC 4 × 3A @ 48VDC 4 × 3A @ 48VDC
Tach Inputs 2 channels 2 channels 2 channels 2 channels
T/C Inputs 4 channels 8 channels 8 channels 8 channels
RTD Inputs 8 channels 8 channels 8 channels None
Total Temp Channels 12 16 16 8
ADC Resolution 24-bit (±0.5/0.3°C) 24-bit (±0.5/0.3°C) 16-bit (±1/0.5°C) 16-bit (±1°C)
Predictive Maintenance Yes Yes No No
RTD Fault Detection Yes Yes Yes No
Operating Temp -40°C to +75°C -40°C to +75°C 0°C to +60°C 0°C to +60°C
Vibration 5g RMS 5g RMS 1g RMS 1g RMS
Fault Log 500 events 500 events Basic Basic
Cost Ultra-Premium Ultra-Premium Very High High

Selection Recommendations

  • Choose the DS3800NHVL1C1C if:

    • You need 125VDC relay outputs with 2A current capacity and predictive maintenance.

    • You need higher-current solid-state outputs (3A @ 48VDC) for larger auxiliary fans.

    • You require RTD inputs (8 channels) but only need 4 thermocouple inputs (12 total channels).

    • You require RTD fault detection for sensor integrity monitoring.

    • You require tachometer feedback for fan speed verification.

    • You need ultra-precise temperature monitoring (±0.5°C / ±0.3°C).

    • Your installation is in extreme environments (-40°C to +75°C) with high vibration.

    • You need 500-event fault logging.

  • Choose the full DS3800NHVL (base) if: You need both 8 thermocouple and 8 RTD inputs (16 total channels) with the same advanced features.

  • Choose the DS3800NHVK if: You need 16 temperature channels but operate in a climate-controlled environment and do not require predictive maintenance.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap. Static damage to the 24-bit ADC degrades accuracy.

  • High-Voltage Hazard: Relay outputs switch 125VDC—lethal voltage present on terminals. Observe all high-voltage safety procedures. Use wiring rated for ≥125VDC.

  • Missing Thermocouple Channels: The DS3800NHVL1C1C has only 4 thermocouple inputs (channels 1–4). Channels 5–8 are physically absent and will not function—do not attempt to connect T/C sensors to these positions.

  • RTD Wiring: Use 3-wire Pt100 RTDs. All three wires must be connected. Open/short circuits trigger the yellow “RTD Fault” LED.

  • RTD Lead Resistance: Use wire with resistance ≤10Ω per lead for accurate measurements.

  • DC Polarity (Relay): Relay outputs are DC only—observe correct polarity.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • Tachometer Wiring: Use shielded twisted-pair cable. Connect shield to designated terminal—not at the fan end.

  • Relay Current Limitation: Rated at 2A continuous @ 125VDC. Verify fan current does not exceed this limit.

  • SS Current Limitation: Rated at 3A continuous @ 24–48VDC. At 75°C, derate to 2.2A.

  • Inductive Load Derating (Relay): Derate to 1.5A or use external RC snubbers (rated for 125VDC).

  • No AC Connection: Do not connect AC loads to either output type.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed—all advanced features disabled in fallback mode.

  • Firmware Compatibility: The DS3800NHVL1C1C requires Mark V CPU firmware v5.0 or higher for full 24-bit ADC, predictive maintenance, and RTD support. For v4.x, the board reverts to 16-bit mode with no predictive maintenance.

  • Power Supply: Draws 4.8A on +5V rail—verify sufficient capacity. A power supply upgrade may be required.

GE IC693CHS398G
GE IC693CHS392J
SIEMENS 6ES72350KD220XA8