GE DS3800NHVH1B1B

¥999.00

The DS3800NHVH1B1B is a revision of General Electric’s Mark V series Fan/Exhaust Control board, engineered for high-voltage DC applications with a hybrid output configuration and tachometer feedback. The suffix “1B1B” indicates Revision B firmware with enhanced 16-bit ADC (±1°C accuracy), extended temperature components (-20°C to +65°C), and the hybrid + tachometer architecture. This board provides:

  • 8 mechanical relays (2A @ 125VDC) for high-voltage exhaust fans

  • 4 solid-state outputs (2A @ 24–48VDC) for low-voltage circulating fans or alarms

  • 8 thermocouple input channels for temperature monitoring

  • 2 tachometer input channels for fan speed verification

The DS3800NHVH1B1B combines the higher relay current capacity (2A @ 125VDC) of the “NHVH” series with improved temperature accuracy (16-bit ADC) and an extended operating temperature range (-20°C to +65°C).

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NHVH1B1B
Power Supply +5V DC @ 3.8A, +15V DC @ 0.6A, -15V DC @ 0.4A
Temperature Inputs 8 differential thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy)
Relay Outputs 8 mechanical relays, 2A continuous @ 125VDC (surge 4A)
SS Outputs 4 solid-state relays, 2A continuous @ 24–48VDC
Tachometer Inputs 2 channels with improved debounce filtering (up to 10 kHz)
Communication Mark V proprietary parallel backplane bus
Operating Temperature -20°C to +65°C
LED Indicators Power, Relay Run (8x amber), SS Run (4x green), Tach Fail (red x2), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Hybrid Output + Tachometer Feedback: Combines 8 high-voltage DC relay outputs (125VDC), 4 low-voltage solid-state outputs, AND 2 tachometer inputs on a single board.

  • Higher Relay Current (2A @ 125VDC): Supports more powerful 110–125VDC fans.

  • Improved Temperature Accuracy (16-bit ADC): ±1°C accuracy—double the precision of the base 12-bit (±2°C) model.

  • Extended Temperature Range: -20°C to +65°C supports moderately harsh environments.

  • Enhanced Tachometer Debounce Filtering (Revision B): Reduces false speed failure alarms.

  • Solid-State Auxiliary Outputs: Silent, maintenance-free switching for low-voltage fans or alarms.


Typical Application Fields

  • Safety-Critical 125VDC Cooling Systems: Where fan failure must be detected immediately.

  • High-Voltage Industrial Fan Systems: 110–125VDC exhaust fans with low-voltage auxiliary controls and speed monitoring.

  • Military & Naval Applications: 125VDC systems in shipboard environments.

  • Unheated Shelters & Outdoor Enclosures: -20°C to +65°C range.

  • Legacy Turbine Installations: Older systems using 125VDC fan motors.


Comparison with Related Models

Feature DS3800NHVH1B1B DS3800NHVH (Base) DS3800NHVF1B1A DS3800NHVB
Relay Outputs 8 × 2A @ 125VDC 8 × 2A @ 125VDC 8 × 1A @ 250VDC 8 × 2A @ 125VDC
SS Outputs 4 × 2A @ 48VDC 4 × 2A @ 48VDC 4 × 2A @ 48VDC None
Tach Inputs 2 channels 2 channels 2 channels None
ADC Resolution 16-bit (±1°C) 12-bit (±2°C) 16-bit (±1°C) 12-bit (±2°C)
Enhanced Tach Filter Yes (Rev B) No Yes (Rev B) N/A
Operating Temp -20°C to +65°C 0°C to +60°C 0°C to +60°C 0°C to +60°C
Firmware B A/B B A/B
Cost High High Medium-High Medium

Selection Recommendations

  • Choose the DS3800NHVH1B1B if:

    • You need 125VDC relay outputs with 2A current capacity for more powerful fans.

    • You also need low-voltage solid-state outputs (24–48VDC) for auxiliary fans or alarms.

    • You require tachometer feedback for fan speed verification.

    • You want improved temperature accuracy (±1°C) and enhanced tachometer filtering.

    • Your installation requires extended temperature range (-20°C to +65°C).

  • Choose the DS3800NHVF1B1A if: You need 250VDC relay outputs (1A) with the same hybrid + tachometer features.

  • Choose the DS3800NHVB if: You need 125VDC relay outputs (2A) without solid-state auxiliary outputs or tachometer feedback.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • High-Voltage Hazard: Relay outputs switch 125VDC—lethal voltage present on terminals. Observe all high-voltage safety procedures. Use wiring rated for ≥125VDC.

  • DC Polarity (Relay): Relay outputs are DC only—observe correct polarity.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • Tachometer Wiring: Use shielded twisted-pair cable. The enhanced debounce filtering reduces noise sensitivity, but proper grounding is still essential.

  • Relay Current Limitation: Rated at 2A continuous @ 125VDC. Verify fan current does not exceed this limit.

  • SS Current Limitation: Rated at 2A continuous @ 24–48VDC.

  • Inductive Load Derating (Relay): Derate to 1.5A or use external RC snubbers (rated for 125VDC).

  • No AC Connection: Do not connect AC loads to either output type.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed—tachometer monitoring disabled in fallback mode.

  • Firmware Compatibility: Revision B firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x, the enhanced ADC accuracy and tachometer filtering may be partially disabled—confirm compatibility before purchasing.

A-B 1756-RMC1
A-B 1756-CPR2
OMRON S8FS-G10024C