GE DS3800NHVE1C1A

¥999.00

The DS3800NHVE1C1A is a revision of General Electric’s Mark V series Fan/Exhaust Control board, designed for high-voltage DC applications with a hybrid output configuration. The suffix “1C1A” indicates Revision C firmware with enhanced 16-bit ADC (±1°C accuracy), standard temperature components (0°C to +60°C), and the hybrid output architecture. This board provides:

  • 8 mechanical relays (1A @ 250VDC) for high-voltage exhaust fans

  • 4 solid-state outputs (2A @ 24–48VDC) for low-voltage circulating fans or alarms

  • 8 thermocouple input channels for temperature monitoring

The DS3800NHVE1C1A builds upon the “1B1A” variant with Revision C firmware’s improved cold-junction compensation and enhanced noise filtering on the ADC inputs, providing more stable temperature readings in electrically noisy environments.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NHVE1C1A
Power Supply +5V DC @ 3.6A, +15V DC @ 0.6A, -15V DC @ 0.4A
Temperature Inputs 8 differential thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy)
Relay Outputs 8 mechanical relays, 1A continuous @ 250VDC (surge 2A)
SS Outputs 4 solid-state relays, 2A continuous @ 24–48VDC
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature 0°C to +60°C
LED Indicators Power, Relay Run (8x amber), SS Run (4x green), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Hybrid Output Architecture: Combines 8 high-voltage DC relay outputs (250VDC) with 4 low-voltage solid-state outputs (24–48VDC) on a single board.

  • Improved Cold-Junction Compensation (Revision C): Enhanced temperature measurement stability in fluctuating ambient conditions.

  • Enhanced Noise Filtering: Improved ADC input filtering for stable readings in high-EMI environments.

  • 250VDC Relay Capability: Supports high-voltage exhaust fans for specialized industrial, railway, or turbine applications.

  • Solid-State Auxiliary Outputs: Silent, maintenance-free switching for low-voltage circulating fans or alarms.


Typical Application Fields

  • High-Voltage Industrial Fan Systems: 220–250VDC exhaust fans with low-voltage auxiliary controls.

  • Railway and Traction Applications: High-voltage DC cooling with 24VDC control circuits.

  • Specialized Turbine Installations: Mixed high-voltage and low-voltage fan systems.

  • High-EMI Environments: Where noise filtering provides more stable temperature readings.


Comparison with Related Models

Feature DS3800NHVE1C1A DS3800NHVE1B1A DS3800NHVE1A1A DS3800NHVD1C1B
Relay Outputs 8 × 1A @ 250VDC 8 × 1A @ 250VDC 8 × 1A @ 250VDC 8 × 1A @ 250VDC
SS Outputs 4 × 2A @ 48VDC 4 × 2A @ 48VDC 4 × 2A @ 48VDC None
ADC Resolution 16-bit (±1°C) 16-bit (±1°C) 12-bit (±2°C) 16-bit (±1°C)
Enhanced CJC Yes (Rev C) No No Yes (Rev C)
Noise Filtering Yes (Rev C) No No Yes (Rev C)
Operating Temp 0°C to +60°C 0°C to +60°C 0°C to +60°C -20°C to +65°C
Firmware C B A C
Cost Medium-High Medium Medium Medium-High

Selection Recommendations

  • Choose the DS3800NHVE1C1A if:

    • You need 250VDC relay outputs for high-voltage exhaust fans.

    • You also need low-voltage solid-state outputs (24–48VDC) for auxiliary fans or alarms.

    • You want improved temperature accuracy (±1°C) with enhanced cold-junction compensation.

    • Your installation is in a high-EMI environment requiring stable temperature readings.

    • You have a climate-controlled environment (0°C to +60°C).

  • Choose the DS3800NHVE1B1A if: You need the same hybrid outputs and accuracy but do not require enhanced CJC or noise filtering.

  • Choose the DS3800NHVD1C1B if: You need 250VDC relay outputs with improved accuracy and extended temperature range but do not require solid-state auxiliary outputs.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • Extreme High-Voltage Hazard: Relay outputs switch 250VDC—lethal voltage present on terminals. Observe all high-voltage safety procedures. Use wiring rated for ≥250VDC.

  • DC Polarity (Relay): Relay outputs are DC only—observe correct polarity.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • Relay Current Limitation: Rated at 1A continuous @ 250VDC. Verify fan current does not exceed this limit.

  • SS Current Limitation: Rated at 2A continuous @ 24–48VDC.

  • Inductive Load Derating (Relay): Derate to 0.75A or use external RC snubbers (rated for 250VDC).

  • No AC Connection: Do not connect AC loads to either output type.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed.

  • Firmware Compatibility: Revision C firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x, the enhanced ADC features may be partially disabled—confirm compatibility before purchasing.

A-B 1794-TBN
Schneider MA0185100
ABB TU810V1

Reviews

There are no reviews yet.

Be the first to review “GE DS3800NHVE1C1A”

Your email address will not be published. Required fields are marked *