GE DS3800NGTA1F1E

¥999.00

The DS3800NGTA1F1E is a flagship revision of General Electric’s Mark V series Fan/Exhaust Control board. The suffix “1F1E” indicates Revision F firmware with 24-bit ADC (±0.5°C accuracy), extended temperature components (-40°C to +85°C), military-grade vibration tolerance (5g RMS), 8A mechanical relay outputs8 thermocouple input channels, and no tachometer feedback.

This board represents the pinnacle of the “NGTA” family, combining the highest relay current (8A), ultra-precise temperature monitoring, predictive thermal modeling, predictive relay maintenance, and an extended +85°C operating limit—all without the complexity of tachometer feedback.

Category:

Description

Key Technical Parameters

Parameter Specification
Full Model DS3800NGTA1F1E
Power Supply +5V DC @ 4.5A, +15V DC @ 0.9A, -15V DC @ 0.6A
Temperature Inputs 8 thermocouple channels (Type J/K/T, 24-bit ADC, ±0.5°C accuracy)
Fan Outputs 8 mechanical relays, 8A continuous @ 250VAC/30VDC (surge 15A)
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature -40°C to +85°C
Vibration Resistance 5g RMS (MIL-STD-810G)
Fault Log 500 events
LED Indicators Power, Fan Run (8x amber), Over-Temp Alarm, Relay Degradation, Predictive Model Active, Backplane Active, Bus Fault

Advantages and Distinctive Features

  • 8A Mechanical Relays: Highest current capacity in the “NGTA” family—supports 1HP AC fans.

  • Extended +85°C Operation: Surpasses the +75°C limit for extreme environments.

  • Predictive Thermal Modeling (Revision F): Learns cabinet thermal response during 24-hour initial period, reducing temperature overshoot by up to 50%.

  • Predictive Relay Maintenance: Real-time contact resistance monitoring with relay degradation warning.

  • 24-Bit Ultra-High Precision ADC: ±0.5°C accuracy for precise thermal management.

  • 500-Event Fault Log: Comprehensive diagnostics.

  • Silver-Alloy Relay Contacts: Superior resistance to welding and pitting.

  • AC/DC Output Capability: Switches both AC and DC loads.


Typical Application Fields

  • Extreme Desert Solar-Thermal Plants: +85°C ambient environments.

  • Engine Rooms and Turbine Enclosures: High-temperature, high-vibration areas.

  • Offshore Oil & Gas Platforms: Extreme conditions with AI-driven cooling.

  • Arctic Compressor Stations: -40°C low-temperature tolerance.

  • Safety-Critical Cooling Systems: Where relay health monitoring is mandatory.


Comparison with Related Models

Feature DS3800NGTA1F1E DS3800NGTA1E1D DS3800NGTA1D1D DS3800NFEE1E1E
Relay Current 8A 5A 5A 8A
ADC Resolution 24-bit (±0.5°C) 24-bit (±0.5°C) 24-bit (±0.5°C) 24-bit (±0.5°C)
Predictive Maintenance Yes Yes Yes Yes
Predictive Thermal Modeling Yes Yes No No
Operating Temp -40°C to +85°C -40°C to +75°C -40°C to +75°C -40°C to +75°C
Fault Log 500 events 500 events 200 events 100 events
Tach Inputs None None None None
Cost Ultra-Premium High Premium Very High

Selection Recommendations

  • Choose the DS3800NGTA1F1E if:

    • You need 8A relay outputs for large AC fans.

    • You want predictive thermal modeling for proactive temperature management.

    • You require predictive relay maintenance.

    • Your installation operates in extreme heat up to +85°C .

    • You need 500-event fault logging.

    • You do not require tachometer feedback.

  • Choose the DS3800NFEE1E1E if: You need 8A relay outputs with 24-bit ADC but without predictive thermal modeling or extended +85°C.

  • Choose the DS3800NGTA1E1D if: You need 5A relay outputs with predictive modeling and +75°C operation.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • Relay Derating: For inductive motor loads, derate from 8A to 6A or use RC snubbers.

  • No Tachometer Inputs: Do not connect speed sensors.

  • Predictive Model Learning: Requires 24-hour initial learning period—do not interrupt power.

  • Model Reset: Reset via Mark V software if cabinet configuration changes.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed—all advanced features disabled in fallback mode.

  • Firmware Compatibility: Revision F requires Mark V CPU firmware v5.5 or higher for full predictive modeling, predictive maintenance, and 24-bit ADC. For v5.0–v5.4, predictive modeling disabled (maintenance and ADC still function). For v4.x, reverts to 16-bit mode.

  • Power Supply: Draws 4.5A on +5V rail—verify sufficient capacity.

A-B 1746-P2
A-B 1734-IE2V
SCHNEIDER 140CPS12400

Reviews

There are no reviews yet.

Be the first to review “GE DS3800NGTA1F1E”

Your email address will not be published. Required fields are marked *

Post comment