GE DS3800NGDC1A1A

¥999.00

The DS3800NGDC1A1A is a specific revision of General Electric’s Mark V series Fan/Exhaust Control board, part of the Speedtronic™ turbine control system. The suffix “1A1A” indicates Revision A firmware (baseline), standard 12-bit ADC, and standard temperature components (0°C to +60°C). This board features 8 mechanical relay outputs (3A) , 8 thermocouple input channels, and no tachometer feedback capability—identical in function to the base DS3800NGDC but with minor component revisions.

The DS3800NGDC1A1A is a straightforward, cost-effective relay-based fan control board designed for climate-controlled environments where tachometer feedback is not required. It relies entirely on the Mark V CPU for control logic, functioning as a simple I/O interface for AC/DC fan switching with full temperature monitoring.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NGDC1A1A
Power Supply +5V DC @ 3.0A, +15V DC @ 0.5A, -15V DC @ 0.3A (via backplane)
Temperature Inputs 8 differential thermocouple channels (Type J/K/T, 12-bit ADC, ±2°C accuracy)
RTD Inputs None
Fan Outputs 8 mechanical relays, 3A continuous @ 115VAC or 30VDC (surge 5A for 100ms)
Tachometer Inputs None
Communication Mark V proprietary parallel backplane bus
Operating Temperature 0°C to +60°C
Storage Temperature -40°C to +85°C
LED Indicators Power (green), Fan Run (8x amber), Over-Temp Alarm (red), Backplane Active (yellow)

Advantages and Distinctive Features

  • Mechanical Relay Outputs: The DS3800NGDC1A1A provides 3A mechanical relays with 5A surge handling, offering complete galvanic isolation (2500V) and robust AC/DC switching capability.

  • Full 8 Thermocouple Inputs: Comprehensive zone-by-zone temperature monitoring for large cabinets.

  • Simple, CPU-Dependent Operation: No onboard setpoint storage or logic—relies entirely on the Mark V CPU, keeping the board simple and cost-effective.

  • AC/DC Output Capability: Can switch both AC and DC fan loads, offering flexibility for mixed cabinet installations.

  • Baseline Revision A: The DS3800NGDC1A1A is the original, unmodified version of this board—ideal for replacing like-for-like in legacy systems.


Typical Application Fields

  • Climate-Controlled Indoor Installations: 0°C to +60°C range supports standard power plant environments.

  • Turbine Cabinets with AC or DC Fans: Where tachometer feedback is not required.

  • Legacy System Replacements: Direct drop-in replacement for original DS3800NGDC boards.

  • Budget-Conscious Relay-Based Applications: Cost-effective solution for basic fan control.

  • High-Surge Fan Applications: Mechanical relays handle startup surges better than solid-state alternatives.


Comparison with Related Models

Feature DS3800NGDC1A1A DS3800NGDC (Base) DS3800NFEE DS3800NFIB
Output Type Mechanical relay Mechanical relay Mechanical relay Solid-state (DC only)
Output Current 3A 3A 3A 2A
Thermocouple Inputs 8 channels 8 channels 8 channels 8 channels
Tachometer Inputs None None None None
ADC Resolution 12-bit (±2°C) 12-bit (±2°C) 12-bit (±2°C) 12-bit (±2°C)
Onboard Logic No No No No
AC Fan Capability Yes Yes Yes No
Operating Temp 0°C to +60°C 0°C to +60°C 0°C to +60°C 0°C to +60°C
Fallback Mode Full speed (100%) Full speed (100%) Full speed (100%) Full speed (100%)
Firmware Revision A (baseline) Unknown A/B A/B
Cost (Used) Low Low Low Low

Selection Recommendations

  • Choose the DS3800NGDC1A1A if:

    • Your fans require mechanical relay outputs (AC or DC) with 3A continuous rating.

    • You do not require tachometer speed feedback.

    • Your cabinet requires 8 temperature sensors for comprehensive monitoring.

    • You have a climate-controlled environment (0°C to +60°C).

    • The Mark V CPU handles all control logic.

    • You need a direct replacement for an existing DS3800NGDC board.

  • Choose the DS3800NFEE if: You need similar relay functionality but prefer a different component revision (verify compatibility).

  • Choose the DS3800NFLA if: You need tachometer feedback with relay outputs.

  • Choose the DS3800NFIB if: You prefer solid-state DC outputs (silent, maintenance-free) without tachometer feedback.


Critical Precautions

  • ESD Protection: The DS3800NGDC1A1A contains sensitive ADC components. Always wear a grounded ESD wrist strap.

  • Relay Contact Wear: Mechanical relays are rated for 100,000 operations at 3A. For frequent cycling applications, consider derating or using solid-state alternatives.

  • Inductive Load Derating: The 3A rating applies to resistive loads. For inductive fan motors, derate to 2A or use an external RC snubber across each relay output.

  • No Tachometer Inputs: The DS3800NGDC1A1A has no tachometer capability. Do not connect speed sensors.

  • No Hot-Swap: Always depower the Mark V rack before inserting or removing the DS3800NGDC1A1A.

  • Slot Assignment: Install in auxiliary I/O slots (typically slots 8–10). Do not install in CPU or analog input slots.

  • CPU Dependency: Since the DS3800NGDC1A1A has no onboard logic, the Mark V CPU must send fan ON/OFF commands. If backplane communication is lost, the board defaults to 100% fan speed (fallback mode). Address communication issues promptly.

  • Firmware Compatibility: The DS3800NGDC1A1A is compatible with all Mark V CPU firmware versions (v3.x and above). No specific CPU upgrade is needed.

 

CJK5-250
A-B 20-HIM-A6
SIEMENS 6ES7307-1BA00-0AA0

Reviews

There are no reviews yet.

Be the first to review “GE DS3800NGDC1A1A”

Your email address will not be published. Required fields are marked *