GE DS3800HSAA1R1K

¥999.00

The General Electric DS3800HSAA1R1K is a discrete (digital) input/output module for GE Mark IV/V Speedtronic turbine control systems. It is a specific variant of the HSAA series, offering a combination of 16 input and 8 output channels for binary signal processing. The General Electric DS3800HSAA1R1K is designed for turbine start/stop sequencing, valve control, and alarm annunciation in standard control applications.

Category:

Description

Technical Parameters

Parameter Specification
Inputs 16 digital, optically isolated
Input Voltage 24V DC / 125V DC (selectable)
Input Current 5mA typical per channel
Outputs 8 digital, solid‑state (MOSFET)
Output Voltage 24V DC / 125V DC (selectable)
Output Current 0.5A per channel (continuous), 1.0A peak
Response Time <2ms (inputs), <5ms (outputs)
Isolation 1500V RMS (field‑to‑backplane)
Diagnostics Open/short detection, overcurrent protection, watchdog
Power +5V @ 0.9A; +15V @ 0.35A (VME backplane)
Firmware Factory‑programmed (not field‑upgradeable)
Conformal Coating No
MTBF >195,000 hours

Advantages

  • Standard I/O – 16 inputs and 8 outputs in a single slot.

  • Dual Voltage Support – 24V or 125V DC field power.

  • Optical Isolation – 1500V isolation for noise immunity.

  • Fast Response – <2ms input scan time.

  • Hot‑Swap Capable – IEEE 1101.11 compliant.

  • Diagnostics – Open/short detection and overcurrent protection.


Applications

Industry Use
Gas Turbines Start/stop sequencing, valve control, flame detection, status monitoring
Steam Turbines Emergency trip signals, solenoid control, governor actuation
Combined Cycle HRSG damper control, pump run/stop status
Oil & Gas Compressor anti‑surge status, shutdown logic

Comparison

Feature DS3800HSAA1R1K DS3800HSAA1R1J DS3800HSAA DS3800HMPK
Inputs 16 digital 16 digital 16 digital 8 analog
Outputs 8 digital 8 digital 8 digital None
Voltage 24/125V selectable 24/125V selectable 24/125V selectable N/A
Type Digital I/O Digital I/O Digital I/O Analog input
Best For Standard control Standard control Standard control Temperature

Note: The DS3800HSAA1R1K is functionally identical to other HSAA variants in all key specifications. The suffix indicates a minor calibration or firmware variation. The “R” and “K” in the suffix indicate specific factory configuration profiles.


Selection

Scenario Choice
Standard I/O (16 in / 8 out) DS3800HSAA1R1K – standard control.
More outputs (16 in / 16 out) Use DS3800HPLA or DS3800HRPB.
More inputs (32 in) Use DS3800HPCA (32 inputs) + separate output module.
Temperature monitoring Use DS3800HMPK series.
TMR Three identical 1R1K modules. Do not mix revisions.
Non‑GE Do not use – VME only.

Critical Precautions

  • Authenticate – Check GE hologram, serial number.

  • ESD – Wear grounded wrist strap.

  • Backplane – Verify +5V, +15V, -15V before insertion.

  • Voltage Selection – Verify field voltage (24V or 125V) matches module configuration.

  • Wiring – Use shielded cable; maintain separation from AC power.

  • Load Check – Outputs rated 0.5A continuous; 1.0A peak. Verify connected load.

  • External Fusing – GE recommends external fuses on each output for protection.

  • Torque – 0.5‑0.6 Nm.

  • Temp – Keep rack <70°C.

  • Firmware – Factory‑programmed; cannot be field‑updated.

  • Sourcing – Obsolete; source refurbished from certified GE repair centers.


Final Summary

The General Electric DS3800HSAA1R1K is a standard digital I/O module for GE Speedtronic systems, offering 16 optically isolated inputs and 8 isolated outputs with selectable 24V or 125V DC field power. It is ideal for standard monitoring and actuation applications. It is functionally identical to other HSAA variants. For balanced I/O with more outputs, use DS3800HPLA or DS3800HRPB. For temperature monitoring, choose DS3800HMPK. Source from certified repair centers.

A-B 1756-PSCA2
SIEMENS 6ES7153-2BA02-0XB0
A-B 1794-ADN

 

Reviews