GE DS3800HPLA1F1D

¥999.00

The General Electric DS3800HPLA1F1D is a discrete (digital) input/output module for GE Mark IV/V Speedtronic turbine control systems. It is a specific variant of the HPLA series, offering a balanced combination of 16 input and 16 output channels for medium‑scale binary signal processing. The General Electric DS3800HPLA1F1D is designed for turbine start/stop sequencing, valve control, and alarm annunciation in applications where both monitoring and actuation are required.

Category:

Description

Technical Parameters

Parameter Specification
Inputs 16 digital, optically isolated
Input Voltage 24V DC / 125V DC (selectable)
Input Current 5mA typical per channel
Outputs 16 digital, solid‑state (MOSFET)
Output Voltage 24V DC / 125V DC (selectable)
Output Current 0.5A per channel (continuous), 1.0A peak
Response Time <2ms (inputs), <5ms (outputs)
Isolation 1500V RMS (field‑to‑backplane)
Diagnostics Open/short detection, overcurrent protection, watchdog
Power +5V @ 1.0A; +15V @ 0.4A (VME backplane)
Firmware Factory‑programmed (not field‑upgradeable)
Conformal Coating No
MTBF >195,000 hours

Advantages

  • Balanced I/O – 16 inputs and 16 outputs in a single slot.

  • Dual Voltage Support – 24V or 125V DC field power.

  • Optical Isolation – 1500V isolation for noise immunity.

  • Fast Response – <2ms input scan time.

  • Hot‑Swap Capable – IEEE 1101.11 compliant.

  • Diagnostics – Open/short detection and overcurrent protection.


Applications

Industry Use
Gas Turbines Start/stop sequencing, valve control, flame detection, status monitoring
Steam Turbines Emergency trip signals, solenoid control, governor actuation
Combined Cycle HRSG damper control, pump run/stop status
Oil & Gas Compressor anti‑surge status, shutdown logic

Comparison

Feature DS3800HPLA1F1D DS3800HPLA1E1C DS3800HPLA DS3800HMPK
Inputs 16 digital 16 digital 16 digital 8 analog
Outputs 16 digital 16 digital 16 digital None
Voltage 24/125V selectable 24/125V selectable 24/125V selectable N/A
Type Digital I/O Digital I/O Digital I/O Analog input
Best For Balanced control Balanced control Balanced control Temperature

Note: The DS3800HPLA1F1D is functionally identical to other HPLA variants in all key specifications. The suffix indicates a minor calibration or firmware variation.


Selection

Scenario Choice
Balanced I/O (16 in / 16 out) DS3800HPLA1F1D – equal inputs and outputs.
More inputs than outputs Use DS3800HPCA (32 inputs) + DS3800HPIB (16 outputs).
More outputs than inputs Use DS3800HPID (32 outputs) + DS3800HPCA (32 inputs).
Standard I/O (16 in / 8 out) Use DS3800HPBC.
Temperature monitoring Use DS3800HMPK series.
TMR Three identical 1F1D modules. Do not mix revisions.
Non‑GE Do not use – VME only.

Critical Precautions

  • Authenticate – Check GE hologram, serial number.

  • ESD – Wear grounded wrist strap.

  • Backplane – Verify +5V, +15V, -15V before insertion.

  • Voltage Selection – Verify field voltage (24V or 125V) matches module configuration.

  • Wiring – Use shielded cable; maintain separation from AC power.

  • Load Check – Outputs rated 0.5A continuous; 1.0A peak. Verify connected load.

  • External Fusing – GE recommends external fuses on each output for protection.

  • Torque – 0.5‑0.6 Nm.

  • Temp – Keep rack <70°C.

  • Firmware – Factory‑programmed; cannot be field‑updated.

  • Sourcing – Obsolete; source refurbished from certified GE repair centers.


Final Summary

The General Electric DS3800HPLA1F1D is a balanced digital I/O module for GE Speedtronic systems, offering 16 optically isolated inputs and 16 isolated outputs with selectable 24V or 125V DC field power. It is ideal for applications requiring equal monitoring and actuation capacity. It is functionally identical to other HPLA variants. For standard I/O (16 in / 8 out), use DS3800HPBC. For temperature monitoring, choose DS3800HMPK. Source from certified repair centers.