GE DS3800HIOA

¥999.00

The DS3800HIOA is a General Electric Mark IV Speedtronic turbine control board, a high-density analog input/output module designed for processing mixed analog signals including both inputs (4–20mA, 0–10V) and outputs (4–20mA, 0–10V) on a single board. The “A” suffix typically indicates basic configuration with standard environmental protection. This hybrid I/O board is ideal for applications requiring both sensor monitoring and actuator control in a compact form factor, reducing the need for separate input and output boards.

Category:

Description

Parameters

  • Analog Inputs: 4 channels, 4–20mA (default) or 0–10V DC (jumper-configurable)

  • Analog Outputs: 4 channels, 4–20mA (default) or 0–10V DC (jumper-configurable)

  • Resolution: 12-bit ADC (inputs) / 12-bit DAC (outputs)

  • Accuracy: ±0.1% of full scale (inputs and outputs)

  • Input Impedance: 250Ω (current) / >1MΩ (voltage)

  • Output Drive: 4–20mA into 750Ω max / 0–10V into 5kΩ min

  • Isolation: 1500V RMS optical isolation (channel-to-backplane)

  • Power: +5V DC @ 1.0A, +15V DC @ 0.3A (requires both rails)

  • Scan/Update Rate: 100ms (inputs) / 100ms (outputs)

  • Coating: Basic conformal coating (suffix A) – single-layer acrylic

  • Temp Range: 0°C to +60°C

  • Mounting: 6U VME Eurocard, single-slot

  • Diagnostics: LED status per channel (input over-range/under-range, output fault/open-circuit)

Advantages & Features

  • Hybrid I/O capability – 4 analog inputs + 4 analog outputs on a single board, saving cabinet space and reducing overall board count

  • Versatile signal support – inputs and outputs independently configurable for 4–20mA or 0–10V, compatible with most industrial transmitters and actuators

  • Isolated channels reduce ground loop interference and protect the backplane from field wiring faults

  • Simple configuration – signal type selected via jumpers (no complex software setup)

  • Basic A-grade coating provides light moisture and dust protection for indoor installations

  • Front-panel LEDs for per-channel status (input over-range/under-range, output fault/open-circuit)

  • Compatible with Mark IV backplanes and some VIe systems (with adapter)

Application Cases

  • Turbine inlet guide vane (IGV) position control – reading 4–20mA position feedback and outputting 4–20mA to positioner/actuator

  • Fuel gas pressure control – reading pressure transmitter and outputting to control valve positioner

  • Steam pressure and flow control – reading transmitters and outputting to throttle or extraction valve positioners

  • Lube oil pressure and temperature control – reading sensors and outputting to cooling water or bypass valves

  • Retrofit projects replacing separate input and output boards with a single hybrid solution

Competitor Comparison

  • vs. DS3800HIMA (input-only): HIOA offers outputs in addition to inputs, but fewer total channels (4 in/4 out vs. 8 differential inputs on HIMA)

  • vs. DS3800HOMB (output-only): HIOA offers inputs and outputs in a single board, reducing board count vs. separate HIMA + HOMB

  • vs. DS3800HSCB (high-speed analog): HIOA is standard speed (100ms), HSCB offers faster scanning for dynamic signals

  • vs. ABB TB711 : ABB offers higher resolution (14-bit) and PROFIBUS/Modbus communication, but lacks hybrid I/O on a single board

  • vs. Siemens 7MH410 : Siemens offers HART protocol support on some variants, but GE HIOA offers hybrid I/O in one slot

  • vs. Woodward 8440-2015 : Woodward offers more flexible configuration software, but GE HIOA provides a compact hybrid solution

  • vs. Honeywell 51304638 : Honeywell offers better long-term stability (±0.05%), but GE HIOA combines inputs and outputs

Selection Suggestions

  • Critical: Confirm input and output signal types (4–20mA or 0–10V) before installation – jumpers must match your transmitters and actuators

  • Verify your backplane provides both +5V and +15V – this board requires both rails

  • Assess channel count – 4 inputs and 4 outputs are suitable for small to medium control loops; for larger applications, consider multiple boards or separate HIMA/HOMB boards

  • Determine accuracy requirement – 0.1% is sufficient for most turbine control loops

  • Evaluate environmental conditions – A coating is suitable for clean, dry indoor installations; upgrade to B/C/D/G/H if needed

  • Order mating front connector (p/n may vary – confirm with GE)

  • For critical applications, consider used/refurbished units with 90-day warranty

Precautions

  • Critical: Do not exceed 30mA or ±30V on input channels – overvoltage may damage the ADC and isolation circuits

  • Critical: Do not short-circuit output channels – outputs are protected but prolonged shorts may cause damage

  • Critical: Use shielded twisted-pair cables for all analog inputs and outputs to avoid EMI – especially near VFDs or large transformers

  • Ensure field power supply (+24V DC) for loop-powered transmitters is stable (if used)

  • Basic A coating does not protect against humidity or corrosive gases – upgrade to B/C/D/G/H if your environment has moisture or chemicals

  • Allow 30-minute warm-up before calibration

  • Store in ESD-safe packaging – edge connector is static-sensitive

  • Periodically verify input and output calibration every 2 years against a certified reference

  • Do not hot-swap – Mark IV backplanes require power-off for insertion/removal

  • If replacing separate input and output boards, verify wiring and pinout compatibility – HIOA may differ from HIMA/HOMB series in pin assignments