Description
Parameters
-
Input Type: 4–20mA (default), 0–10V DC, ±10V DC (jumper-configurable)
-
Channels: 8 differential (fixed)
-
Resolution: 12-bit ADC
-
Accuracy: ±0.08% of full scale (improved over A1’s ±0.1%)
-
Input Impedance: 250Ω (current) / >1MΩ (voltage)
-
Filtering: 50Hz/60Hz noise rejection (B1 feature)
-
Isolation: 1500V RMS optical isolation (channel-to-backplane)
-
Power: +5V DC @ 0.8A, +15V DC @ 0.2A (requires both rails)
-
Scan Rate: 80ms per channel (B1 optimized, faster than A1’s 100ms)
-
Coating: Conformal coating (suffix B) – single-layer acrylic
-
Temp Range: 0°C to +60°C
-
Mounting: 6U VME Eurocard, single-slot
-
Diagnostics: Enhanced LED status per channel (over-range, under-range, open-circuit, and signal noise alert)
Advantages & Features
-
Versatile input support – accepts 4–20mA, 0–10V, or ±10V signals via jumpers, compatible with most industrial transmitters
-
B1 firmware offers improved accuracy (±0.08%), faster scan (80ms), and built-in 50/60Hz noise filtering – a significant upgrade over A1
-
8 differential channels provide noise rejection for long cable runs in turbine environments
-
Isolated channels reduce ground loop interference and protect the backplane from field wiring faults
-
Basic B-grade coating provides light moisture and dust protection for indoor installations
-
Front-panel LEDs for per-channel status including signal noise detection alerts
-
Compatible with Mark IV backplanes and some VIe systems (with adapter)
Application Cases
-
Turbine inlet guide vane (IGV) position feedback – 4–20mA from LVDT transmitters requiring stable, noise-free readings
-
Fuel gas pressure monitoring – 4–20mA transmitters in gas turbine fuel skids where 50/60Hz noise is present
-
Steam pressure and flow monitoring – for steam turbine throttle and extraction lines with improved accuracy needs
-
Lube oil pressure and temperature – from standard 4–20mA transmitters on bearing and sump systems
-
Retrofit projects upgrading from A1 firmware to B1 for better noise rejection and faster response
Competitor Comparison
-
vs. DS3800HIMA1A1B (A1/B variant): Better accuracy (±0.08% vs. ±0.1%), faster scan (80ms vs. 100ms), built-in noise filtering, and signal noise diagnostics – significant upgrade
-
vs. DS3800HIMA (standard A variant): Better specifications across the board; B1 is a meaningful improvement
-
vs. DS3800HIMA1C1C (C variant): Similar performance, but B coating is basic vs. C’s improved moisture resistance
-
vs. DS3800HFPB (thermocouple board): Handles different signal types – HIMA1B1B is for 4–20mA/voltage, not thermocouples
-
vs. DS3800HSCB (high-speed analog input): HIMA is standard speed (80ms), HSCB offers faster scanning for dynamic signals
-
vs. ABB TB711 : Similar channel count, but ABB offers higher resolution (14-bit) and PROFIBUS/Modbus communication
-
vs. Siemens 7MH410 : Similar functionality, but Siemens offers HART protocol support on some variants
-
vs. Woodward 8440-2015 : Similar channel count, but Woodward offers more flexible configuration software
-
vs. Honeywell 51304638 : Similar channel count, but Honeywell offers better long-term stability (±0.05%)
Selection Suggestions
-
Critical: Confirm input signal type (4–20mA, 0–10V, or ±10V) before installation – jumper settings must match your transmitters
-
Verify your backplane provides both +5V and +15V – this board requires both rails
-
Assess if B1’s noise filtering and faster scan rate are beneficial – particularly valuable near VFDs or in electrically noisy environments
-
Evaluate environmental conditions – B coating is suitable for clean, dry indoor installations; upgrade to C/D/G/H for more demanding environments
-
Order mating front connector (p/n may vary – confirm with GE)
-
For critical applications, consider used/refurbished units with 90-day warranty or new-old-stock with calibration certificate
Precautions
-
Critical: Do not exceed 30mA or ±30V on input channels – overvoltage may damage the ADC and isolation circuits
-
Critical: Use shielded twisted-pair cables for all analog inputs to avoid EMI – B1’s filtering helps but is not a substitute for good wiring practices
-
Ensure field power supply (+24V DC) for 2-wire transmitters is stable and within specifications (if loop-powered)
-
B1 firmware offers improved noise rejection – configure jumpers correctly for 50Hz or 60Hz based on your region
-
Basic B coating does not protect against humidity or corrosive gases – upgrade to C/D/G/H if your environment has moisture or chemicals
-
Allow 30-minute warm-up before calibration
-
Store in ESD-safe packaging – edge connector is static-sensitive
-
Periodically verify channel calibration every 2 years against a certified reference
-
Do not hot-swap – Mark IV backplanes require power-off for insertion/removal
-
If replacing a similar board, confirm pinout compatibility – HIMA series may differ from HFP or HHR series in wiring assignments