Description
Technical Specifications
-
Product Type: High-Density Digital Analog Board
-
Part Number: DS3800HDDA
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems
-
Input Channels: 32 differential analog inputs – highest density in Mark IV
-
Input Type: Voltage (±10V, 0-10V, or 0-5V) (jumper-selectable per channel)
-
Input Impedance: > 10MΩ
-
Resolution: 12-bit
-
Accuracy: ±0.1% of full scale at 25°C; ±0.02% per °C drift
-
Protection: Over-voltage protection (±30V) per input
-
Isolation: 1500Vrms opto-isolation (field-to-logic)
-
Temperature Range: 0°C to +60°C
-
MTBF: > 150,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
High Channel Density: The GE DS3800HDDA provides 32 analog inputs on a single 6U board, doubling the density of standard boards like the DS3800DVIA.
-
Flexible Input Configuration: Jumper-selectable voltage ranges per channel.
-
Space-Saving Design: Reduces rack space requirements in large Mark IV systems.
-
Diagnostic LEDs: Front-panel LEDs indicate input status and fault conditions.
Typical Application Cases
-
Large-Scale Monitoring: Monitors multiple temperature, pressure, and flow signals in large turbine systems.
-
Space-Constrained Installations: Maximizes I/O density where rack space is limited.
-
Retrofit Projects: Replaces multiple lower-density boards with a single GE DS3800HDDA.
Competitive Comparison
| Feature | GE DS3800HDDA | GE DS3800DVIA (Standard) | GE DS3800HCMA (Multiplexer) | Modern High-Density Module |
|---|---|---|---|---|
| Channels | 32 | 16 | 16 in / 1 out | 32 |
| Input Type | Voltage only | Voltage only | Voltage or current | Voltage or current |
| Resolution | 12-bit | 12-bit | 12-bit | 16-bit |
| Isolation | 1500Vrms | 1500Vrms | 1500Vrms | 500Vrms |
| Compatibility | Mark IV | Mark IV | Mark IV | Universal |
The GE DS3800HDDA offers the highest analog input density in the Mark IV family.
Selection Guidelines & Precautions
-
Input Range Selection: Configure jumpers per channel for ±10V, 0-10V, or 0-5V.
-
Channel Count: Ensure total channels do not exceed 32.
-
Wiring: Use shielded twisted-pair cables; ground shield at board end only.
-
ESD Handling: Use ESD-safe practices.
-
Sourcing: Obsolete. Request functional test report including all 32 channels tested.
-
Spare Strategy: Keep one spare GE DS3800HDDA on-site for critical high-density applications.

NI SCXI-1302
B&R X20BC0083
SCHNEIDER 140DDI35300


Reviews