Description
Technical Specifications
-
Product Type: High-Current Multiplexer Analog Board (Revision 1E1G)
-
Part Number: DS3800HCMA1E1G
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems (Rev. M and later)
-
Input Channels: 16 differential analog inputs
-
Output Channels: 1 multiplexed differential analog output
-
Input Type: Voltage (±10V) or current (4-20mA) (jumper-selectable per channel)
-
Input Impedance: > 10MΩ (voltage mode); 250Ω (current mode)
-
Input Current: Up to 60mA per channel (current mode) – highest in series
-
Multiplexing Speed: 500 channels per second (2ms per channel) – fastest in series
-
Scan Sequence: Sequential, skip, or programmable priority scan (jumper-selectable)
-
Accuracy: ±0.1% of full scale at 25°C; ±0.008% per °C drift – best in series
-
Protection: Enhanced over-voltage (±100V) and over-current protection per input – highest in series
-
Diagnostics: Individual channel fault detection (over-voltage, over-current, open-circuit, signal out-of-range) with LED indication and backplane reporting
-
Isolation: 2500Vrms reinforced isolation with enhanced common-mode transient immunity (> 100kV/µs)
-
Temperature Range: -40°C to +90°C – widest in series
-
MTBF: > 250,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
Fastest Scanning Speed: The GE DS3800HCMA1E1G scans at 500 channels per second (2ms per channel), providing the fastest data acquisition in the HCMA series.
-
Maximum Input Protection: Withstands ±100V, offering the highest resilience against wiring errors and transients.
-
Highest Drive Capability: Handles up to 60mA per channel in current mode.
-
Programmable Priority Scan: Allows critical channels to be scanned more frequently than non-critical channels.
-
Best Accuracy: ±0.008% per °C drift ensures precision in fluctuating temperatures.
-
Advanced Diagnostics: Individual channel fault detection with LED and backplane reporting for predictive maintenance.
-
Highest Transient Immunity: > 100kV/µs for superior noise rejection.
-
Widest Temperature Range: -40°C to +90°C suits the most extreme environments.
Typical Application Cases
-
High-Speed Temperature Monitoring: Multiplexes thermocouple and RTD signals with rapid scan rates.
-
Pressure Transducer Scanning: Monitors multiple pressure transmitters with priority scanning for critical channels.
-
Vibration Monitoring: Scans accelerometer signals for turbine health monitoring.
-
Process Control: Multiplexes analog inputs for high-speed DCS integration.
-
Extreme Environment Installations: Widest temperature range suits offshore, arctic, or desert sites.
Competitive Comparison
| Feature | DS3800HCMA1E1G | DS3800HCMA1A1B | GE DS3800HCMA (Base) | Modern Multiplexer |
|---|---|---|---|---|
| Scan Speed | 500 ch/s | 200 ch/s | 100 ch/s | Software configurable |
| Input Current | 60mA | 50mA | 50mA | 20mA |
| Input Protection | ±100V | ±60V | ±30V | ±30V |
| Priority Scan | Yes | No | No | Software configurable |
| Diagnostics | LED+BP+out-of-range | LED | LED | Software diagnostics |
| Temperature Drift | ±0.008%/°C | ±0.015%/°C | ±0.02%/°C | ±0.01%/°C |
| Temperature Range | -40°C to +90°C | -40°C to +70°C | 0°C to +60°C | 0°C to +60°C |
| Transient Immunity | > 100kV/µs | 50kV/µs | 10kV/µs | 10kV/µs |
| Compatibility | Mark IV Rev. M+ | Mark IV Rev. L+ | Mark IV | Universal |
The GE DS3800HCMA1E1G is the definitive pinnacle of the HCMA series, offering the fastest scanning speed, highest protection, and broadest environmental tolerance.
Selection Guidelines & Precautions
-
Input Type Selection: Configure jumpers per channel for voltage or current to match your field sensors.
-
Scan Speed: The GE DS3800HCMA1E1G scans at 2ms per channel. Ensure this meets your application’s requirements.
-
Priority Scan: Configure priority scan for critical channels requiring more frequent sampling.
-
Skip Mode: Unused channels should be set to “skip” to optimize scan time.
-
Input Protection: The GE DS3800HCMA1E1G withstands ±100V. Prolonged exposure may degrade accuracy.
-
Diagnostic Reporting: Requires Mark IV firmware Rev. M or later for full diagnostic support.
-
Wiring: Use shielded twisted-pair cables; ground shield at board end only.
-
ESD Handling: Use ESD-safe practices.
-
Sourcing: Obsolete. Request functional test report including:
-
All 16 channels tested in voltage and current modes
-
Scan speed verification (500 ch/s)
-
Priority scan verification
-
Accuracy and drift test (±0.008%/°C)
-
Protection validation (±100V)
-
Diagnostic reporting validation
-
Isolation test (2500Vrms)
-
-
Spare Strategy: Keep one spare GE DS3800HCMA1E1G on-site for critical high-speed multiplexing applications. If unavailable, the DS3800HCMA1A1B is a compatible alternative with reduced specifications. Proactive replacement after 10 years of continuous operation is recommended.

PHOENIX 9662-610
NI 192061-02
A-B 1756-A13


Reviews