Description
Technical Specifications
-
Product Type: High-Amplitude Current Analog Output Board (Revision 1A1B)
-
Part Number: DS3800HACB1A1B
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems (Rev. L and later)
-
Output Channels: 4 independent analog current outputs
-
Output Type: 4-20mA or 0-20mA (jumper-selectable), loop-powered
-
Drive Capability: Up to 60mA per channel (sourcing or sinking)
-
Loop Power: Internal 24Vdc loop power supply (isolated)
-
Compliance Voltage: 24Vdc (allows driving loads up to 600Ω at 20mA; 400Ω at 60mA)
-
Resolution: 12-bit
-
Accuracy: ±0.1% of full scale at 25°C; ±0.02% per °C drift
-
Protection: Over-current, short-circuit, and reverse-polarity protection per channel
-
Diagnostics: Individual channel fault detection (open-loop, short-circuit, over-temperature) with backplane reporting
-
Isolation: 2500Vrms reinforced isolation
-
Temperature Range: -40°C to +70°C
-
Heat Dissipation: Integrated heatsink with thermal monitoring
-
MTBF: > 180,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
High Drive Capability: The GE DS3800HACB1A1B delivers up to 60mA per channel, providing margin for driving multiple devices or long cable runs.
-
Diagnostic Reporting: Individual channel fault detection (open-loop, short-circuit, over-temperature) is reported via the backplane to the Mark IV processor.
-
Reinforced Isolation: 2500Vrms for superior ground loop and transient protection.
-
Extended Temperature Range: -40°C to +70°C suits harsh environments.
-
Improved Thermal Management: Integrated heatsink with thermal monitoring allows sustained high-current operation.
-
Loop-Powered Outputs: Integrated 24Vdc loop power eliminates external power supplies.
-
Comprehensive Protection: Over-current, short-circuit, and reverse-polarity protection.
-
Diagnostic LEDs: Front-panel LEDs indicate output status, fault, and loop power presence per channel.
Typical Application Cases
-
I/P (Current-to-Pressure) Converters: Drives I/P converters for pneumatic valve actuators.
-
Valve Positioners: Provides 4-20mA control signals for smart and analog positioners.
-
Long-Distance Transmitter Powering: Supplies loop power and control signal to remote transmitters up to 1200m.
-
Variable Speed Drives (VSDs): Provides 4-20mA speed references to VSDs.
-
Damper and Louver Actuators: Controls 4-20mA actuated dampers.
Competitive Comparison
| Feature | DS3800HACB1A1B | GE DS3800HACB (Base) | GE DS3800HACA1A1A | Modern Analog Module |
|---|---|---|---|---|
| Max Current | 60mA | 60mA | 50mA | 20-25mA |
| Loop Diagnostics | Yes (backplane) | Yes (backplane) | No | Yes (HART) |
| Isolation | 2500Vrms | 2500Vrms | 1500Vrms | 500Vrms |
| Temperature Range | -40°C to +70°C | -40°C to +70°C | 0°C to +60°C | 0°C to +60°C |
| Thermal Management | Heatsink + monitor | Heatsink + monitor | None | None |
| Compliance Voltage | 24V (600Ω @ 20mA) | 24V (600Ω @ 20mA) | 24V (600Ω @ 20mA) | 12-15V |
| Compatibility | Mark IV Rev. L+ | Mark IV | Mark IV | Universal |
The GE DS3800HACB1A1B offers the same features as the base DS3800HACB with minor component refinements, making it the preferred choice for diagnostic-enabled 4-20mA applications.
Selection Guidelines & Precautions
-
Loop Configuration: Verify sourcing or sinking mode for your field devices. Set jumpers on DS3800HACB1A1B accordingly.
-
Load Resistance: Calculate total loop resistance. Drives up to 600Ω at 20mA; derate to 400Ω at 60mA.
-
Loop Power: Internal 24V loop power is isolated. Ensure field devices do not have their own power supply.
-
Cable Length: Supports cables up to 1200m. For longer runs, reduce load or use a repeater.
-
Diagnostic Reporting: Verify Mark IV firmware (Rev. L or later) supports diagnostic reporting. Earlier firmware may ignore fault data.
-
Thermal Management: Ensure cabinet airflow is adequate (minimum 100 CFM) for sustained high-current operation.
-
Commissioning: Use a precision current meter to verify each channel. Calibrate using onboard trimmers if necessary.
-
Wiring: Use shielded twisted-pair cables; ground shield at board end only.
-
ESD Handling: Use ESD-safe practices.
-
Sourcing: Obsolete. Request functional test report including:
-
All 4 channels tested at 4mA, 20mA, and 60mA
-
Load regulation test (up to 600Ω)
-
Loop power verification (24V)
-
Diagnostic fault reporting validation (open-loop, short-circuit)
-
Isolation test (2500Vrms)
-
Thermal monitoring verification
-
-
Spare Strategy: Keep one spare DS3800HACB1A1B on-site for critical 4-20mA control applications. The diagnostic features make this the preferred choice over earlier HACA revisions.

A-B 2711P-RN15S
A-B 1769-IQ32
Schneider 140DDO35300
A-B 1769-PA4


Reviews
There are no reviews yet.