Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization and thermal isolation
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Operating Temp: -30°C to +70°C (extended upper limit vs G1A at 65°C)
Storage Temp: -40°C to +85°C
Mounting: VME rack
Suffix “G1B”: High accuracy + advanced diagnostics (drift, degradation, sense-lead) + F1 wiring + extended upper temperature limit (70°C) + standard conformal coating
Key Features
High accuracy – ±0.08% for critical temperature monitoring
Advanced diagnostics – drift monitoring, degradation prediction, sense-lead integrity, and open/short detection
Extended upper temperature limit – operates up to 70°C, suitable for hotter cabinets
Faster sampling – 10 Hz for responsive monitoring
F1 wiring configuration – specific channel-to-terminal mapping for certain GE cabinet variants; direct fit for F1-configured systems
Improved cold-junction compensation – stable readings across ambient variations
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health with diagnostic indicators
Standard conformal coating for moisture/dust resistance
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Gas turbine EGT monitoring in F1 cabinets with elevated temperatures – where cabinet temperatures reach 65-70°C and predictive diagnostics are valuable
Steam turbine bearings in poorly ventilated F1 systems – critical protection with drift anticipation
Generator stator cooling in tropical environments with F1 wiring – precision measurement with diagnostic assurance
Compressor performance monitoring in desert installations with F1 configuration – reliability under thermal stress
Critical points requiring both high accuracy and early fault warnings
Comparison with Competitors
| Feature | DS200TCQFG1B |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Diagnostics | Drift + degradation + open/short | Group-level | Per-channel + HART |
| Temp Range | -30°C to +70°C | -25°C to +65°C | -20°C to +60°C |
| Wiring Config | F1-specific | Standard | Standard |
| GE Native Integration with F1 Cabs | Yes (direct fit) | No | No |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
Selection Tips
Choose the DS200TCQFG1B only if your cabinet uses F1 wiring configuration and you require high accuracy (±0.08%) with advanced diagnostics and extended temperature capability (70°C)
For F1 systems with the same features but standard temperature (65°C), the DS200TCQFG1A may be sufficient
For F1 systems with enhanced cold-junction compensation and similar specs, consider DS200TCQFG1A (if enhanced CJC needed)
For F1 systems with high accuracy but no diagnostics, consider DS200TCEAFG1B (if available)
For enhanced coating protection with similar specs, consider DS200TCQFG1B with specialized coating suffix (e.g., DS200TCQFG1BBC or similar)
For G1 systems requiring similar features, use DS200TCQBG1B
For C1 systems requiring similar features, use DS200TCQCG1B
Verify existing wiring pinout against F1 standard – using the wrong terminal block or miswiring will scramble channel readings
Source refurbished units with F1 pinout verification and diagnostic test validation
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -30°C to +70°C operating range – exceeding 70°C reduces component life
Pinout critical – F1 mapping differs from other series; verify cabinet wiring before installation
Calibrate every 24 months – diagnostics and accuracy depend on a valid baseline calibration
Ground shields only at the board end
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
Monitor diagnostic logs – drift warnings indicate sensor aging; plan proactive replacement
Label clearly – mark board and slot as “TCQFG1B – DIAG/EXT TEMP/F1” to ensure proper handling and prevent future miswiring with other series boards
Do not mix F1, E1, C1, G1, and G2 boards without verifying terminal block compatibility in the same rack
Monitor cabinet temperature – if consistently near 70°C, consider cooling improvements or upgrade to wider-range variants if needed

GE IC200ALG328
A-B 2094-BM01-S
A-B 1756-ENBT
Westinghouse 1C31179G01