Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization and improved thermal isolation
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Operating Temp: -30°C to +70°C
Storage Temp: -40°C to +85°C
Mounting: VME rack
Suffix “G2AEB”: High accuracy + advanced diagnostics (drift, degradation, sense-lead) + G2 wiring + extended upper temperature (70°C) + enhanced cold-junction compensation + “EB” premium coating (high-grade urethane or silicone blend offering excellent moisture barrier, good-to-high chemical resistance, and moderate solvent resistance)
Key Features
High accuracy – ±0.08% for critical temperature monitoring
Advanced diagnostics – drift monitoring, degradation prediction, sense-lead integrity, and open/short detection
Extended upper temperature limit – operates up to 70°C, suitable for hotter cabinets
Enhanced cold-junction compensation – better linearization across ambient variations
“EB” premium coating – excellent moisture resistance, good-to-high chemical protection, and moderate solvent resistance; suitable for harsh environments
G2-specific wiring configuration – unique channel-to-terminal mapping for G2-configured systems
Faster sampling – 10 Hz for responsive monitoring
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health with diagnostic indicators
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Chemical processing plants with G2 wiring – premium coating protects against solvents and chemicals while diagnostics ensure reliability
Coastal power plants with heavy salt spray – excellent moisture barrier with enhanced performance at elevated cabinet temperatures
Paper and pulp mills – harsh chemical environments with humidity and heat
Gas turbine EGT monitoring in corrosive, hot environments – high accuracy with predictive diagnostics and environmental protection
Compressor monitoring in chemically aggressive areas – noise rejection with environmental protection
Comparison with Competitors
| Feature | DS200TCQBG2AEB |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Diagnostics | Drift + degradation + open/short | Group-level | Per-channel + HART |
| Cold Junction Comp. | Enhanced | Standard | Standard |
| Temp Range | -30°C to +70°C | -25°C to +65°C | -20°C to +60°C |
| Wiring Config | G2-specific | Standard | Standard |
| Coating Type | “EB” premium | Standard acrylic | Standard acrylic |
| Moisture Resistance | Excellent | Moderate | Moderate |
| Chemical Resistance | Good to high | Low | Low |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
| GE Native Integration with G2 Cabs | Yes (direct fit) | No | No |
Selection Tips
Choose the DS200TCQBG2AEB only if your cabinet uses G2 wiring configuration and you need high accuracy (±0.08%), advanced diagnostics, enhanced cold-junction compensation, extended temperature (70°C), and premium coating protection – ideal for hot, chemically aggressive G2 environments requiring predictive maintenance
For G2 systems with the same features but standard coating, consider DS200TCQBG2A (less protection)
For severe chemical/corrosion exposure, upgrade to DS200TCQBG2AJE (military-grade) or DS200TCQBG2ATF (PTFE) if available
For G1 systems requiring similar features, use DS200TCQBG1AEB (if available)
If you are rewiring the cabinet, consider converting to G1 for broader board availability
Verify existing wiring pinout against G2 standard – using the wrong terminal block or miswiring will scramble channel readings
Source refurbished units with G2 pinout verification, coating inspection, and diagnostic test validation
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -30°C to +70°C operating range – exceeding 70°C reduces component life
Pinout critical – G2 mapping differs from G1; verify cabinet wiring before installation
Avoid damaging the coating – scratches compromise protection
Use isopropyl alcohol only for cleaning – “EB” coating resists many solvents but avoid acetone/MEK; confirm compatibility with GE documentation
Calibrate every 24 months – diagnostics and accuracy depend on a valid baseline calibration
Ground shields only at the board end
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
Monitor diagnostic logs – drift warnings indicate sensor aging; plan proactive replacement
Label clearly – mark board and slot as “TCQBG2AEB – DIAG/EXT TEMP/ENH CJC/G2/EB COAT” to ensure proper handling and prevent future miswiring with G1 boards
Do not mix G1 and G2 boards without verifying terminal block compatibility in the same rack
Monitor cabinet temperature – if consistently near 70°C, consider cooling improvements or upgrade to wider-range variants if needed

FOXBORO FBM230
PACIFIC SCIENTIFIC 6410-001-C-N-N
OVATION 1C31116G04