Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization and thermal isolation
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Operating Temp: -30°C to +65°C
Storage Temp: -40°C to +85°C
Mounting: VME rack
Suffix “G1”: High accuracy + advanced diagnostics (drift, degradation, sense-lead integrity) + G1 wiring configuration + basic temperature range + standard conformal coating
Key Features
High accuracy – ±0.08% for critical temperature monitoring
Advanced diagnostics – drift monitoring, degradation prediction, sense-lead integrity, and open/short detection
Faster sampling – 10 Hz for responsive monitoring
G1 wiring configuration – standard channel-to-terminal mapping matching most GE cabinets
Improved cold-junction compensation – stable readings across ambient variations
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health with diagnostic indicators
Standard conformal coating for moisture/dust resistance
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Gas turbine EGT monitoring – high accuracy with predictive diagnostics for early fault detection
Steam turbine bearing and casing temperatures – critical protection with drift anticipation
Generator stator cooling monitoring – precise measurements with diagnostic assurance
HRSG temperature measurements – enhanced reliability for efficiency-critical points
Compressor performance monitoring – where sensor degradation cannot be tolerated
Comparison with Competitors
| Feature | DS200TCQAG1 |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Diagnostics | Drift + degradation + open/short | Group-level | Per-channel + HART |
| Temp Range | -30°C to +65°C | -25°C to +65°C | -20°C to +60°C |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
| GE Native Integration | Yes | No | No |
Selection Tips
Choose the DS200TCQAG1 if you need high accuracy (±0.08%) and advanced diagnostics (drift/degradation) with G1 wiring in a standard temperature environment
For extended temperature range (70°C) with similar features, consider DS200TCQAG1B (if available)
For enhanced coating protection with similar specs, consider DS200TCQAG1 with specialized coating suffix (e.g., DS200TCQAG1BBA or similar)
For basic accuracy without diagnostics, the DS200TCEBG1 is more economical
For 4-wire long-distance needs with diagnostics, consider DS200TCDAH1BGD (lower accuracy at ±0.10%)
Verify existing wiring is 2-wire standard – G1-series terminal mapping applies
Source refurbished units with diagnostic test validation
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -30°C to +65°C operating range
Calibrate every 24 months – diagnostics depend on a valid baseline calibration
Ground shields only at the board end
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
Monitor diagnostic logs – drift warnings indicate sensor aging; plan proactive replacement
Label clearly – mark as “TCQAG1 – DIAG” to ensure proper handling and maintenance tracking