Description
Technical Parameters
Based on the Mark V DS200 series specifications, the DS200TCCAG2A features the following key parameters:
-
Primary Function: Thermocouple Input Termination Board with Enhanced Cold-Junction Compensation
-
Input Channels: 8 thermocouple input channels
-
Thermocouple Types Supported: J, K, T, E, S, R, B (enhanced over G1 series)
-
Cold-Junction Compensation: Onboard high-accuracy thermistor with ±0.4°C accuracy typical (improved over G1 ±0.5°C)
-
Input Impedance: >1 MΩ
-
Terminal Type: Screw-type terminal blocks (accepts 0.5-2.5mm² wire, AWG 20-14)
-
Voltage Rating: 300V AC/DC maximum
-
Current Rating: 10A per terminal (maximum)
-
Isolation: No active isolation (passive termination); relies on connected modules for isolation
-
Form Factor: Single-slot 6U Eurocard (160mm), 96-pin DIN connector to backplane
-
Mounting: Direct plug-in to Mark V rack; front-facing screw terminals for thermocouple wiring
-
Operating Environment: -10°C to 65°C ambient temperature (extended range), 5% to 95% non-condensing humidity
-
Labels: Enhanced labeling with clearly marked channel designations (CH+, CH-) and type selection guides
-
Compliance: UL recognized, CE marked, RoHS compliant
Advantages and Features
The DS200TCCAG2A offers several distinctive advantages for Mark V system thermocouple signal termination:
-
Enhanced Cold-Junction Compensation: With ±0.4°C CJC accuracy (improved over G1’s ±0.5°C), the DS200TCCAG2A provides superior temperature measurement precision.
-
Extended Temperature Range: Rated for -10°C to 65°C, the DS200TCCAG2A is suitable for installations in extreme environments.
-
Multi-Type Support: Supports thermocouple Types J, K, T, E, S, R, and B (enhanced over G1 series).
-
Second-Generation Design: The “G2” revision features improved component selection for enhanced long-term stability and reliability.
-
Integrated Cold-Junction Compensation: The onboard CJC thermistor ensures accurate temperature readings.
-
High-Density Termination: With 8 dedicated thermocouple channels, provides efficient termination for multiple sensors in a single slot.
-
Passive Design: Contains no active electronics (other than CJC thermistor), making the DS200TCCAG2A highly reliable.
-
Hot-Swap Capable: Supports live insertion and removal with proper ESD protocols.
Application Cases in Application Fields
The DS200TCCAG2A is deployed across multiple heavy-industrial sectors:
-
Combined Cycle Power Plants: A 750MW CCPP facility uses the DS200TCCAG2A for critical exhaust temperature spread monitoring. The ±0.4°C CJC accuracy improved measurement precision, enhancing turbine efficiency calculations.
-
Gas Turbine Test Cells: The DS200TCCAG2A provides high-accuracy thermocouple termination for performance validation testing with Type B thermocouples at high temperatures.
-
Gas Pipeline Compressor Stations: The DS200TCCAG2A terminates thermocouples for compressor discharge temperature monitoring with enhanced CJC accuracy for precise surge protection calculations.
-
Offshore Oil Platforms: The extended temperature range of the DS200TCCAG2A ensures reliable operation in unheated offshore enclosures.
Comparison with Competing Products
| Aspect | DS200TCCAG2A | DS200TCCAG1A | DS200TCCAG1B (16-Channel) | Third-Party Board |
|---|---|---|---|---|
| CJC Accuracy | ±0.4°C | ±0.5°C | ±0.5°C | Varies; often ±1°C |
| Temperature Range | -10°C to 65°C | 0°C to 60°C | 0°C to 60°C | Varies; often 0-50°C |
| Thermocouple Types | J, K, T, E, S, R, B | J, K, T, E, S, R | J, K, T, E, S, R | Varies; often limited |
| Channel Count | 8 channels | 8 channels | 16 channels | Varies; often 4-8 |
| Passive Design | Yes (plus CJC) | Yes (plus CJC) | Yes (plus CJC) | Varies |
| Hot-Swap Capable | Yes | Yes | Yes | Usually no |
| Drop-in Compatibility | Direct plug-in | Direct plug-in | Direct plug-in | Requires external mounting |
Selection Suggestions and Precautions
Before purchasing or installing the DS200TCCAG2A:
-
Verify Exact Model: Ensure the board is precisely DS200TCCAG2A, not DS200TCCAG1A or other variants. The “G2A” suffix is critical for enhanced CJC accuracy, extended temperature range, and Type B support.
-
Confirm Thermocouple Types: Ensure your thermocouple types (J, K, T, E, S, R, B) are supported by the DS200TCCAG2A.
-
Environmental Assessment: If your installation experiences temperatures outside 0-60°C, the DS200TCCAG2A is the recommended choice.
-
Thermocouple Wiring: Use correct thermocouple extension wire (same type as sensor). Avoid standard copper wire for extensions.
-
Polarity: Ensure correct polarity for all terminations.
-
Shielding: Use shielded thermocouple cables in electrically noisy environments. Connect the shield at the DS200TCCAG2A end only.
-
CJC Stability: Ensure adequate airflow around the DS200TCCAG2A and avoid mounting near heat sources to maintain ±0.4°C CJC accuracy.
-
ESD Protection: Use grounded wrist straps during handling.
-
Post-Installation Validation:
-
Verify all terminations are mechanically secure.
-
Confirm correct polarity and sensor type for each channel.
-
Check CJC readings against a known ambient temperature reference.
-
Verify temperature readings at the HMI match expected values.
-
-
Spare Strategy: Maintain at least one spare DS200TCCAG2A on-site.
-
Supplier Qualification: Request visual inspection and CJC accuracy verification (±0.4°C) before shipment.
Final Recommendation
For GE Mark V turbine systems requiring enhanced thermocouple input termination with superior CJC accuracy and extended temperature range, the DS200TCCAG2A is the optimal solution. Its ±0.4°C CJC accuracy, -10°C to 65°C operating range, and Type B thermocouple support provide superior measurement reliability for critical temperature monitoring applications. Prioritize reputable aftermarket suppliers offering tested units with CJC accuracy verification. Maintain spares on-site, use correct thermocouple extension wire, and ensure proper polarity to guarantee the long-term reliability of your DS200TCCAG2A and the entire Mark V control system.

KOLLMORGEN PRD-MZ205S0Z-10
A-B SST-PFB-SLC
FOXBORO FBM216
A-B 1794-L34B
SIEMENS HFD63F250


Reviews