Description
Key Technical Parameters
| Parameter | Specification |
|---|---|
| +5V Output | 5A continuous, 6A peak |
| Other Outputs | +15V @1.5A, -15V @1A, +24V @1A |
| Input | 115 VAC ±10% (47-63 Hz) ONLY – no DC input option |
| Efficiency | 78% typical at full load |
| Protection | OVP (latch), OCP, OTP (latch – manual reset required), 2kV surge |
| Diagnostics | 4 LEDs – green “PWR OK”, green “AC OK”, red “FAULT”, yellow “CUR LIM” |
| Conformal Coating | None – standard industrial grade |
| Temp Range | 0 to +50°C ambient (75 CFM forced air recommended) |
| Form Factor | 6U VME, 1-slot width (no adjacent slot clearance required) |
| Weight | 1.2 kg (approx. 2.6 lbs) |
Advantages & Core Features
-
Adequate 5A +5V capacity – Sufficient for standard Mark V configurations with moderate I/O counts (typically 8-16 analog inputs, 8-12 digital I/O, and 1-2 communication boards). The DS200PCCAG1A is the most cost-effective power solution for installations with total +5V loads under 5A.
-
Simple AC-only input – No DC infrastructure required; operates directly from standard 115 VAC plant power. This simplifies installation in facilities that lack 125 VDC battery systems.
-
Widely available and cost-effective – As the most common Mark V power converter, the DS200PCCAG1A has the shortest lead times (typically 2-4 weeks) and lowest cost among all Mark V power boards. Spare units are readily available from multiple industrial surplus suppliers.
-
Compact 1-slot form factor – Unlike the 1.5-slot DS200PCCAG10A and DS200PCCAG10ACB, the DS200PCCAG1A fits in any standard Mark V rack slot without requiring adjacent empty space, making it ideal for densely populated racks.
-
Reliable protection features – Overvoltage and overcurrent protection prevent damage to downstream modules. The overtemperature protection (latching) ensures the board shuts down before overheating, though it requires manual reset after cooling.
-
Simple LED diagnostics – Four LEDs provide immediate visual status: AC input present, +5V output healthy, current limit active, and general fault. No complex diagnostic tools required for basic troubleshooting.
Application Cases
-
Standard utility gas turbine – A 200 MW combined-cycle plant uses the DS200PCCAG1A in their Mark V rack for a Frame 6B turbine with standard I/O (12 analog inputs, 8 analog outputs, 16 digital I/O, 2 communication boards). Total +5V load is 4.2A, well within the 5A capacity. The board has operated reliably for 8+ years with only preventative fan replacements.
-
Industrial steam turbine – A paper mill uses the DS200PCCAG1A for steam turbine speed control with minimal I/O requirements (6 analog inputs, 4 digital outputs). The AC-only input eliminates the need for DC battery maintenance, reducing overall system complexity.
-
Compressor control retrofit – A natural gas pipeline station replaced a failed third-party power supply with the DS200PCCAG1A in a Mark V rack controlling two centrifugal compressors. The 5A capacity proved sufficient after load calculations, and the board’s 1-slot width allowed installation in a fully populated rack without rearranging other modules.
-
Backup/spare for critical systems – Many facilities maintain one or more DS200PCCAG1A units as on-site spares for emergency replacement, given their low cost and wide availability compared to higher-capacity variants.
Comparison with Higher-Capacity Variants
| Feature | DS200PCCAG1A (Base) | DS200PCCAG10A (10A) | DS200PCCAG10ACB (Coated/Bus) |
|---|---|---|---|
| +5V Capacity | 5A (6A peak) | 10A (12A peak) | 10A (12A peak) |
| DC Input Option | No (AC only) | Yes (dual AC/DC) | Yes (dual AC/DC) |
| Input Surge Protection | 2kV | 6kV | 6kV (with logging) |
| Efficiency | 78% | >85% | >85% |
| Current Sharing | None | Active (±5%) | Active (±2%) |
| Diagnostics | 4 LEDs (basic) | 6 LEDs + 20-event log | 8 LEDs + I²C + 50-event log |
| Conformal Coating | No | No | Yes (1,000 hr salt-spray) |
| Slot Width | 1-slot | 1.5-slot | 1.5-slot |
| Availability | Common (2-4 weeks) | Rare (8-14 weeks) | Very rare (10-16 weeks) |
| Cost | Low-moderate | High | Very high |
| Best For | Standard indoor, low I/O density | High I/O density, DC backup | Harsh environments + predictive maintenance |
Key Takeaway: The DS200PCCAG1A is the workhorse power supply for the majority of Mark V installations. Only upgrade to the DS200PCCAG10A or DS200PCCAG10ACB if your +5V load exceeds 5A or if you require DC input, redundancy, or harsh-environment protection. For standard applications, the DS200PCCAG1A offers the best balance of cost, availability, and reliability.
Selection Suggestions
-
Calculate your +5V load – Sum the +5V current draw of all boards in your Mark V rack (processor, I/O, communication). If the total is under 5A continuous, the DS200PCCAG1A is sufficient. If between 5A and 7A, consider the DS200PCCAG7 (if available) or the DS200PCCAG10A. If above 7A, the DS200PCCAG10A or DS200PCCAG10ACB is mandatory.
-
Confirm AC power availability – The DS200PCCAG1A accepts 115 VAC only. If your facility provides 230 VAC or 125 VDC, you will need an external step-down transformer or choose the dual-input DS200PCCAG10A variant.
-
Assess environmental conditions – For clean indoor control rooms (climate-controlled, low humidity, no chemical exposure), the DS200PCCAG1A is perfectly adequate. For coastal, offshore, chemical, or high-humidity environments, select the conformally coated DS200PCCAG10ACB (though note this requires higher capacity – there is no conformally coated 5A version).
-
Evaluate redundancy needs – The DS200PCCAG1A does not support parallel current sharing. If you require N+1 redundant power, you must use two DS200PCCAG10A or DS200PCCAG10ACB boards with active sharing capability.
-
Check slot availability – The DS200PCCAG1A fits in any 1-slot position. No adjacent empty slot is required, making it the preferred choice for densely populated racks.
-
Procurement – Purchase from reputable industrial surplus suppliers offering functional testing (full-load burn-in for 24 hours), ripple/noise measurements, and a 1-year warranty. Lead times are typically 2-4 weeks. Avoid “new old stock” without test certifications, as capacitors may have degraded during storage.
-
Stock spares – Given the DS200PCCAG1A‘s common availability, maintaining one on-site spare is prudent for critical applications, but multiple spares are not necessary unless you operate a large fleet of Mark V systems.
Important Precautions
-
Power down completely – De-energize the entire rack and wait 5 minutes for input capacitors (1,000 µF) to discharge. Hot-swapping is not supported – doing so will damage the board and backplane.
-
ESD protection – Use wrist strap and anti-static mat. The DS200PCCAG1A uses CMOS components sensitive to electrostatic discharge.
-
AC input only – Do not apply DC voltage to the input terminals. The DS200PCCAG1A lacks the rectifier circuitry for DC operation and will be damaged by DC input.
-
Overtemperature reset – If the red FAULT LED illuminates and the board has overheated (OTP triggered), allow it to cool for at least 15 minutes. The OTP circuit is latching and requires a manual power cycle (disconnect AC input, wait 30 seconds, reconnect) to reset. Do not repeatedly reset without investigating cooling system health.
-
Fan replacement – The onboard 40mm fan has a 40,000-hour lifespan (approx. 4.5 years). Replace preventatively every 4 years. Use only GE-specified fans with the correct connector and airflow rating (5 CFM minimum at 50°C).
-
Cleaning – Use compressed air (max 50 PSI, from 30 cm distance) to remove dust. Do not use liquid cleaners, alcohol, or brushes, as the board is not conformally coated and is susceptible to moisture ingress.
-
Storage – Store spares at 10-30°C, 20-50% RH. Rotate every 24 months – install and run at 50% load for 24 hours to reform electrolytic capacitors, then return to storage.
-
Fault diagnosis – If red FAULT illuminates:
-
Verify AC input voltage (103-127 VAC).
-
Check for output shorts using a multimeter.
-
Allow 15-minute cool-down if OTP suspected.
-
Cycle input power (disconnect 30 seconds, reconnect).
-
If FAULT persists, the board requires repair or replacement – do not continuously reset.
-
Final Expert Recommendation
The DS200PCCAG1A is the most practical and cost-effective power converter for the vast majority of GE Mark V turbine control systems. Its 5A +5V capacity adequately supports standard I/O configurations, its AC-only input simplifies installation in facilities without DC infrastructure, and its 1-slot width maximizes rack space efficiency. The DS200PCCAG1A is the recommended choice for clean indoor environments with total +5V loads under 5A.
Only upgrade to the DS200PCCAG10A if your system requires:
-
+5V loads above 5A (high-density I/O or dual processors)
-
DC input capability (125 VDC battery backup)
-
Active current sharing for N+1 redundancy
Only consider the DS200PCCAG10ACB if your installation is in a harsh environment (coastal, offshore, chemical, high-humidity) and you have the backplane support for its I²C diagnostic bus.
For standard applications, the DS200PCCAG1A delivers reliable, stable power at the lowest total cost of ownership. Its widespread availability ensures short lead times and easy sourcing of replacements. Proper installation, regular fan replacement, and periodic cleaning will allow the DS200PCCAG1A to provide 10+ years of dependable service. Perform a load calculation before purchase, verify your AC power source, and always purchase from certified suppliers who provide functional test documentation. The DS200PCCAG1A remains the enduring workhorse of the Mark V power system.

TRICONEX 3721
EPRO MMS6120
ABB SPASI23
SIEMENS 6RA7000-0MV62-0