Description

Specifications
- Part Number: 8910-PS-DC
- Series: MTL 8000
- Input: 18.5–36 VDC
- Output: 12 VDC ±5%, max 4.9 A
- Isolation: 720 VDC input to output isolation
- Power fail signal: Supports power loss alarm to BIM module
- Protection: Reverse polarity protection, internal fuse, overvoltage / overcurrent / short-circuit protection
- Cooling: Passive cooling, no fan
- Operating temperature: -40°C ~ +55°C (full load, optimal orientation); -40°C ~ +70°C (60% derated load)
- Storage temperature: -40°C ~ +85°C
- Humidity: 5–95% RH, non-condensing
- Weight: 0.775 kg
- Mounting: Slot on MTL8000 node carrier
Advantages and Features
GE 8910-PS-DC is developed for hazardous zone intrinsic safety systems, with stable output and comprehensive fault diagnosis. Two power supplies can be installed in one carrier for redundant power feeding, achieving bumpless switchover when one supply fails. It provides power-fail status signal to the backplane BIM module for system alarm. Compact, fanless design reduces failure points in explosion-proof cabinet environments. It conforms to IEC intrinsic safety standards.
Application & Case
It is widely used in oil, gas and chemical plant safety instrumented systems (SIS) for MTL8000 IS node racks. In a refinery SIS overhaul project, 8910-PS-DC replaced the faulty power supply. After installation, node controller and backplane communication modules regained stable 12V power, and all IS field bus signals and ESD interlock functions worked normally.
Comparison
It is a dedicated 12V power supply for MTL8000 node racks, not a Mark VIe turbine power supply. It cannot be mixed with GE Mark VIe, RX3i or other DCS rack power modules. Other MTL8000 power variants have different output parameters and are not interchangeable.
Selection Notes
Confirm full part number 8910-PS-DC. Confirm matching node carrier model and whether redundant power configuration is required. This is an obsolete MTL legacy spare.
Precautions
Cut off DC input before replacement and take ESD protection. Check wiring polarity strictly. After installation, verify 12V output voltage, power-fail alarm signal and redundant switchover function before putting into service.

ATEN/EQ CE624