DS3800HLIC1A1B GE

¥999.00

The DS3800HLIC1A1B is a General Electric Mark IV Speedtronic turbine control board, a high-speed discrete input module with a suffix code indicating: 24 high-speed input channels (1), firmware revision A1 (A1), and basic environmental protection (B = single-layer conformal coating). The “HLI” designation denotes a high-speed logic interface module for critical turbine protection applications, offering ultra-fast response (<0.5ms) and hardware latch capability. The A1 firmware provides standard high-speed logic processing, while the B-grade coating offers basic moisture resistance for standard indoor applications. This variant is ideal for applications requiring a high number of critical protection inputs.

Category:

Description

Parameters

  • Input Type: 24V DC discrete (sourcing/sinking, configurable)

  • Input Channels: 24 channels (higher density than HLIA’s 16)

  • Input Voltage: 24V DC (nominal), 10–30V DC range

  • Input Current: 5mA per channel (typical)

  • Response Time: <0.5ms (hardware-accelerated)

  • Hardware Latch: Yes – captures short-duration pulses (<1ms)

  • Isolation: 2500V RMS optical isolation (channel-to-backplane)

  • Power: +5V DC @ 0.9A, +24V DC @ 0.3A (field power)

  • Filtering: Programmable input debounce filter (configurable)

  • Coating: Conformal coating (suffix B) – single-layer acrylic

  • Temp Range: 0°C to +60°C

  • Mounting: 6U VME Eurocard, single-slot

  • Diagnostics: LED status per channel, open-wire detection, and short-circuit protection

Advantages & Features

  • Higher channel density – 24 high-speed inputs on a single board, more than HLIA’s 16 channels

  • Ultra-fast response (<0.5ms) – designed for critical protection logic

  • Hardware latch capability – captures short-duration pulses that might otherwise be missed by firmware polling

  • Flexible input configuration – channels can be set as sourcing or sinking via jumpers

  • Isolated channels protect the backplane from field wiring faults and surges

  • B-grade coating provides basic moisture and dust protection for indoor installations

  • Front-panel LEDs for per-channel status, fault, and open-wire detection

  • Compatible with Mark IV backplanes and some VIe systems (with adapter)

Application Cases

  • Overspeed protection – ultra-fast magnetic pickup sensor inputs for turbine overspeed trip logic with multiple sensors

  • Flame detection – high-speed UV/IR flame scanner signals for burner management across multiple zones

  • Emergency trip systems (ETS) – critical discrete inputs for emergency shutdown logic with high channel count

  • Turbine start-up sequencing – fast-response speed and position sensors

  • Retrofit projects replacing multiple lower-density high-speed input boards with a single higher-density solution

Competitor Comparison

  • vs. DS3800HLIA1A1B (A1/B variant): More input channels (24 vs. 16) – HLIC1A1B offers higher density, otherwise similar A1 firmware and B coating

  • vs. DS3800HLIA1B1D (B1/D variant): HLIC1A1B offers more channels but lacks B1 firmware features and D-grade coating – choose based on channel count vs. advanced diagnostics

  • vs. DS3800HLEA1C1C (input-only high-speed): HLIC1A1B offers faster response (<0.5ms vs. <0.6ms) and hardware latch – HLIC is for critical protection applications

  • vs. DS3800HLCA (hybrid I/O): HLIC1A1B is input-only with faster response (<0.5ms vs. <1ms) and hardware latch – better for critical protection

  • vs. DS3800HHRB1D1D (standard discrete I/O): HLIC1A1B offers significantly faster response (<0.5ms vs. 3ms) – critical for high-speed protection

  • vs. ABB DSDI series: Similar high-speed discrete capability, but GE offers hardware latch and better Mark IV integration

  • vs. Siemens 6ES7 series: Similar functionality, but GE offers faster response and higher channel density

  • vs. Woodward 5437 modules: GE offers faster response and hardware latch for critical protection

Selection Suggestions

  • Critical: Confirm input type (sourcing vs. sinking) – jumper settings must match your field devices

  • Critical: Verify response time requirement – HLIC1A1B’s <0.5ms is for critical protection

  • Verify your backplane provides both +5V and +24V field power with sufficient current capacity (+24V @ 0.3A)

  • Assess channel count – 24 channels cover larger monitoring applications with multiple high-speed sensors

  • Evaluate environmental conditions – B coating is suitable for clean, dry indoor installations; upgrade to C/D/G/H if needed

  • Order mating front connector (p/n may vary – confirm with GE)

  • For critical protection applications, consider used/refurbished units with 90-day warranty or new-old-stock with calibration certificate

Precautions

  • Critical: Do not exceed 30V DC on input channels – overvoltage may damage the isolation circuits

  • Critical: High-speed inputs are extremely sensitive to noise – use shielded twisted-pair cables, proper grounding, and dedicated field wiring to avoid false triggers

  • Critical: Hardware latch capability requires proper configuration – ensure the latch settings match your application requirements to avoid missing pulses or false captures

  • Ensure field power supply (+24V DC) is stable and within 10–30V DC range

  • A1 firmware is a baseline revision – verify it supports your specific hardware latch configuration requirements

  • Programmable debounce filtering must be set correctly – for critical protection, very short debounce delays (or none) may be needed

  • B coating provides basic protection but is not suitable for frequent humidity, salt spray, or chemical exposure – upgrade to C/D/G/H if needed

  • Allow 30-minute warm-up before commissioning

  • Store in ESD-safe packaging – edge connector is static-sensitive

  • Periodically verify input operation every 6 months (critical protection circuits require frequent testing)

  • Do not hot-swap – Mark IV backplanes require power-off for insertion/removal

  • If replacing multiple lower-density boards, verify wiring and pinout compatibility – HLIC may differ from HLIA in pin assignments

A-B 1746-IB32