Description
Parameters
-
Input Type: 24V DC discrete (sourcing/sinking, configurable)
-
Input Channels: 24 channels (high-density configuration)
-
Input Voltage: 24V DC (nominal), 10–30V DC range
-
Input Current: 5mA per channel (typical)
-
Response Time: <0.6ms (C1 optimized, faster than B1’s <0.8ms)
-
Isolation: 2500V RMS optical isolation (channel-to-backplane)
-
Power: +5V DC @ 0.9A, +24V DC @ 0.3A (field power)
-
Filtering: Programmable input debounce filter with 50Hz/60Hz adaptive noise rejection (C1 feature)
-
Coating: Conformal coating (suffix B) – single-layer acrylic
-
Temp Range: 0°C to +60°C
-
Mounting: 6U VME Eurocard, single-slot
-
Diagnostics: Enhanced onboard with per-channel LED status, open-wire detection, short-circuit protection, signal noise alert, and fault logging (C1 feature)
Advantages & Features
-
High-density input monitoring – 24 channels on a single board, providing more sensor inputs than HLCA (8 in) or HLCB (4 in)
-
C1 firmware offers faster response (<0.6ms), adaptive 50/60Hz noise rejection, and enhanced diagnostics including fault logging – a significant upgrade over B1
-
Flexible input configuration – channels can be set as sourcing or sinking via jumpers
-
Isolated channels protect the backplane from field wiring faults and surges
-
B-grade coating provides basic moisture and dust protection for indoor installations
-
Front-panel LEDs for per-channel status, fault, open-wire detection, and signal noise alerts
-
Compatible with Mark IV backplanes and some VIe systems (with adapter)
Application Cases
-
Turbine overspeed monitoring – high-speed inputs from multiple magnetic pickup sensors with adaptive noise rejection
-
Flame detection systems – digital signals from UV/IR flame scanners across multiple burner zones with fault logging
-
Valve position feedback monitoring – limit switches from fuel, steam, and bypass valves
-
Proximity switch monitoring – for turbine speed, position, and timing applications
-
Retrofit projects replacing multiple lower-density input boards with a single high-density solution with advanced diagnostics
Competitor Comparison
-
vs. DS3800HLEA1B1B (B1/B variant): Faster response (<0.6ms vs. <0.8ms), adaptive noise rejection, and C1 fault logging – significant upgrade
-
vs. DS3800HLEA (standard A variant): Substantially faster response, C1 diagnostics, and B coating – major upgrade
-
vs. DS3800HLCA (A variant): More input channels (24 vs. 8) but no outputs – HLEA1C1B is input-only with higher density and C1 features
-
vs. DS3800HLCB (B variant): More input channels (24 vs. 4) but no outputs – HLEA1C1B is input-only with significantly higher density and C1 features
-
vs. DS3800HL0A1EC (input-only high-speed): Higher channel density (24 vs. 16), C1 firmware, and B coating – HLEA1C1B is a more advanced variant
-
vs. DS3800HHRB1D1D (standard discrete I/O): HLEA1C1B offers faster response (<0.6ms vs. 3ms) and higher input density – significant upgrade for high-speed monitoring
-
vs. ABB DSDI series: Similar high-speed discrete capability, but GE offers higher channel density, C1 adaptive filtering, and better Mark IV integration
-
vs. Siemens 6ES7 series: Similar functionality, but GE offers specialized high-speed input-only configuration with higher density and C1 features
-
vs. Woodward 5437 modules: GE offers higher input density, faster response, and adaptive noise rejection
Selection Suggestions
-
Critical: Confirm input type (sourcing vs. sinking) – jumper settings must match your field devices
-
Verify your backplane provides both +5V and +24V field power – this board requires both rails
-
Assess channel count – 24 inputs cover large turbine monitoring applications with multiple sensors
-
Evaluate if C1’s fault logging and adaptive noise rejection are beneficial – particularly valuable in electrically noisy environments and for post-event analysis
-
Evaluate environmental conditions – B coating is suitable for clean, dry indoor installations; upgrade to C/D/G/H if needed
-
Order mating front connector (p/n may vary – confirm with GE)
-
For critical protection applications, purchase with a calibration certificate and 12-month warranty
Precautions
-
Critical: Do not exceed 30V DC on input channels – overvoltage may damage the isolation circuits
-
Critical: High-speed inputs are sensitive to noise – use shielded twisted-pair cables and proper grounding to avoid false triggers; C1’s adaptive filtering helps but is not a substitute for good wiring practices
-
Ensure field power supply (+24V DC) is stable and within 10–30V DC range
-
C1 firmware offers adaptive 50/60Hz noise rejection – configure settings correctly for your region’s line frequency
-
B coating provides basic protection but is not suitable for frequent humidity, salt spray, or chemical exposure – upgrade to C/D/G/H if needed
-
Allow 30-minute warm-up before commissioning
-
Store in ESD-safe packaging – edge connector is static-sensitive
-
Periodically verify input operation every year (high-speed protection circuits require regular testing)
-
Do not hot-swap – Mark IV backplanes require power-off for insertion/removal
-
If replacing multiple lower-density boards, verify wiring and pinout compatibility – HLEA may differ from other discrete series in pin assignments

A-B 1794-IB32
SCHNEIDER 140DDO35300
A-B 1769-OW16