Description
Parameters
-
Analog Inputs: 8 channels, 4–20mA (default) or 0–10V DC (jumper-configurable)
-
Analog Outputs: 4 channels, 4–20mA (default) or 0–10V DC (jumper-configurable)
-
Resolution: 12-bit ADC (inputs) / 12-bit DAC (outputs)
-
Accuracy: ±0.1% of full scale
-
Input Impedance: 250Ω (current) / >1MΩ (voltage)
-
Output Drive: 4–20mA into 750Ω max / 0–10V into 5kΩ min
-
Isolation: 1500V RMS optical isolation (channel-to-backplane)
-
Power: +5V DC @ 1.1A, +15V DC @ 0.35A (higher than HIOA due to more channels)
-
Scan/Update Rate: 100ms (inputs) / 100ms (outputs)
-
Coating: Basic conformal coating (suffix B) – single-layer acrylic
-
Temp Range: 0°C to +60°C
-
Mounting: 6U VME Eurocard, single-slot
-
Diagnostics: LED status per channel (input over-range/under-range, output fault/open-circuit)
Advantages & Features
-
Higher channel density – 8 analog inputs + 4 analog outputs on a single board, providing more control loops than HIOA (4 in/4 out)
-
Hybrid I/O capability – combines inputs and outputs on one board, saving cabinet space
-
Versatile signal support – inputs and outputs independently configurable for 4–20mA or 0–10V, compatible with most industrial transmitters and actuators
-
Isolated channels reduce ground loop interference and protect the backplane from field wiring faults
-
Basic B-grade coating provides light moisture and dust protection for indoor installations
-
Compatible with Mark IV backplanes and some VIe systems (with adapter)
-
Front-panel LEDs for per-channel status
Application Cases
-
Turbine inlet guide vane (IGV) position control – reading multiple position feedbacks and outputting to positioners
-
Fuel gas pressure and flow control – multiple pressure transmitters and control valve positioners in gas turbine fuel skids
-
Steam pressure, flow, and temperature control – for steam turbine throttle, extraction, and reheat lines
-
Lube oil pressure, temperature, and cooling control – multiple sensors and actuators on bearing systems
-
Retrofit projects replacing separate input and output boards with a single hybrid solution
Competitor Comparison
-
vs. DS3800HIOA (A variant): More inputs (8 vs. 4) with same 4 outputs – HIOB offers greater channel density at the cost of slightly higher power consumption
-
vs. DS3800HIMA (input-only): HIOB offers outputs in addition to inputs, but fewer total inputs (8 vs. 8 differential on HIMA)
-
vs. DS3800HOMB (output-only): HIOB offers inputs and outputs in a single board, reducing board count
-
vs. DS3800HSCB (high-speed analog): HIOB is standard speed (100ms), HSCB offers faster scanning for dynamic signals
-
vs. ABB TB711 : ABB offers higher resolution (14-bit) and PROFIBUS/Modbus communication, but lacks hybrid I/O on a single board
-
vs. Siemens 7MH410 : Siemens offers HART protocol support on some variants, but GE HIOB offers hybrid I/O in one slot
-
vs. Woodward 8440-2015 : Woodward offers more flexible configuration software, but GE HIOB provides a compact hybrid solution
-
vs. Honeywell 51304638 : Honeywell offers better long-term stability (±0.05%), but GE HIOB combines inputs and outputs
Selection Suggestions
-
Critical: Confirm input and output signal types (4–20mA or 0–10V) before installation – jumpers must match your transmitters and actuators
-
Verify your backplane provides both +5V and +15V with sufficient current capacity (+5V @ 1.1A, +15V @ 0.35A)
-
Assess channel count – 8 inputs and 4 outputs cover medium-sized control loop applications
-
Determine accuracy requirement – 0.1% is sufficient for most turbine control loops
-
Evaluate environmental conditions – B coating is suitable for clean, dry indoor installations; upgrade to C/D/G/H if needed
-
Order mating front connector (p/n may vary – confirm with GE)
-
For critical applications, consider used/refurbished units with 90-day warranty
Precautions
-
Critical: Do not exceed 30mA or ±30V on input channels – overvoltage may damage the ADC and isolation circuits
-
Critical: Do not short-circuit output channels – outputs are protected but prolonged shorts may cause damage
-
Critical: Use shielded twisted-pair cables for all analog inputs and outputs to avoid EMI – especially near VFDs or large transformers
-
Ensure field power supply (+24V DC) for loop-powered transmitters is stable (if used)
-
Basic B coating does not protect against humidity or corrosive gases – upgrade to C/D/G/H if your environment has moisture or chemicals
-
Allow 30-minute warm-up before calibration
-
Store in ESD-safe packaging – edge connector is static-sensitive
-
Periodically verify input and output calibration every 2 years against a certified reference
-
Do not hot-swap – Mark IV backplanes require power-off for insertion/removal
-
If replacing separate input and output boards, verify wiring and pinout compatibility – HIOB may differ from HIOA or other series in pin assignments

A-B 1756-IM16I
ABB NKAS01-15
MITSUBISHI AJ65BT-64DAV


Reviews