Description
Parameters
-
Input Type: 4–20mA (default), 0–10V DC, ±10V DC (configurable)
-
Channels: 16 single-ended or 8 differential (configurable via jumpers)
-
Resolution: 12-bit ADC
-
Accuracy: ±0.1% of full scale
-
Input Impedance: 250Ω (current) / >1MΩ (voltage)
-
Isolation: 1500V RMS optical isolation (channel-to-backplane)
-
Power: +5V DC @ 0.9A, +15V DC @ 0.25A (slightly higher than HIMA)
-
Scan Rate: 100ms per channel (standard)
-
Coating: Basic conformal coating (suffix B) – single-layer acrylic
-
Temp Range: 0°C to +60°C
-
Mounting: 6U VME Eurocard, single-slot
-
Diagnostics: LED status per channel (over-range, under-range, open circuit)
Advantages & Features
-
Higher channel density – supports up to 16 single-ended channels, doubling the capacity of HIMA (8 differential)
-
Flexible configuration – channels can be set as differential (8) or single-ended (16) via jumpers, adapting to different wiring schemes
-
Versatile input support – accepts 4–20mA, 0–10V, or ±10V signals, compatible with most industrial transmitters
-
Isolated channels reduce ground loop interference and protect the backplane from field wiring faults
-
Basic B-grade coating provides light moisture and dust protection for indoor installations
-
Compatible with Mark IV backplanes and some VIe systems (with adapter)
-
Front-panel LEDs for per-channel status (over-range, under-range, open-circuit)
Application Cases
-
Turbine inlet guide vane (IGV) position feedback – 4–20mA from LVDT transmitters in larger turbines with more feedback points
-
Fuel gas pressure and flow monitoring – multiple 4–20mA transmitters in gas turbine fuel skids
-
Steam pressure and flow monitoring – for steam turbine throttle, extraction, and reheat lines
-
Lube oil pressure and temperature – multiple transmitters on bearing and sump systems
-
Retrofit projects replacing obsolete GE DS3800H series analog boards where more channels are needed
Competitor Comparison
-
vs. DS3800HIMA (A variant): Higher channel density (16 single-ended vs. 8 differential) – HIMB offers more channels at the cost of slightly higher power consumption
-
vs. DS3800HIMA1C1D (C1/D variant): HIMB has basic firmware vs. C1’s advanced features; HIMB offers more channels but lower accuracy and slower scan
-
vs. DS3800HFPB (thermocouple board): Handles different signal types – HIMB is for 4–20mA/voltage, not thermocouples
-
vs. DS3800HSCB (high-speed analog input): HIMB offers more channels but slower scanning; HSCB is for dynamic signals
-
vs. ABB TB711 : Similar channel count, but ABB offers higher resolution (14-bit) and PROFIBUS/Modbus communication
-
vs. Siemens 7MH410 : Similar functionality, but Siemens offers HART protocol support on some variants
-
vs. Woodward 8440-2015 : Similar channel count, but Woodward offers more flexible configuration software
-
vs. Honeywell 51304638 : Similar channel count, but Honeywell offers better long-term stability (±0.05%)
Selection Suggestions
-
Critical: Confirm input signal type (4–20mA, 0–10V, or ±10V) and channel configuration (differential vs. single-ended) before installation – jumper settings must match your transmitters
-
Verify your backplane provides both +5V and +15V – this board requires both rails
-
Assess channel count – 16 single-ended channels cover larger turbine installations with more transmitters
-
Determine accuracy requirement – 0.1% is sufficient for most turbine process variables
-
Evaluate environmental conditions – B coating is suitable for clean, dry indoor installations; upgrade to C/D/G/H if needed
-
Order mating front connector (p/n may vary – confirm with GE)
-
For critical applications, consider used/refurbished units with 90-day warranty
Precautions
-
Critical: Do not exceed 30mA or ±30V on input channels – overvoltage may damage the ADC and isolation circuits
-
Critical: Use shielded twisted-pair cables for all analog inputs to avoid EMI – especially near VFDs or large transformers
-
Critical: Configure jumpers correctly for differential vs. single-ended wiring – incorrect settings will cause measurement errors
-
Ensure field power supply (+24V DC) for 2-wire transmitters is stable (if loop-powered)
-
Basic B coating does not protect against humidity or corrosive gases – upgrade to C/D/G/H if your environment has moisture or chemicals
-
Allow 30-minute warm-up before calibration
-
Store in ESD-safe packaging – edge connector is static-sensitive
-
Periodically verify channel calibration every 2 years against a certified reference
-
Do not hot-swap – Mark IV backplanes require power-off for insertion/removal
-
If replacing a similar board, confirm pinout compatibility – HIMB may differ from HIMA or other series in wiring assignments