Description
Technical Specifications
-
Product Type: High-Amplitude Isolated Current Output Board (Revision 1C1B)
-
Part Number: DS3800HAIC1C1B
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems (Rev. M and later)
-
Output Channels: 4 independent isolated current outputs
-
Output Type: 4-20mA or 0-20mA (jumper-selectable), loop-powered
-
Drive Capability: Up to 100mA per channel (sourcing or sinking) – improved
-
Loop Power: Internal 24Vdc isolated loop power per channel (galvanically isolated)
-
Compliance Voltage: 28Vdc (allows driving loads up to 700Ω at 20mA) – improved
-
Isolation Voltage: 2500Vrms reinforced isolation per channel (channel-to-channel and channel-to-logic)
-
Resolution: 12-bit
-
Accuracy: ±0.1% of full scale at 25°C; ±0.012% per °C drift – improved
-
Protection: Over-current, short-circuit, and reverse-polarity protection per channel
-
Diagnostics: Individual channel fault detection (open-loop, short-circuit, over-temperature, load impedance variation) with LED indication and backplane reporting
-
Temperature Range: -40°C to +75°C (extended)
-
Heat Dissipation: Active thermal management with integrated heatsink, temperature sensor, and variable-speed cooling fan control output
-
MTBF: > 180,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
Per-Channel Reinforced Isolation: The GE DS3800HAIC1C1B provides 2500Vrms isolation per channel, eliminating ground loops and protecting logic from field-side faults.
-
Higher Drive Capability: Delivers up to 100mA per channel for driving multiple devices in parallel or long cable runs.
-
Higher Compliance Voltage: 28V compliance drives loads up to 700Ω at 20mA.
-
Enhanced Diagnostics: Individual channel fault detection (open-loop, short-circuit, over-temperature, load impedance variation) with LED and backplane reporting for predictive maintenance.
-
Improved Accuracy: ±0.012% per °C drift ensures precision in fluctuating temperatures.
-
Active Thermal Management: Integrated temperature sensor and variable-speed fan control output ensure sustained high-current operation without thermal derating.
-
Extended Temperature Range: -40°C to +75°C suits harsh environments.
-
Comprehensive Protection: Over-current, short-circuit, and reverse-polarity protection.
Typical Application Cases
-
Explosive Atmospheres (Ex/ATEX): Provides galvanic isolation suitable for driving devices in hazardous areas with appropriate external barriers.
-
Long-Distance Signal Transmission: Drives 4-20mA signals over distances up to 1400m with complete isolation.
-
I/P (Current-to-Pressure) Converters: Drives I/P converters for pneumatic valve actuators with full isolation.
-
Valve Positioners: Provides 4-20mA control signals for smart and analog positioners.
-
Remote I/O Powering: Supplies isolated loop power and control signals to remote transmitters and actuators.
-
Extreme Environment Installations: Extended temperature range suits offshore, arctic, or desert sites.
Competitive Comparison
| Feature | DS3800HAIC1C1B | DS3800HAIC1B1A | DS3800HAIC1A1A | GE DS3800HAIA (Higher Amp) |
|---|---|---|---|---|
| Per-Channel Isolation | Yes (2500Vrms) | Yes (2500Vrms) | Yes (1500Vrms) | Yes (2500Vrms) |
| Max Current | 100mA | 90mA | 80mA | 150mA |
| Compliance Voltage | 28V (700Ω @ 20mA) | 26V (650Ω @ 20mA) | 24V (600Ω @ 20mA) | 30V (750Ω @ 20mA) |
| Temperature Drift | ±0.012%/°C | ±0.015%/°C | ±0.02%/°C | ±0.008%/°C |
| Diagnostics | LED + backplane + load | LED + over-temp | LED | LED + backplane + load + drift |
| Thermal Management | Active (variable fan) | Passive (monitor) | Passive | Active (variable fan) |
| Temperature Range | -40°C to +75°C | -40°C to +70°C | 0°C to +60°C | -40°C to +85°C |
| Compatibility | Mark IV Rev. M+ | Mark IV Rev. L+ | Mark IV | Mark IV Rev. M+ |
The GE DS3800HAIC1C1B offers a balanced combination of high current, advanced diagnostics, active thermal management, and wide temperature tolerance, making it the preferred choice for demanding isolated current output applications.
Selection Guidelines & Precautions
-
Isolation Requirements: Provides 2500Vrms per channel. Ensure this meets your system’s safety requirements.
-
Loop Configuration: Verify sourcing or sinking mode. Set jumpers accordingly.
-
Load Resistance: Calculate total loop resistance. Drives up to 700Ω at 20mA. Exceeding this causes saturation.
-
Loop Power: Each channel has isolated loop power. Ensure field devices do not have their own power supply.
-
Cable Length: Supports cables up to 1400m. For longer runs, reduce load or use a repeater.
-
Active Thermal Management: Connect the variable-speed fan control output to a cabinet cooling fan (24Vdc, < 500mA) for active temperature regulation.
-
Diagnostic Reporting: Verify Mark IV firmware (Rev. M or later) supports backplane diagnostic reporting.
-
Load Impedance Monitoring: Familiarize yourself with fault codes for load impedance variation in the Mark IV diagnostic menu.
-
Short-Circuit Protection: Protected, but repeated shorting may affect reliability.
-
Commissioning: Use a precision current meter to verify each channel. Calibrate using onboard trimmers if necessary.
-
Wiring: Use shielded twisted-pair cables; ground shield at board end only. Do not connect shield to isolated output circuit.
-
ESD Handling: Use ESD-safe practices.
-
Sourcing: Obsolete. Request functional test report including:
-
All 4 channels tested at 4mA and 20mA
-
Load regulation test (up to 700Ω)
-
Loop power verification (28V per channel)
-
Isolation test (2500Vrms per channel, channel-to-channel)
-
Diagnostic fault reporting validation (including load impedance monitoring)
-
Accuracy and drift test (±0.012%/°C)
-
Thermal management verification (variable-speed fan control)
-
Protection validation
-
-
Spare Strategy: Keep one spare GE DS3800HAIC1C1B on-site for critical isolated 4-20mA control applications. This revision is the preferred choice for demanding applications requiring diagnostics and active cooling. If you require higher current capability (>100mA) or the highest accuracy, consider the DS3800HAIA1E1D instead. Proactive replacement after 10 years of continuous operation is recommended.