DS3800HAIC1B1A GE

¥999.00

The GE DS3800HAIC1B1A is a High-Amplitude Isolated Current output board for the GE Speedtronic Mark IV turbine control system. It provides high-current 4-20mA loop-powered outputs with per-channel galvanic isolation. The “1B1A” suffix indicates a revision with reinforced isolationimproved thermal management, and enhanced diagnostic capabilities compared to the initial “1A1A” version.

Category:

Description

Technical Specifications

  • Product Type: High-Amplitude Isolated Current Output Board (Revision 1B1A)

  • Part Number: DS3800HAIC1B1A

  • Manufacturer: General Electric (GE)

  • System Compatibility: GE Speedtronic Mark IV Turbine Control Systems (Rev. L and later)

  • Output Channels: 4 independent isolated current outputs

  • Output Type: 4-20mA or 0-20mA (jumper-selectable), loop-powered

  • Drive Capability: Up to 90mA per channel (sourcing or sinking) – improved

  • Loop Power: Internal 24Vdc isolated loop power per channel (galvanically isolated)

  • Compliance Voltage: 26Vdc (allows driving loads up to 650Ω at 20mA) – improved

  • Isolation Voltage: 2500Vrms reinforced isolation per channel (upgraded from 1500Vrms)

  • Resolution: 12-bit

  • Accuracy: ±0.1% of full scale at 25°C; ±0.015% per °C drift – improved

  • Protection: Over-current, short-circuit, and reverse-polarity protection per channel

  • Diagnostics: Individual channel fault detection (open-loop, short-circuit, over-temperature) with LED indication

  • Temperature Range: -40°C to +70°C (extended)

  • Heat Dissipation: Enhanced integrated heatsink with thermal monitoring

  • MTBF: > 180,000 hours (MIL-HDBK-217F)


Key Features & Advantages

  • Reinforced Isolation: The GE DS3800HAIC1B1A provides 2500Vrms isolation per channel (upgraded from 1500Vrms), offering superior ground loop and transient protection.

  • Higher Drive Capability: Delivers up to 90mA per channel, providing additional margin for driving multiple devices or longer cable runs.

  • Higher Compliance Voltage: 26V compliance drives loads up to 650Ω at 20mA, accommodating a wider range of field devices.

  • Enhanced Diagnostics: Individual channel fault detection (open-loop, short-circuit, over-temperature) with LED indication aids troubleshooting.

  • Improved Accuracy: ±0.015% per °C drift ensures better precision in fluctuating temperatures.

  • Extended Temperature Range: -40°C to +70°C suits harsh environments.

  • Improved Thermal Management: Enhanced heatsink with thermal monitoring allows sustained high-current operation.

  • Loop-Powered Outputs: Integrated 24Vdc loop power per channel eliminates external power supplies.


Typical Application Cases

  • Explosive Atmospheres (Ex/ATEX): Provides galvanic isolation suitable for driving devices in hazardous areas with appropriate external barriers.

  • Long-Distance Signal Transmission: Drives 4-20mA signals over distances up to 1300m with complete isolation.

  • I/P (Current-to-Pressure) Converters: Drives I/P converters for pneumatic valve actuators with full isolation.

  • Valve Positioners: Provides 4-20mA control signals for smart and analog positioners.

  • Remote I/O Powering: Supplies isolated loop power and control signals to remote transmitters and actuators.

  • Harsh Environment Installations: Extended temperature range suits offshore, arctic, or desert sites.


Competitive Comparison

Feature DS3800HAIC1B1A DS3800HAIC1A1A GE DS3800HAIA (Higher Amp) GE DS3800HACB (Non-Isolated)
Per-Channel Isolation Yes (2500Vrms) Yes (1500Vrms) Yes (2500Vrms) No
Max Current 90mA 80mA 100mA 60mA
Compliance Voltage 26V (650Ω @ 20mA) 24V (600Ω @ 20mA) 24V (600Ω @ 20mA) 24V (600Ω @ 20mA)
Temperature Drift ±0.015%/°C ±0.02%/°C ±0.02%/°C ±0.02%/°C
Temperature Range -40°C to +70°C 0°C to +60°C -40°C to +70°C -40°C to +70°C
Thermal Monitoring Yes No No No
Diagnostics LED + over-temp LED LED LED + backplane
Compatibility Mark IV Rev. L+ Mark IV Mark IV Mark IV

The GE DS3800HAIC1B1A offers significant improvements over the “1A1A” revision in isolation, drive capability, accuracy, and environmental tolerance.


Selection Guidelines & Precautions

  1. Isolation Requirements: Provides 2500Vrms per channel. Ensure this meets your system’s safety requirements.

  2. Loop Configuration: Verify sourcing or sinking mode. Set jumpers accordingly.

  3. Load Resistance: Calculate total loop resistance. Drives up to 650Ω at 20mA. Exceeding this causes saturation.

  4. Loop Power: Each channel has isolated loop power. Ensure field devices do not have their own power supply.

  5. Cable Length: Supports cables up to 1300m. For longer runs, reduce load or use a repeater.

  6. Thermal Monitoring: Observe thermal LED during sustained high-current operation to prevent over-temperature conditions.

  7. Short-Circuit Protection: Protected, but repeated shorting may affect reliability.

  8. Commissioning: Use a precision current meter to verify each channel. Calibrate using onboard trimmers if necessary.

  9. Wiring: Use shielded twisted-pair cables; ground shield at board end only. Do not connect shield to isolated output circuit.

  10. ESD Handling: Use ESD-safe practices.

  11. Sourcing: Obsolete. Request functional test report including:

    • All 4 channels tested at 4mA and 20mA

    • Load regulation test (up to 650Ω)

    • Loop power verification (26V per channel)

    • Isolation test (2500Vrms per channel, channel-to-channel)

    • Diagnostic fault reporting validation (open-loop, short-circuit, over-temperature)

    • Accuracy and drift test (±0.015%/°C)

    • Protection validation

  12. Spare Strategy: Keep one spare GE DS3800HAIC1B1A on-site for critical isolated 4-20mA control applications. This revision is preferred over “1A1A” for harsh or high-power environments. If you require higher current capability (>90mA), consider the DS3800HAIA series.