Description
Technical Specifications
-
Product Type: High-Amplitude Isolated Current Output Board (Revision 1A1A)
-
Part Number: DS3800HAIC1A1A
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems
-
Output Channels: 4 independent isolated current outputs
-
Output Type: 4-20mA or 0-20mA (jumper-selectable), loop-powered
-
Drive Capability: Up to 80mA per channel (sourcing or sinking)
-
Loop Power: Internal 24Vdc isolated loop power per channel (galvanically isolated)
-
Compliance Voltage: 24Vdc (allows driving loads up to 600Ω at 20mA)
-
Isolation Voltage: 1500Vrms isolation per channel (channel-to-channel and channel-to-logic)
-
Resolution: 12-bit
-
Accuracy: ±0.1% of full scale at 25°C; ±0.02% per °C drift
-
Protection: Over-current, short-circuit, and reverse-polarity protection per channel
-
Diagnostics: Individual channel fault detection (open-loop, short-circuit) with LED indication
-
Temperature Range: 0°C to +60°C
-
Heat Dissipation: Integrated heatsink for high-power operation
-
MTBF: > 160,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
Per-Channel Galvanic Isolation: The GE DS3800HAIC1A1A provides individual 1500Vrms isolation for each output channel, eliminating ground loops and protecting logic from field-side faults.
-
High Drive Capability: Delivers up to 80mA per channel, suitable for driving multiple devices in parallel or long cable runs.
-
Loop-Powered Outputs: Integrated 24Vdc loop power per channel eliminates external power supplies.
-
Comprehensive Protection: Over-current, short-circuit, and reverse-polarity protection safeguards the board and field devices.
-
Diagnostic LEDs: Front-panel LEDs indicate output status and fault conditions per channel.
-
Proven Reliability: Initial revision with long field track record.
Typical Application Cases
-
Explosive Atmospheres (Ex/ATEX): Provides galvanic isolation suitable for driving devices in hazardous areas when used with appropriate external barriers.
-
Long-Distance Signal Transmission: Drives 4-20mA signals over distances up to 1200m with complete isolation.
-
I/P (Current-to-Pressure) Converters: Drives I/P converters for pneumatic valve actuators with full isolation.
-
Valve Positioners: Provides 4-20mA control signals for smart and analog positioners.
-
Remote I/O Powering: Supplies isolated loop power and control signals to remote transmitters and actuators.
Competitive Comparison
| Feature | DS3800HAIC1A1A | GE DS3800HAIC (Base) | GE DS3800HAIA (Higher Amp) | GE DS3800HACB (Non-Isolated) |
|---|---|---|---|---|
| Per-Channel Isolation | Yes (1500Vrms) | Yes (1500Vrms) | Yes (2500Vrms) | No |
| Max Current | 80mA | 80mA | 100mA | 60mA |
| Isolation Voltage | 1500Vrms | 1500Vrms | 2500Vrms | N/A |
| Temperature Range | 0°C to +60°C | 0°C to +60°C | -40°C to +70°C | -40°C to +70°C |
| Diagnostics | LED | LED | LED | LED + backplane |
| Compatibility | Mark IV | Mark IV | Mark IV | Mark IV |
The GE DS3800HAIC1A1A is functionally identical to the base DS3800HAIC, providing a cost-effective isolated current output solution with proven reliability.
Selection Guidelines & Precautions
-
Isolation Requirements: Provides 1500Vrms per channel. For higher isolation (2500Vrms) or extended temperature range, consider the DS3800HAIA series.
-
Loop Configuration: Verify sourcing or sinking mode. Set jumpers accordingly.
-
Load Resistance: Calculate total loop resistance. Drives up to 600Ω at 20mA. Exceeding this causes saturation.
-
Loop Power: Each channel has isolated loop power. Ensure field devices do not have their own power supply.
-
Cable Length: Supports cables up to 1200m. For longer runs, reduce load or use a repeater.
-
Short-Circuit Protection: Protected, but repeated shorting may affect reliability.
-
Commissioning: Use a precision current meter to verify each channel. Calibrate using onboard trimmers if necessary.
-
Wiring: Use shielded twisted-pair cables; ground shield at board end only. Do not connect shield to isolated output circuit.
-
ESD Handling: Use ESD-safe practices.
-
Sourcing: Obsolete. Request functional test report including:
-
All 4 channels tested at 4mA and 20mA
-
Load regulation test (up to 600Ω)
-
Loop power verification (24V per channel)
-
Isolation test (1500Vrms per channel, channel-to-channel)
-
Sourcing/sinking mode verification
-
Protection validation
-
-
Spare Strategy: Keep one spare GE DS3800HAIC1A1A on-site for critical isolated 4-20mA control applications. If you require higher isolation or temperature range, consider the DS3800HAIA series instead.

SCHNEIDER 140DDI35300
MITSUBISHI GS2107-WTBD
SCHNEIDER 140DDI35300


Reviews