DS3800HACA1A1A GE

¥999.00

The GE DS3800HACA1A1A is a High-Amplitude Current Analog output board for the GE Speedtronic Mark IV turbine control system. It is specifically designed for high-current 4-20mA loop-powered applications, providing robust output drive for field devices such as current-to-pneumatic (I/P) converters, valve positioners, and long-distance transmitters. The “1A1A” suffix indicates the initial production revision with fixed output modes and proven reliability.

Category:

Description

Technical Specifications

  • Product Type: High-Amplitude Current Analog Output Board (Revision 1A1A)

  • Part Number: DS3800HACA1A1A

  • Manufacturer: General Electric (GE)

  • System Compatibility: GE Speedtronic Mark IV Turbine Control Systems

  • Output Channels: 4 independent analog current outputs

  • Output Type: 4-20mA or 0-20mA (jumper-selectable), loop-powered

  • Drive Capability: Up to 50mA per channel (sourcing or sinking)

  • Loop Power: Internal 24Vdc loop power supply (isolated)

  • Compliance Voltage: 24Vdc (allows driving loads up to 600Ω at 20mA)

  • Resolution: 12-bit

  • Accuracy: ±0.1% of full scale at 25°C; ±0.02% per °C drift

  • Protection: Over-current, short-circuit, and reverse-polarity protection per channel

  • Isolation: 1500Vrms opto-isolation (logic-to-output)

  • Temperature Range: 0°C to +60°C

  • MTBF: > 150,000 hours (MIL-HDBK-217F)


Key Features & Advantages

  • High Drive Capability: The GE DS3800HACA1A1A delivers up to 50mA per channel, suitable for driving multiple field devices in parallel or long cable runs.

  • Loop-Powered Outputs: Integrated 24Vdc loop power eliminates the need for external power supplies for 4-20mA loops.

  • High Compliance Voltage: 24V compliance allows driving loads up to 600Ω, accommodating most industrial field devices.

  • Sourcing or Sinking: Jumper-selectable sourcing or sinking modes for flexibility with different device configurations.

  • Comprehensive Protection: Over-current, short-circuit, and reverse-polarity protection safeguards the board and field devices.

  • Diagnostic LEDs: Front-panel LEDs indicate output status, fault, and loop power presence per channel.

  • Proven Reliability: Initial revision with long field track record.


Typical Application Cases

  • I/P (Current-to-Pressure) Converters: Drives I/P converters that control pneumatic valve actuators.

  • Valve Positioners: Provides 4-20mA control signals for smart and analog valve positioners.

  • Long-Distance Transmitter Powering: Supplies loop power and control signal to remote transmitters over distances up to 1000m.

  • Variable Speed Drives (VSDs): Provides 4-20mA speed reference signals to VSDs.

  • Damper and Louver Actuators: Controls 4-20mA actuated dampers for airflow regulation.


Competitive Comparison

Feature DS3800HACA1A1A GE DS3800HACA (Base) GE DS3800HA1C (Voltage) Modern Analog Output Module
Output Type Current (4-20mA) Current (4-20mA) Voltage or current Voltage or current
Max Current 50mA 50mA 2A (voltage mode) 20-25mA
Loop Power Internal (24V) Internal (24V) N/A External required
Compliance Voltage 24V (600Ω load) 24V (600Ω load) N/A 12-15V
Isolation 1500Vrms 1500Vrms 1500Vrms 500Vrms
Temperature Range 0°C to +60°C 0°C to +60°C 0°C to +60°C 0°C to +60°C
Compatibility Mark IV Mark IV Mark IV Universal fieldbus

The GE DS3800HACA1A1A is functionally identical to the base DS3800HACA and is the preferred board for high-current 4-20mA loop-powered applications.


Selection Guidelines & Precautions

  1. Loop Configuration: Verify sourcing or sinking mode for your field devices. Set jumpers on GE DS3800HACA1A1A accordingly.

  2. Load Resistance: Calculate total loop resistance (device + cable). The GE DS3800HACA1A1A drives up to 600Ω at 20mA. Exceeding this will cause saturation.

  3. Loop Power: The internal 24V loop power is isolated. Ensure field devices do not have their own power supply.

  4. Cable Length: Supports cables up to 1000m. For longer runs, reduce load or use a repeater.

  5. Short-Circuit Protection: Protected, but repeated shorting may affect reliability. Check wiring before power-up.

  6. Reverse Polarity: Protected, but verify wiring to avoid fault indications.

  7. Commissioning: Use a precision current meter to verify each channel. Calibrate using onboard trimmers if necessary.

  8. Wiring: Use shielded twisted-pair cables; ground shield at board end only.

  9. ESD Handling: Use ESD-safe practices.

  10. Sourcing: Obsolete. Request functional test report including:

    • All 4 channels tested at 4mA and 20mA

    • Load regulation test (up to 600Ω)

    • Loop power verification (24V)

    • Sourcing/sinking mode verification

    • Over-current and reverse-polarity protection validation

  11. Spare Strategy: Keep one spare GE DS3800HACA1A1A on-site for critical 4-20mA control applications

GE IC200GBI001
3RX9501-0BA00
GE IC200GBI001