DS3800DXRC1D1B GE

¥999.00

The GE DS3800DXRC1D1B is a Digital Expansion Relay and Alarm board for the GE Speedtronic Mark IV turbine control system. It provides 16 additional relay outputs as a slave expansion board. The “C1D1B” suffix indicates a high-specification revision with latching relay capabilityenhanced diagnostics, and improved backplane communication, bridging the gap between standard expansion and latching flag boards.

Category:

Description

Technical Specifications

  • Product Type: Digital Expansion Relay & Alarm Board (Revision C1D1B)

  • Part Number: DS3800DXRC1D1B

  • Manufacturer: General Electric (GE)

  • System Compatibility: GE Speedtronic Mark IV Turbine Control Systems

  • Output Channels: 16 digital outputs (Form C – SPDT relays)

  • Relay Type: Magnetic latching relays (maintain state after power loss)

  • Contact Rating: 5A @ 250VAC or 5A @ 30VDC (resistive); 3A @ 250VAC (inductive)

  • Surge Suppression: Enhanced RC snubbers + bidirectional TVS diodes

  • Indicators: Front-panel LEDs per channel + mechanical flag indicators (latching)

  • Isolation: 2500Vrms reinforced opto-isolation

  • Expansion Interface: Backplane slave connection; address configurable via DIP switches

  • Diagnostics: Individual channel fault detection and status reporting via backplane

  • Temperature Range: -40°C to +70°C

  • MTBF: > 200,000 hours (MIL-HDBK-217F)


Key Features & Advantages

  • Latching Relays with Flags: The GE DS3800DXRC1D1B is the only expansion relay board with magnetic latching relays and mechanical flags, combining the functionality of both DS3800DXRA (expansion) and DS3800DRFA (flags) into a single board.

  • State Retention: Magnetic latching relays maintain their state after power loss, critical for trip circuits that require visual and electrical memory of alarm conditions.

  • Mechanical Flag Indicators: Provide instant visual confirmation of relay status without tools or software.

  • Enhanced Diagnostics: Individual channel fault detection reported via backplane to the Mark IV processor.

  • Reinforced Isolation: 2500Vrms for ground loop and transient protection.

  • Flexible Addressing: DIP switch configuration for easy address assignment.

  • Diagnostic LEDs: Front-panel LEDs indicate output status, fault, and flag state.


Typical Application Cases

  • Critical Trip Circuits: The GE DS3800DXRC1D1B provides latching outputs for emergency shutdown valves, maintaining trip state after power loss with mechanical flag indication.

  • Alarm Annunciation with Memory: Provides alarms that remain visually indicated even after power cycles, aiding post-trip fault analysis.

  • Expanded Latching Outputs: Adds latching relay capacity beyond the base DS3800DRFA boards.

  • Remote Signaling with Latching: Sends latched status signals to plant DCS, maintaining state during communication interruptions.

  • Retrofit Projects: Replaces combination of separate expansion and flag boards, saving rack space.


Competitive Comparison

Feature DS3800DXRC1D1B DS3800DXRA1C1C DS3800DRFA1B1A DS3800DXRA1A1A
Relay Type Latching Standard Latching Standard
Mechanical Flags Yes No Yes No
Inductive Load Rating 3A 3A 2A 2A
Isolation 2500Vrms 2500Vrms 2500Vrms 1500Vrms
Diagnostic Reporting Yes (backplane) No No No
Slave Expansion Yes Yes No Yes
Temperature Range -40°C to +70°C -40°C to +70°C -40°C to +70°C 0°C to +60°C
Surge Suppression RC + TVS RC + TVS RC + TVS RC + flyback

The GE DS3800DXRC1D1B uniquely combines latching relays, mechanical flags, and expansion capability in a single board, offering the most functionality in the expansion relay family.


Selection Guidelines & Precautions

  1. Latching Relay Reset: After a trip, latching relays must be reset via a command from the Mark IV processor or manual reset button. The GE DS3800DXRC1D1B will retain its state until reset, preventing turbine restart if not cleared.

  2. Processor Compatibility: Verify Mark IV firmware supports diagnostic reporting from expansion boards. Earlier firmware may ignore fault data.

  3. Flag Maintenance: Mechanical flags can stick after prolonged idle periods. Cycle each channel during commissioning to ensure free movement.

  4. Address Configuration: Set DIP switches correctly to avoid backplane address conflicts.

  5. Contact Current: Do not exceed 5A resistive or 3A inductive. Use external interposing relays for larger loads.

  6. Wiring: Use shielded cables; ground shield at board end only.

  7. ESD Handling: Use ESD-safe practices.

  8. Sourcing: Obsolete. Request functional test report including:

    • All 16 channels tested under rated load (resistive and inductive)

    • Latching functionality verified (state retention after power cycle)

    • Mechanical flag operation verified

    • Diagnostic reporting validated via backplane

    • Contact resistance (< 0.1Ω new, < 0.5Ω refurbished)

    • Surge suppression verification

    • Isolation test (2500Vrms)

  9. Spare Strategy: Keep one spare GE DS3800DXRC1D1B on-site, especially for critical trip circuits. Consider this board the preferred replacement when both expansion and latching/flag functionality are required.

Bently 330130-040-00-00