Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization and improved thermal isolation (better than standard G2)
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Operating Temp: -30°C to +70°C
Storage Temp: -40°C to +85°C
Mounting: VME rack
Suffix “G2A”: High accuracy + advanced diagnostics (drift, degradation, sense-lead) + G2 wiring configuration + extended upper temperature (70°C) + enhanced cold-junction compensation + standard conformal coating
Key Features
High accuracy – ±0.08% for critical temperature monitoring
Advanced diagnostics – drift monitoring, degradation prediction, sense-lead integrity, and open/short detection
Extended upper temperature limit – operates up to 70°C, suitable for hotter cabinets
Enhanced cold-junction compensation – better linearization across ambient variations than standard G2
G2-specific wiring configuration – unique channel-to-terminal mapping matching specific GE cabinet wiring standards; direct drop-in for G2-configured systems
Faster sampling – 10 Hz for responsive monitoring
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health with diagnostic indicators
Standard conformal coating for moisture/dust resistance
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Legacy gas turbine retrofits with G2 wiring – where existing field wiring uses G2 terminal assignments and high accuracy with diagnostics and improved compensation is required
Steam turbine bearing monitoring in G2 cabinets – critical protection with drift anticipation and enhanced ambient stability
Pipeline compressor stations with G2-configured cabinets – precision monitoring with predictive maintenance
Industrial cogeneration plants – where OEM specified G2 wiring for thermocouple terminations
Facilities with G2-standard cabinets requiring diagnostic insights
Comparison with Competitors
| Feature | DS200TCQBG2A |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Diagnostics | Drift + degradation + open/short | Group-level | Per-channel + HART |
| Cold Junction Compensation | Enhanced | Standard | Standard |
| Temp Range | -30°C to +70°C | -25°C to +65°C | -20°C to +60°C |
| Wiring Config | G2-specific | Standard | Standard |
| GE Native Integration with G2 Cabs | Yes (direct fit) | No | No |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
Selection Tips
Choose the DS200TCQBG2A only if your cabinet uses G2 wiring configuration and you require high accuracy (±0.08%) with advanced diagnostics and enhanced cold-junction compensation – this board combines precision, predictive maintenance, improved stability, and G2 pinout compatibility
For G2 systems with the same features but standard cold-junction compensation, consider DS200TCQBG2 (if available)
For G2 systems with high accuracy but no diagnostics, consider DS200TCEAG2B
For G2 systems with basic accuracy without diagnostics, the DS200TCDAG2B is more economical
For G1 systems requiring similar features, use the DS200TCQBG1A
If you are rewiring the cabinet, consider converting to G1 and using DS200TCQBG1A or DS200TCDAG1ADA
Verify existing wiring pinout against G2 standard – using the wrong terminal block or miswiring will scramble channel readings
Source refurbished units with G2 pinout verification and diagnostic test validation in the test report
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -30°C to +70°C operating range – exceeding 70°C reduces component life
Pinout critical – G2 mapping differs from G1; verify cabinet wiring before installation
Calibrate every 24 months – diagnostics, enhanced accuracy, and cold-junction compensation depend on a valid baseline calibration
Ground shields only at the board end
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
Monitor diagnostic logs – drift warnings indicate sensor aging; plan proactive replacement
Label clearly – mark board and slot as “TCQBG2A – DIAG/EXT TEMP/ENH CJC/G2” to ensure proper handling and prevent future miswiring with G1 boards
Do not mix G1 and G2 boards without verifying terminal block compatibility in the same rack
Monitor cabinet temperature – if consistently near 70°C, consider cooling improvements or upgrade to wider-range variants if needed

NI NI-9505
SAC IOP331
ABB TET106 11355-0-6050000
A-B 1747-L542


Reviews