Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization and thermal isolation
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Temp Range: -30°C to +70°C (operating) – wider upper limit than G1A (65°C)
Storage: -40°C to +85°C
Mounting: VME rack
Suffix “G1B”: Enhanced accuracy + G1 wiring + extended diagnostics (drift, degradation, sense-lead integrity) + extended upper temperature limit (70°C) + fixed firmware
Key Features
-
Enhanced accuracy – ±0.08% for critical temperature monitoring
-
Extended diagnostics – drift monitoring, degradation prediction, and sense-lead integrity checks (beyond basic open/short)
-
Faster sampling – 10 Hz for responsive monitoring
-
Extended upper temperature limit – operates up to 70°C, suitable for hotter cabinets
-
Improved cold-junction compensation – stable readings across ambient variations
-
Simple swap – no firmware changes required in most Mark V systems
-
LED status per channel + board health, with extended diagnostic indicators
-
Standard conformal coating for moisture/dust resistance
-
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
-
Gas turbine EGT monitoring in hot climates – where cabinet temperatures reach 65–70°C and predictive diagnostics are valuable
-
Steam turbine bearings in poorly ventilated areas – critical protection with drift anticipation
-
Generator stator cooling in tropical environments – precision measurement with diagnostic assurance
-
Compressor performance monitoring in desert installations – reliability under thermal stress
-
Critical points requiring both high accuracy and early fault warnings
Comparison with Competitors
| Feature | DS200TCPDG1B |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Diagnostics | Drift + degradation + open/short | Group-level | Per-channel + HART |
| Temp Range | -30°C to +70°C | -25°C to +65°C | -20°C to +60°C |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
| GE Native Integration | Yes | No | No |
Selection Tips
-
Choose the
DS200TCPDG1Bif you need high accuracy, extended diagnostics, and the ability to operate at up to 70°C in a G1 cabinet -
For the same features but standard temperature (65°C), the
DS200TCPDG1Amay be sufficient -
For high accuracy with extended diagnostics and extreme environmental protection (wider range, coatings), consider
DS200TCDAH1BGD(4-wire) orDS200TCDAG1ADA(2-wire) -
For basic accuracy without diagnostics, the
DS200TCEBG1Bis more economical -
Source refurbished units with diagnostic validation and drift baseline records
Precautions
-
ESD sensitive – use wrist strap
-
Power down for Mark V removal (no hot-swap)
-
Torque terminals to 0.5 N·m max
-
Do not exceed -30°C to +70°C operating range – exceeding 70°C reduces component life
-
Calibrate every 24 months – extended diagnostics depend on valid baseline calibration
-
Ground shields only at the board end
-
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
-
Monitor diagnostic logs – drift warnings indicate sensor aging; plan proactive replacement
-
Label clearly – mark as “G1B PRECISION + DIAG” to ensure proper handling and maintenance tracking
-
Monitor cabinet temperature – if consistently near 70°C, consider cooling improvements or upgrade to -40°C to +75°C variants if needed

FUJI EW400EAGC-3P250J
BENTLY 1701/06
SCHNEIDER 140CRA93200
Inovance MD290T18.5G/22P


Reviews
There are no reviews yet.