Description
Technical Parameters
Manufacturer: GE
Series: Mark V / Mark VIe
Channels: 16 differential
Input Range: -10 mV to +100 mV (Type J/K/T/E)
Cold Junction: Single onboard sensor with enhanced linearization
Isolation: 1500V AC
Accuracy: ±0.08% at 25°C, ±0.15% across full temperature range
Sampling: 10 Hz sequential
Temp Range: -30°C to +65°C (operating), -40°C to +85°C (storage)
Mounting: VME rack
Suffix “G1A”: Enhanced accuracy + G1 wiring configuration + basic diagnostics (open/short only) + fixed firmware
Key Features
Enhanced accuracy – ±0.08% for high-precision temperature monitoring
Faster sampling – 10 Hz for responsive monitoring compared to standard G1 series
Improved cold-junction compensation – stable readings across ambient temperature variations
Basic self-diagnostics – open-circuit and short-circuit detection per channel
Simple swap – no firmware changes required in most Mark V systems
LED status per channel + board health
Standard conformal coating for moisture/dust resistance
Backward compatible with Mark V and Mark VIe (hot-swap only on VIe Rev D+)
Applications
Gas turbine EGT monitoring – tighter accuracy improves combustion control and thermal efficiency
Steam turbine bearing and casing temperatures – critical protection with precision measurements
Generator stator cooling monitoring – accurate over-temperature detection
HRSG temperature measurements – improved thermal efficiency tracking
Compressor performance monitoring – precision data for performance optimization
Comparison with Competitors
| Feature | DS200TCPAG1A |
ABB TTH300 | Siemens 7KG7750 |
|---|---|---|---|
| Channels | 16 | 8 | 12 |
| Accuracy | ±0.08% | ±0.10% | ±0.12% |
| Sampling | 10 Hz | 10 Hz (simultaneous) | 8 Hz (simultaneous) |
| Temp Range | -30°C to +65°C | -25°C to +65°C | -20°C to +60°C |
| Diagnostics | Open/short | Group-level | Per-channel + HART |
| Hot-Swap | No (V) / Yes (VIe) | No | Yes |
| GE Native Integration | Yes | No | No |
Selection Tips
Choose the DS200TCPAG1A if you need enhanced accuracy (±0.08%) and faster sampling (10 Hz) with G1 wiring
For basic monitoring where ±0.12% is acceptable, the DS200TCEBG1 is more economical
For the same accuracy with extended temperature range, consider DS200TCEAG1B
For advanced diagnostics (drift/degradation), consider DS200TCDAG1ADA
Verify existing wiring is 2-wire standard – G1-series terminal mapping applies
Source refurbished units with accuracy verification in test report
Precautions
ESD sensitive – use wrist strap
Power down for Mark V removal (no hot-swap)
Torque terminals to 0.5 N·m max
Do not exceed -30°C to +65°C operating range
Calibrate every 24 months – accuracy spec depends on valid calibration
Ground shields only at the board end
Verify thermocouple type – optimized for J/K (T/E reduces accuracy to ±0.15%)
Label clearly – mark as “G1A PRECISION” to distinguish from lower-accuracy boards

A-B 1785-L60B
APC AP7721
A-B SST-PFB-SLC
WESTINGHOUSE 1C31169G02


Reviews