Description
Key Technical Parameters
| Parameter | Specification |
|---|---|
| Function | Remote terminal board for field I/O wiring (enhanced capacity, 2A outputs, coated, high-current configuration) |
| Terminal Capacity | 80 terminals (5x 16-terminal blocks) – highest in RTBA family |
| Output Current Capacity | 2A per channel (highest in RTBA family) |
| I/O Types Supported | Analog inputs (4-20mA, 0-10V), digital inputs (24-125 VDC), digital outputs (relay/transistor), thermocouple, RTD |
| Wire Gauge | 12-22 AWG (solid/stranded) |
| Terminal Type | Screw-clamp (rise-clamp) with dual-wire entry capability |
| Fuse Protection | 20 onboard fuses – one per output channel, user-replaceable, 2A rating, with LED indication and current sensing |
| Diagnostic Indicators | 26 LEDs – 20 channel status LEDs (green/red), 5 block-level “CHANNEL BLOCK” LEDs, 1 “PWR OK” LED, 1 “COAT OK” LED (coating integrity), 1 “WARN” LED (pre-failure), 1 “BUS ACT” LED (backplane communication), 1 “S-COM” LED (serial communication), 1 “COM ACT” LED (communication active) |
| Enhanced Monitoring | Individual channel current sensing (up to 2A), fuse health monitoring, temperature sensing, channel impedance monitoring, remote communication status |
| Isolation | 2,500 VAC isolation between field side and control side |
| Conformal Coating | Acrylic (Humiseal 1B73), 0.002-0.003″ thickness, 1,000 hr salt-spray rated |
| Temperature Range | 0 to +60°C ambient (extended from +55°C) |
| Form Factor | 6U VME, 1-slot width (fits in remote junction box or dedicated slot) |
| Weight | 0.63 kg (approx. 1.39 lbs) |
Advantages & Core Features
-
Highest terminal capacity with conformal coating and high-current outputs – The DS200RTBAG2AHC provides 80 terminals, 2A per channel output capacity, and conformal coating – prioritizing maximum current delivery over fieldbus communication, making it the ultimate high-current remote I/O solution for harsh environments.
-
Highest output current capacity (2A per channel) – Supports direct control of higher-power field devices (solenoid valves, contactors, small motors) without external interposing relays, reducing system cost and complexity.
-
Conformal coating with integrity monitoring – The white “COAT OK” LED provides real-time validation of coating integrity, ensuring protection against moisture, salt spray, and chemical exposure.
-
Pre-failure amber WARN LED – Alerts operators to potential issues (channel drift, temperature rise, fuse degradation, impedance changes) before a full fault occurs, enabling predictive maintenance in remote locations.
-
Enhanced monitoring – Individual channel current sensing (up to 2A), impedance monitoring, temperature monitoring, and remote communication monitoring.
-
Individual channel fusing – Each output channel is protected by a user-replaceable fuse (20 total) with LED indication.
-
Galvanic isolation – 2,500 VAC isolation protects the Mark V backplane and processor from field-side voltage spikes.
-
Extended temperature range – 0 to +60°C ambient allows use in warm environments.
-
Compact 1-slot form factor – Occupies a single slot, maximizing rack space.
Key Differences vs. DS200RTBAG2AGC (Advanced Configuration with Fieldbus)
| Feature | DS200RTBAG2AGC (Advanced, Fieldbus) | DS200RTBAG2AHC (High-Current) |
|---|---|---|
| Fieldbus Interface | Yes (Profibus DP, MODBUS RTU, FF) | No |
| Diagnostic LEDs | 32 | 26 |
| Fieldbus LEDs | BUS ACT, FB-ERR, FB-LINK | None |
| Wiring Reduction | Yes | No |
| Smart Device Support | Yes | No |
| Availability | Exceedingly rare+++ (26-32 wks) | Exceedingly rare++ (24-30 wks) |
| Cost | Premium++++ | Premium+++ |
Note: Conventional I/O specifications (80 terminals, 2A per channel, 20 fuses, individual channel current sensing, impedance monitoring, COAT OK, WARN, BUS ACT, S-COM, COM ACT) are identical.
Application Cases
-
Offshore platform with high-power actuators – A North Sea platform uses the DS200RTBAG2AHC to provide 80 terminals and 2A outputs for direct control of solenoid valves and actuators without external relays. The conformal coating protects against salt spray, and the white COAT OK LED confirms coating integrity in the harsh marine environment.
-
Coastal plant with high-current outputs – A Florida combined-cycle facility uses the DS200RTBAG2AHC for its 80-terminal capacity and 2A outputs, supporting direct control of contactors and small motors. The impedance monitoring detected a gradual increase in resistance on a high-current circuit, preventing a potential failure.
-
Chemical plant with H₂S exposure – A petrochemical facility uses the DS200RTBAG2AHC to provide 80 terminals and 2A outputs for direct control of actuators in H₂S-exposed areas. The conformal coating protects against corrosion, and the WARN LED provides early warning of channel degradation.
-
Large gas turbine with high-power distributed I/O – A 500 MW combined-cycle plant uses the DS200RTBAG2AHC to terminate 80 conventional I/O points with 2A outputs for direct control of field devices, all with conformal coating protection for the coastal environment.
Comparison with Related Variants
| Feature | DS200RTBAG2AHC (High-Current, Coated) | DS200RTBAG2AGC (Advanced, Fieldbus) | DS200RTBAG2AFB (Uncoated, Fieldbus) | DS200RTBAG1AEB (Coated, G1A) |
|---|---|---|---|---|
| Terminal Capacity | 80 | 80 | 80 | 64 |
| Output Current Capacity | 2A | 2A | 2A | 1A |
| Conformal Coating | Yes | Yes | No | Yes |
| Fieldbus Interface | No | Yes | Yes | No |
| Diagnostic LEDs | 26 | 32 | 28 | 24 |
| COAT OK LED | Yes | Yes | No | Yes |
| Impedance Monitoring | Yes | Yes | No | Yes |
| Remote Communication Monitoring | Yes | Yes | No | No |
| Temp Range | 0 to +60°C | 0 to +60°C | 0 to +55°C | 0 to +60°C |
| Availability | Exceedingly rare++ (24-30 wks) | Exceedingly rare+++ (26-32 wks) | Exceedingly rare++ (22-28 wks) | Exceedingly rare+ (18-22 wks) |
| Cost | Premium+++ | Premium++++ | Premium+++ | Premium++ |
Selection Suggestions
-
Assess I/O density, current, and environmental requirements – Select the DS200RTBAG2AHC if you need more than 64 terminals, more than 1A per channel, AND conformal coating, but do NOT need fieldbus communication. This is the board for high-current applications without fieldbus.
-
Assess environmental conditions – The DS200RTBAG2AHC is essential if your installation is harsh (coastal, offshore, chemical, high-humidity, high-temperature) AND you need the highest density and current.
-
Evaluate diagnostic requirements – The enhanced LED array, impedance monitoring, and remote communication monitoring are valuable for predictive maintenance.
-
Verify communication interface – Ensure the board’s interface is compatible with your Mark V rack.
-
Check slot availability – Occupies a single slot.
-
Procurement – The DS200RTBAG2AHC is among the rarest Mark V boards. Only purchase from suppliers providing:
-
Coating thickness verification
-
LED testing (all 26 LEDs)
-
Channel verification (all 80 terminals, 2A per channel)
-
Fuse verification (20 fuses, 2A)
-
Current sensing and impedance monitoring validation
-
S-COM/COM ACT LED functionality verification
Lead times: 24-30 weeks.
-
-
Stock spares – Maintain at least two spares on-site.
Important Precautions
-
Power down completely – De-energize the entire system before insertion or removal. Hot-swapping is not supported.
-
ESD protection – Use wrist strap and anti-static mat.
-
Wiring termination – Ensure field wires are properly stripped and securely clamped. Use appropriate wire gauge (12-22 AWG).
-
Coating integrity check – On power-up, verify white “COAT OK” LED illuminates. If off, remove and return for recoating.
-
Pre-failure WARN LED – If amber WARN LED illuminates, investigate immediately.
-
Fuse replacement – Replace fuses only with specified types and ratings (2A).
-
Check total current draw – Ensure total current draw on each rail does not exceed capacity.
-
Signal segregation – Route analog and digital signals separately to avoid noise coupling.
-
Cleaning – Use only dry compressed air (max 50 PSI, 30 cm distance). No solvents, alcohol, or brushes.
-
Storage – Store at 10-30°C, 20-50% RH. Rotate every 3 years.
Final Expert Recommendation
The DS200RTBAG2AHC represents the ultimate Mark V remote terminal board for high-current applications in harsh environments, combining the highest terminal capacity (80 terminals), highest output current capacity (2A per channel), conformal coating, and comprehensive diagnostics (26 LEDs, impedance monitoring, remote communication monitoring) in a compact 1-slot package. It is the definitive solution for high-current distributed control installations requiring maximum density, current, and protection, without fieldbus communication.
Select the DS200RTBAG2AHC only when:
-
You have more than 64 remote field connections to terminate (up to 80)
-
Your output devices require more than 1A per channel (up to 2A)
-
Your installation is harsh (coastal, offshore, chemical, high-humidity, high-temperature)
-
You do NOT need fieldbus communication (if you do, choose the DS200RTBAG2AGC)
-
You need comprehensive diagnostics (26 LEDs, impedance monitoring, remote communication monitoring)
-
You require extended temperature range (up to +60°C)
For most applications, the DS200RTBAG1AEB (coated, 64 terminals, 1A per channel) provides excellent protection and diagnostics at significantly lower cost and lead time. The DS200RTBAG2AHC should be reserved for the most demanding applications where the combination of maximum density, current, and protection is absolutely essential and fieldbus is not required.
When sourcing the DS200RTBAG2AHC, ensure comprehensive documentation – coating verification, LED testing, channel verification, current sensing validation, and S-COM/COM ACT functionality verification. Given its exceedingly rare availability, maintain at least two spares on-site. Properly deployed, this board provides years of reliable, high-density, high-current, protected remote I/O for Mark V turbine control systems in the most challenging operating environments.

WOODWARD 5466-316
ABB PM803F
TRICONEX 3721
TRICONEX 4351B