Danfoss EKC 361

¥9,999.00

Danfoss EKC 361 is a PID modulating medium temperature controller for refrigeration evaporator systems, used together with Danfoss ICS / PM / ICM regulating valves. It precisely controls evaporator temperature, keeps evaporator temperature as high as possible to maintain air humidity and reduce product dehydration loss. It is an obsolete Danfoss refrigeration controller, part number 084B7060

Category:

Description

Specifications

  • Model: EKC 361
  • Power supply: 24 VAC
  • Control algorithm: PID with adaptive response
  • Accuracy: ±0.25°C after stabilizationassets.dan…
  • Sensors: Main medium temperature sensor Sair, optional auxiliary sensor Saux
  • Inputs: Digital start/stop input, analog setpoint offset input
  • Outputs: Analog modulating output for pilot valve CVQ/CVE; relay outputs for fan and liquid line solenoid valve
  • Display: 3-digit LCD, °C / °F selectable
  • Buttons: Two keys for parameter setting
  • Mounting: Panel cut-out mounting
  • Operating temperature: -20°C ~ +60°C
  • Weight: approx 0.32 kgDanfoss Gl…
  • Communication: Optional communication module RC8AC

Advantages and Features

Danfoss EKC 361 has three adaptive response curves for different application requirements: fast cooling with minor overshoot, gentle cooling with small fluctuation, and cooling without temperature overshootassets.dan…. It provides high and low temperature alarm functions, relay alarm output. It can control fan and liquid solenoid valve in linkage. It features simple menu structure and local fault code display for troubleshooting. It is widely used in cold storage, food refrigeration rooms requiring strict humidity control.

Application & Case

It is mainly used in food cold storage, supermarket refrigerated display cabinets and industrial refrigeration evaporator control loops. In a cold storage renovation project, EKC 361 replaced the old temperature controller; after parameter commissioning, evaporator temperature stabilized, humidity control and high/low temperature alarm worked normally.

Comparison

Compared with EKC 366 interface controller, EKC 361 is a standalone local temperature controller without relying on PLC analog output. It is dedicated to evaporator temperature control and cannot be used for compressor capacity control. EKC series models are not interchangeable.

Selection Notes

Confirm the full model EKC 361, confirm matching ICS/PM/ICM valve and CVQ/CVE pilot. This model is discontinued, spare stock is limited.

Precautions

Cut off 24VAC power before replacement. Check sensor polarity and wiring. After installation, set PID parameters, temperature setpoint and alarm limits, test fan, solenoid valve linkage and alarm output before putting into service.