Description
Technical Specifications
-
Product Type: High-Amplitude Analog Output Board
-
Part Number: DS3800HA1C
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems
-
Output Channels: 4 independent analog output channels
-
Output Type: 0-10Vdc, 0-20mA, 4-20mA, or ±10Vdc (jumper-selectable)
-
Drive Capability: Up to 2A per channel (voltage mode); up to 50mA (current mode)
-
Resolution: 12-bit
-
Accuracy: ±0.1% of full scale at 25°C; ±0.02% per °C drift
-
Protection: Over-current, short-circuit, and thermal shutdown protection per channel
-
Isolation: 1500Vrms opto-isolation between logic and output sections
-
Heat Dissipation: Integrated heatsink for high-power operation
-
Temperature Range: 0°C to +60°C
-
MTBF: > 100,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
High Drive Capability: The GE DS3800HA1C delivers up to 2A per channel, making it suitable for direct driving of high-power field devices without external amplifiers.
-
Multiple Output Modes: Jumper-selectable voltage (0-10V, ±10V) or current (0-20mA, 4-20mA) outputs provide flexibility for various field devices.
-
Integrated Protection: Over-current, short-circuit, and thermal shutdown protect both the board and connected field devices from damage.
-
Thermal Management: Built-in heatsink allows sustained high-power operation without derating.
-
Diagnostic LEDs: Front-panel LEDs indicate output status, current limit activation, and thermal warning per channel.
-
12-Bit Resolution: Provides accurate, fine-grained control for precision applications.
Typical Application Cases
-
Proportional Solenoid Control: The GE DS3800HA1C drives proportional solenoids used in hydraulic valve positioning.
-
Motor-Operated Valve (MOV) Control: Provides control signals for MOV actuators requiring 4-20mA or 0-10V inputs.
-
Hydraulic Actuator Control: Drives high-power hydraulic actuators that require > 50mA input current.
-
Fuel Control Actuators: In some installations, the GE DS3800HA1C replaces servo driver boards for fuel valve control.
-
Excitation Systems: Provides control outputs for generator excitation systems requiring high-current analog signals.
Competitive Comparison
| Feature | GE DS3800HA1C | GE DS3800DSAB (Servo Amp) | GE DS3800DSQD (Quad Driver) | Modern Analog Output Module |
|---|---|---|---|---|
| Primary Function | High-power analog output | Servo valve drive | High-current servo drive | Standard analog output |
| Output Type | Voltage or current | Current (±20/40/80mA) | Current (±80-250mA) | Voltage or current |
| Max Current | 2A (voltage mode) | ±80mA | ±250mA | 20-50mA |
| Resolution | 12-bit | 12-bit | 12-bit | 16-bit |
| Protection | Over-current + thermal | Over-current only | Over-current + thermal | Short-circuit only |
| Heatsink | Yes | No | Yes | No |
| Isolation | 1500Vrms | 1500Vrms | 1500Vrms | 500Vrms |
| Compatibility | Mark IV | Mark IV | Mark IV | Universal fieldbus |
The GE DS3800HA1C offers the highest output current capability of any Mark IV analog output board, making it essential for direct high-power actuation.
Selection Guidelines & Precautions
-
Output Mode Selection: Configure jumpers to match your field device input requirements (voltage or current). Incorrect mode selection may damage the device or the GE DS3800HA1C.
-
Load Verification: Confirm the field device’s input impedance and current requirements. The GE DS3800HA1C can drive up to 2A in voltage mode; ensure your load does not exceed this.
-
Thermal Management: The GE DS3800HA1C dissipates significant heat at high output currents. Ensure cabinet airflow is adequate (minimum 100 CFM across the board).
-
Power Supply Capacity: The GE DS3800HA1C draws significant power from the backplane. Verify your Mark IV power supply can handle the additional load.
-
Short-Circuit Protection: While protected, repeated shorting may reduce output capability over time.
-
Wiring: Use shielded cables for analog outputs, especially for long cable runs (> 50m).
-
Commissioning: Start with reduced output and gradually increase to verify correct operation before full power application.
-
ESD Handling: Use ESD-safe practices.
-
Sourcing: Obsolete. Request functional test report including:
-
All 4 channels tested in all output modes
-
Load regulation test (2A capability)
-
Short-circuit and thermal protection validation
-
Accuracy test (±0.1%)
-
-
Spare Strategy: Keep one spare GE DS3800HA1C on-site if you rely on it for critical high-power control functions.

ABB HDZ-70-30 B65W DC220V
SCHNEIDER 140DDI35300
A-B 1756-IM16I