Description
Technical Parameters
| Parameter | Specification |
|---|---|
| Input Voltage | 125 VDC nominal (range 100–150 VDC) |
| Output Rails | 125 VDC / 5A (field device power), +24 VDC / 0.5A (auxiliary control power) |
| Isolation | Full isolation (1.5kV input-to-output) |
| Protection | Overcurrent protection (fixed), short-circuit protection, transient suppression, reverse polarity protection |
| Monitoring | 1 analog feedback channel for voltage monitoring; 1 digital output for fault alarm |
| Operating Temperature | –25°C to +60°C |
| Form Factor | 6U × 8HP (40mm) – requires 2 slots |
| Backplane Connector | Standard VME 96-pin P1 + reinforced 60-pin P2 (high-current) |
| Status LEDs | 4 indicators: POWER ON (green), OUTPUT OK (green), FAULT (red), OVERTEMP (yellow) |
| Certifications | CE, UL 508 (non-hazardous locations only) |
| Efficiency | ~84% at full load |
Critical note: The DS3800NPSL1A1A is physically wider (8HP) and not interchangeable with logic power boards (NPSE, NPSK). It is designed for field power distribution only. Hot-swapping is not supported. This board does not supply +5V or ±15V logic power.
Key Features & Advantages
-
High-Voltage Field Power – The DS3800NPSL1A1A provides conditioned 125VDC power for solenoid valves, hydraulic actuators, and motor starters, reducing the need for separate field power supplies.
-
Full Isolation – 1.5kV isolation protects sensitive control electronics from field device transients and ground-loop currents.
-
Auxiliary +24V Control Power – A dedicated 24V/0.5A output provides power for field-mounted control relays or proximity sensors, eliminating separate power supplies.
-
Built-in Monitoring – One analog feedback channel provides voltage telemetry to the main CPU, enabling remote monitoring of field power health.
-
Fault Indication – The digital fault output triggers external alarms for overcurrent, short-circuit, overtemperature, or undervoltage conditions.
-
Direct Drop-In for Legacy Systems – Pin-compatible with Mark IV backplanes that support 8HP boards, making it a straightforward replacement for failed NPSL units in older installations.
Typical Application Cases
-
Servo Valve Driver Cabinets – Supplies 125VDC power to electro-hydraulic servo valves in gas and steam turbine fuel control systems in legacy Mark IV installations.
-
Solenoid Valve Panels – Provides conditioned 125VDC power to safety shutdown solenoids, trip valves, and purge valves.
-
Actuator Control Cabinets – Powers electric actuators for inlet guide vanes, bleed valves, or turbine bypass controls.
-
Field Device Distribution Panels – Centralizes 125VDC distribution for field instruments in turbine auxiliary skids.
-
Legacy Fleet Replacement – The DS3800NPSL1A1A is the baseline replacement for failed field power boards in older Mark IV systems.
Competitive Comparison
| Aspect | DS3800NPSL1A1A (GE) | DS3800NPSL (later revision) | DS3800NPSJ1B1C (GE) |
|---|---|---|---|
| Primary Output | 125VDC / 5A | 125VDC / 5A or 250VDC / 2.5A | +5V / 22A (logic power) |
| Auxiliary Output | +24V / 0.5A | +24V / 1A | +24V / 2A |
| Isolation | Full (1.5kV) | Full (2.0kV) | Full (1.5kV) |
| Feedback Channels | 1 (voltage only) | 2 (voltage + current) | 4 (logic power) |
| Protection | Fixed OCP | Adjustable OCP | Fixed OCP |
| Operating Temp | –25°C to +60°C | –25°C to +60°C | –40°C to +70°C |
| Efficiency | ~84% | ~85% | ~88% |
| Form Factor | 8HP (2 slots) | 8HP (2 slots) | 8HP (2 slots) |
| Price (refurb) | ~$2,800–$4,200 | ~$3,500–$5,000 | ~$5,500–$7,500 |
The DS3800NPSL1A1A is a capable but aging design—it provides high-voltage field power but lacks the adjustable protection and dual monitoring of later NPSL revisions.
Selection Guidelines & Precautions
-
Application Verification – The DS3800NPSL1A1A supplies 125VDC field power, not logic power (+5V, ±15V). Verify your application requires 125VDC field power before selecting this board.
-
Physical Compatibility – The DS3800NPSL1A1A is 8HP wide, requiring two adjacent empty slots in your Mark IV/V rack. It will not fit in standard 4HP slots.
-
Backplane Compatibility – Uses both P1 and reinforced P2 connectors for high-current output. If your backplane lacks P2 (pre-2005 racks), the 125VDC output and +24V auxiliary will be unavailable.
-
Fixed Overcurrent Protection – The DS3800NPSL1A1A has fixed overcurrent protection (factory-set to ~6A). If your field devices draw close to 5A, nuisance tripping may occur. Consider upgrading to a later NPSL revision with adjustable protection if this is an issue.
-
Grounding – Maintain a single-point ground for the field power return to prevent ground-loop issues. The isolated output allows floating or grounded operation—consult your system’s grounding scheme.
-
Thermal Derating – Full output available up to 50°C:
-
50°C–55°C: derate to 90% of rated current (4.5A)
-
55°C–60°C: derate to 80% of rated current (4.0A)
-
Above 60°C: do not operate
-
-
Spare Sourcing – Production ended in 2005. When purchasing refurbished units, request a load test report verifying 125VDC / 5A output at 25°C and 50°C. Visually inspect for capacitor bulging, transformer discoloration, or burned traces. The DS3800NPSL1A1A is obsolete—consider upgrading to a later NPSL revision (e.g., NPSL1A1B or NPSL1A1C) if available, as they offer improved protection and monitoring features.

OMRON E5CN-Q2HBTC
A-B 1756-TBCH
A-B 1734-IB8


Reviews
There are no reviews yet.