GE DS3800NHVJ

¥999.00

The DS3800NHVJ is a specialized, high-performance Fan/Exhaust Control board from General Electric’s Mark V Speedtronic™ series, engineered for high-voltage DC applications with a hybrid output configuration and enhanced capabilities. The “NHVJ” designation indicates a board with:

  • 8 mechanical relays (2A @ 125VDC) for high-voltage exhaust fans—higher current than standard 1A @ 250VDC boards

  • 4 solid-state outputs (3A @ 24–48VDC)—higher current than the 2A found on NHVH/NHVF boards

  • 8 thermocouple input channels for temperature monitoring

  • 2 tachometer input channels for fan speed verification

  • Enhanced 16-bit ADC with improved cold-junction compensation

The DS3800NHVJ represents a significant upgrade over the “NHVH” series, offering higher solid-state output current (3A) and improved temperature measurement accuracy as standard features, making it the most capable 125VDC hybrid board in the Mark V lineup.

Category:

Description

Key Technical Parameters

Parameter Specification
Manufacturer General Electric (GE)
Series Mark V (Speedtronic)
Full Model DS3800NHVJ
Power Supply +5V DC @ 4.0A, +15V DC @ 0.7A, -15V DC @ 0.5A
Temperature Inputs 8 differential thermocouple channels (16-bit ADC, ±1°C accuracy)
Relay Outputs 8 mechanical relays, 2A continuous @ 125VDC (surge 4A)
SS Outputs 4 solid-state relays, 3A continuous @ 24–48VDC
Tachometer Inputs 2 channels with enhanced filtering (up to 10 kHz)
Communication Mark V proprietary parallel backplane bus
Operating Temperature 0°C to +60°C
LED Indicators Power, Relay Run (8x amber), SS Run (4x green), Tach Fail (red x2), Over-Temp Alarm, Backplane Active

Advantages and Distinctive Features

  • Hybrid Output + Tachometer Feedback: Combines 8 high-voltage DC relay outputs (125VDC), 4 high-current solid-state outputs (3A), AND 2 tachometer inputs on a single board.

  • Higher Solid-State Current (3A): Supports larger 48VDC auxiliary fans compared to 2A boards.

  • Higher Relay Current (2A @ 125VDC): Supports more powerful 110–125VDC fans.

  • Enhanced Temperature Accuracy (16-bit ADC): ±1°C accuracy as standard—no firmware upgrade required.

  • Improved Cold-Junction Compensation: More reliable temperature measurement.

  • Enhanced Tachometer Filtering: Reduces false speed failure alarms.


Typical Application Fields

  • Safety-Critical 125VDC Cooling Systems: Where fan failure must be detected immediately.

  • High-Voltage Industrial Fan Systems: 110–125VDC exhaust fans with higher-power 48VDC auxiliary controls and speed monitoring.

  • Military & Naval Applications: 125VDC systems in shipboard environments.

  • Railway and Traction Applications: 110VDC cooling systems with 48VDC auxiliaries.

  • Legacy Turbine Installations: Older systems using 125VDC fan motors.


Comparison with Related Models

Feature DS3800NHVJ DS3800NHVH DS3800NHVF DS3800NHVB
Relay Outputs 8 × 2A @ 125VDC 8 × 2A @ 125VDC 8 × 1A @ 250VDC 8 × 2A @ 125VDC
SS Outputs 4 × 3A @ 48VDC 4 × 2A @ 48VDC 4 × 2A @ 48VDC None
Tach Inputs 2 channels 2 channels 2 channels None
ADC Resolution 16-bit (±1°C) 12-bit (±2°C) 12-bit (±2°C) 12-bit (±2°C)
Enhanced CJC Yes No No No
Enhanced Tach Filter Yes No No N/A
Operating Temp 0°C to +60°C 0°C to +60°C 0°C to +60°C 0°C to +60°C
Cost High High High Medium

Selection Recommendations

  • Choose the DS3800NHVJ if:

    • You need 125VDC relay outputs with 2A current capacity for more powerful fans.

    • You also need higher-current solid-state outputs (3A @ 48VDC) for larger auxiliary fans.

    • You require tachometer feedback for fan speed verification.

    • You want enhanced temperature accuracy (±1°C) and improved filtering.

    • You have a climate-controlled environment (0°C to +60°C).

  • Choose the DS3800NHVH if: You need 2A @ 125VDC relays and tachometer feedback but can accept 2A solid-state outputs and 12-bit ADC.

  • Choose the DS3800NHVF if: You need 250VDC relay outputs (1A) with hybrid + tachometer features.

  • Choose the DS3800NHVB if: You need 125VDC relay outputs (2A) without solid-state auxiliary outputs or tachometer feedback.


Critical Precautions

  • ESD Protection: Always wear a grounded wrist strap.

  • High-Voltage Hazard: Relay outputs switch 125VDC—lethal voltage present on terminals. Observe all high-voltage safety procedures. Use wiring rated for ≥125VDC.

  • DC Polarity (Relay): Relay outputs are DC only—observe correct polarity.

  • DC Polarity (SS): Solid-state outputs are DC-only and polarity-sensitive—reverse polarity destroys the MOSFET.

  • Tachometer Wiring: Use shielded twisted-pair cable. Connect shield to designated terminal—not at the fan end.

  • Relay Current Limitation: Rated at 2A continuous @ 125VDC. Verify fan current does not exceed this limit.

  • SS Current Limitation: Rated at 3A continuous @ 24–48VDC. At elevated temperatures, consider derating.

  • Inductive Load Derating (Relay): Derate to 1.5A or use external RC snubbers (rated for 125VDC).

  • No AC Connection: Do not connect AC loads to either output type.

  • No Hot-Swap: Always depower the rack before insertion/removal.

  • Slot Assignment: Install in slots 8–10 (auxiliary I/O).

  • CPU Dependency: If backplane communication is lost, the board defaults to 100% fan speed—tachometer monitoring disabled in fallback mode.

  • Firmware Compatibility: The DS3800NHVJ is compatible with Mark V CPU firmware v4.0 and above for full 16-bit ADC functionality. For v3.x, the enhanced ADC features may be partially disabled—confirm compatibility before purchasing.