Description
Key Technical Parameters
| Parameter | Specification |
|---|---|
| Manufacturer | General Electric (GE) |
| Series | Mark V (Speedtronic) |
| Full Model | DS3800NFLA1C1C |
| Power Supply | +5V DC @ 3.5A, +15V DC @ 0.6A, -15V DC @ 0.4A (via backplane) |
| Temperature Inputs | 4 differential thermocouple channels (Type J/K/T, 16-bit ADC, ±1°C accuracy) |
| RTD Inputs | None |
| Fan Outputs | 8 mechanical relays, 5A continuous @ 115VAC or 30VDC (surge 10A for 100ms) |
| Tachometer Inputs | 2 channels with enhanced signal conditioning (up to 15 kHz) |
| Communication | Mark V proprietary parallel backplane bus |
| Operating Temperature | -20°C to +65°C (extended range) |
| Storage Temperature | -40°C to +85°C |
| LED Indicators | Power (green), Fan Run (8x amber), Tach Fail (red x2), Over-Temp Alarm (red), Backplane Active (yellow) |
Advantages and Distinctive Features
-
5A Mechanical Relays: The DS3800NFLA1C1C delivers 5A continuous output capability (10A surge), making it suitable for driving 1/2 HP AC fans or multiple DC fans in parallel—a significant upgrade over the 3A base model.
-
Reduced Thermocouple Count (4 channels): With only 4 temperature inputs, the DS3800NFLA1C1C dedicates additional processing power to tachometer signal conditioning, providing more stable speed readings in high-EMI environments.
-
Enhanced Tachometer Processing: The Revision C firmware includes advanced debounce filtering, reducing false speed failure alarms caused by electrical noise or fan vibration.
-
Improved Temperature Accuracy: The 16-bit ADC with enhanced cold-junction compensation provides ±1°C accuracy—double the precision of the base model’s 12-bit (±2°C) ADC.
-
AC/DC Output Capability: Mechanical relays on the DS3800NFLA1C1C can switch both AC and DC fan loads, offering flexibility for mixed cabinet installations.
-
Complete Galvanic Isolation: Relay outputs provide 2500V isolation between control logic and fan power circuits.
Typical Application Fields
-
Turbine Cabinets with Few Temperature Sensors: Where 4 sensors monitor multiple fan zones, and speed feedback is critical.
-
Safety-Critical Cooling Systems: Applications requiring immediate fan failure detection via tachometer feedback.
-
High-Inrush Fan Applications: 5A relays with 10A surge handling support large AC fans or motorized blowers.
-
High-EMI Environments: Mechanical relays provide superior isolation and noise immunity compared to solid-state alternatives.
-
Retrofit Upgrades: Replacing older DS3800NFLA boards with the DS3800NFLA1C1C for higher current, better accuracy, and extended temperature range.
Comparison with Related Models
| Feature | DS3800NFLA1C1C | DS3800NFLA (Base) | DS3800NFEE1C1B | DS3800NFIA1B1C |
|---|---|---|---|---|
| Output Type | Mechanical relay (AC/DC) | Mechanical relay (AC/DC) | Mechanical relay (AC/DC) | Solid-state (DC only) |
| Output Current | 5A | 3A | 5A | 3A |
| Thermocouple Inputs | 4 channels | 8 channels | 8 channels | 4 channels |
| Tachometer Inputs | 2 channels (enhanced) | 2 channels | None | 2 channels |
| ADC Resolution | 16-bit (±1°C) | 12-bit (±2°C) | 16-bit (±1°C) | 16-bit (±1°C) |
| Onboard Logic | No (CPU-dependent) | No | No | Yes (threshold) |
| Operating Temp | -20°C to +65°C | 0°C to +60°C | -20°C to +65°C | -20°C to +65°C |
| Fallback Mode | Full speed (100%) | Full speed (100%) | Full speed (100%) | Autonomous ON/OFF |
| Cost (Used) | Medium-High | Medium | Medium | Medium |
Selection Recommendations
-
Choose the DS3800NFLA1C1C if:
-
Your fans require mechanical relay outputs (AC or DC) with high surge handling (up to 10A).
-
Your cabinet uses ≤4 temperature sensors but requires 8 fan outputs.
-
You need enhanced tachometer feedback reliability in high-EMI environments.
-
You want improved temperature accuracy (±1°C) for better thermal management.
-
Your installation environment ranges from -20°C to +65°C.
-
-
Choose the DS3800NFLA (base) if: You need 8 thermocouple inputs, 3A relays, and have a climate-controlled environment.
-
Choose the DS3800NFEE1C1B if: You need 5A relays but do not require tachometer feedback.
-
Choose the DS3800NFIA1B1C if: You prefer solid-state DC outputs with tachometer feedback and autonomous fallback logic.
Critical Precautions
-
ESD Protection: The DS3800NFLA1C1C contains sensitive ADC components. Always wear a grounded ESD wrist strap.
-
Missing Thermocouple Channels: The DS3800NFLA1C1C has only 4 thermocouple inputs (channels 1–4). Channels 5–8 are physically absent and will not function—do not attempt to connect sensors.
-
Relay Contact Wear: Mechanical relays are rated for 100,000 operations at 5A. For frequent cycling, consider derating or using solid-state alternatives.
-
Inductive Load Derating: The 5A rating applies to resistive loads. For inductive fan motors, derate to 3.5A or use an external RC snubber across each relay output to suppress arcing.
-
Tachometer Wiring: Use shielded twisted-pair cable for tachometer signals. The enhanced conditioning on the DS3800NFLA1C1C reduces noise sensitivity, but proper grounding is still essential. Connect shield to the designated terminal—not at the fan end.
-
No Hot-Swap: Always depower the Mark V rack before inserting or removing the DS3800NFLA1C1C.
-
Slot Assignment: Install in auxiliary I/O slots (typically slots 8–10). Do not install in CPU or analog input slots.
-
CPU Dependency: Since the DS3800NFLA1C1C has no onboard logic, the Mark V CPU must process tachometer feedback and send fan commands. If backplane communication is lost, the board defaults to 100% fan speed—tachometer monitoring will be disabled in fallback mode.
-
Firmware Compatibility: Revision C firmware is compatible with Mark V CPU firmware v4.0 and above. For v3.x systems, the enhanced tachometer filtering may be partially disabled—confirm compatibility before purchasing.

AB 1747-M13
OMRON C200H-0C224
A-B 1734-OE2V


Reviews