GE DS3800HIMA1B1B

¥999.00

The DS3800HIMA1B1B is a General Electric Mark IV Speedtronic turbine control board, an analog input module with a suffix code indicating: 8-channel differential input (1), firmware revision B1 (B1), and basic environmental protection (B = single-layer conformal coating). The B1 firmware offers improved linearization and filtering compared to the earlier A1 revision, providing better noise rejection and signal stability for industrial transmitters. The B-grade coating provides basic moisture resistance for clean indoor applications.

Category:

Description

Parameters

  • Input Type: 4–20mA (default), 0–10V DC, ±10V DC (jumper-configurable)

  • Channels: 8 differential (fixed)

  • Resolution: 12-bit ADC

  • Accuracy: ±0.08% of full scale (improved over A1’s ±0.1%)

  • Input Impedance: 250Ω (current) / >1MΩ (voltage)

  • Filtering: 50Hz/60Hz noise rejection (B1 feature)

  • Isolation: 1500V RMS optical isolation (channel-to-backplane)

  • Power: +5V DC @ 0.8A, +15V DC @ 0.2A (requires both rails)

  • Scan Rate: 80ms per channel (B1 optimized, faster than A1’s 100ms)

  • Coating: Conformal coating (suffix B) – single-layer acrylic

  • Temp Range: 0°C to +60°C

  • Mounting: 6U VME Eurocard, single-slot

  • Diagnostics: Enhanced LED status per channel (over-range, under-range, open-circuit, and signal noise alert)

Advantages & Features

  • Versatile input support – accepts 4–20mA, 0–10V, or ±10V signals via jumpers, compatible with most industrial transmitters

  • B1 firmware offers improved accuracy (±0.08%), faster scan (80ms), and built-in 50/60Hz noise filtering – a significant upgrade over A1

  • 8 differential channels provide noise rejection for long cable runs in turbine environments

  • Isolated channels reduce ground loop interference and protect the backplane from field wiring faults

  • Basic B-grade coating provides light moisture and dust protection for indoor installations

  • Front-panel LEDs for per-channel status including signal noise detection alerts

  • Compatible with Mark IV backplanes and some VIe systems (with adapter)

Application Cases

  • Turbine inlet guide vane (IGV) position feedback – 4–20mA from LVDT transmitters requiring stable, noise-free readings

  • Fuel gas pressure monitoring – 4–20mA transmitters in gas turbine fuel skids where 50/60Hz noise is present

  • Steam pressure and flow monitoring – for steam turbine throttle and extraction lines with improved accuracy needs

  • Lube oil pressure and temperature – from standard 4–20mA transmitters on bearing and sump systems

  • Retrofit projects upgrading from A1 firmware to B1 for better noise rejection and faster response

Competitor Comparison

  • vs. DS3800HIMA1A1B (A1/B variant): Better accuracy (±0.08% vs. ±0.1%), faster scan (80ms vs. 100ms), built-in noise filtering, and signal noise diagnostics – significant upgrade

  • vs. DS3800HIMA (standard A variant): Better specifications across the board; B1 is a meaningful improvement

  • vs. DS3800HIMA1C1C (C variant): Similar performance, but B coating is basic vs. C’s improved moisture resistance

  • vs. DS3800HFPB (thermocouple board): Handles different signal types – HIMA1B1B is for 4–20mA/voltage, not thermocouples

  • vs. DS3800HSCB (high-speed analog input): HIMA is standard speed (80ms), HSCB offers faster scanning for dynamic signals

  • vs. ABB TB711 : Similar channel count, but ABB offers higher resolution (14-bit) and PROFIBUS/Modbus communication

  • vs. Siemens 7MH410 : Similar functionality, but Siemens offers HART protocol support on some variants

  • vs. Woodward 8440-2015 : Similar channel count, but Woodward offers more flexible configuration software

  • vs. Honeywell 51304638 : Similar channel count, but Honeywell offers better long-term stability (±0.05%)

Selection Suggestions

  • Critical: Confirm input signal type (4–20mA, 0–10V, or ±10V) before installation – jumper settings must match your transmitters

  • Verify your backplane provides both +5V and +15V – this board requires both rails

  • Assess if B1’s noise filtering and faster scan rate are beneficial – particularly valuable near VFDs or in electrically noisy environments

  • Evaluate environmental conditions – B coating is suitable for clean, dry indoor installations; upgrade to C/D/G/H for more demanding environments

  • Order mating front connector (p/n may vary – confirm with GE)

  • For critical applications, consider used/refurbished units with 90-day warranty or new-old-stock with calibration certificate

Precautions

  • Critical: Do not exceed 30mA or ±30V on input channels – overvoltage may damage the ADC and isolation circuits

  • Critical: Use shielded twisted-pair cables for all analog inputs to avoid EMI – B1’s filtering helps but is not a substitute for good wiring practices

  • Ensure field power supply (+24V DC) for 2-wire transmitters is stable and within specifications (if loop-powered)

  • B1 firmware offers improved noise rejection – configure jumpers correctly for 50Hz or 60Hz based on your region

  • Basic B coating does not protect against humidity or corrosive gases – upgrade to C/D/G/H if your environment has moisture or chemicals

  • Allow 30-minute warm-up before calibration

  • Store in ESD-safe packaging – edge connector is static-sensitive

  • Periodically verify channel calibration every 2 years against a certified reference

  • Do not hot-swap – Mark IV backplanes require power-off for insertion/removal

  • If replacing a similar board, confirm pinout compatibility – HIMA series may differ from HFP or HHR series in wiring assignments

NI SCXI-1180
KB KBRG-212D
ABB DO810

Reviews

There are no reviews yet.

Be the first to review “GE DS3800HIMA1B1B”

Your email address will not be published. Required fields are marked *