Description
Technical Specifications
-
Product Type: Digital Voltage Reference & Calibration Board (Revision 1A1)
-
Part Number: GE DS3800DVRC1A1
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems
-
Reference Outputs: 4 precision voltage references (±1V, ±5V, ±10V, and 0-10V)
-
Accuracy: ±0.01% of full scale at 25°C; ±0.003% per °C drift (improved)
-
Temperature Stability: < 3ppm/°C (improved from 5ppm/°C)
-
Long-Term Stability: < 30ppm/year (improved from 50ppm/year)
-
Load Regulation: < 0.005% for 0 to 10mA load
-
Line Regulation: < 0.001% for ±10% input variation
-
Protection: Short-circuit protected outputs
-
Isolation: 1500Vrms isolation from backplane
-
Temperature Range: 0°C to +65°C (extended)
-
MTBF: > 250,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
Enhanced Temperature Stability: The GE DS3800DVRC1A1 offers improved < 3ppm/°C drift, ensuring calibration accuracy over wider temperature variations.
-
Better Long-Term Stability: < 30ppm/year reduces recalibration frequency and maintains system accuracy over extended periods.
-
High-Precision References: Provides ±0.01% accuracy, essential for calibrating the Mark IV’s 12-bit analog-to-digital converters.
-
Four Common Reference Values: Offers ±1V, ±5V, ±10V, and 0-10V, covering the full input range of most Mark IV analog boards.
-
Extended Temperature Range: 0°C to +65°C provides greater margin in warm turbine enclosures.
-
Short-Circuit Protection: Protected outputs prevent damage during calibration setup.
-
Diagnostic LEDs: Front-panel LEDs indicate reference output status and fault conditions.
-
External Test Points: Provides test points for external voltmeter verification during routine maintenance.
Typical Application Cases
-
Analog Input Calibration: Calibrates DS3800DVIA and DS3800DVIA1A1B voltage input boards for accurate field signal readings.
-
Analog Output Verification: Verifies accuracy of output boards by comparing against reference.
-
System Diagnostics: Provides known-good signal source for troubleshooting faulty boards.
-
Preventive Maintenance: Used during annual maintenance to check all analog board calibrations.
-
Commissioning: Essential during initial startup to verify all analog channels meet specifications.
Competitive Comparison
| Feature | GE DS3800DVRC1A1 | GE DS3800DVRC1A | External Voltage Calibrator |
|---|---|---|---|
| Temperature Stability | < 3ppm/°C | < 5ppm/°C | < 1ppm/°C to < 10ppm/°C |
| Long-Term Stability | < 30ppm/year | < 50ppm/year | < 10ppm/year |
| Temperature Range | 0°C to +65°C | 0°C to +60°C | 0°C to +50°C (typical) |
| Accuracy | ±0.01% | ±0.01% | ±0.001% to ±0.01% |
| Reference Values | ±1V, ±5V, ±10V, 0-10V | ±1V, ±5V, ±10V, 0-10V | User-selectable |
| Integration | Rack-mounted | Rack-mounted | Portable |
The GE DS3800DVRC1A1 offers improved temperature and long-term stability over the DS3800DVRC1A, making it the preferred revision for high-ambient-temperature installations.
Selection Guidelines & Precautions
-
Reference Verification: Verify outputs with a calibrated external voltmeter before use. If drift is observed, the board requires factory recalibration.
-
Load Conditions: Accurate only when load current is below 10mA. For higher loads, use external buffer amplifier.
-
Warm-Up Time: Allow the GE DS3800DVRC1A1 to stabilize for at least 30 minutes after power-up before performing critical calibrations.
-
Short-Circuit: While protected, prolonged shorting may degrade accuracy over time.
-
Calibration Interval: GE recommended recalibration every 2 years. Send to qualified calibration lab if internal capability is unavailable.
-
ESD Handling: Use ESD-safe practices; contains precision reference components.
-
Sourcing: Obsolete. Request functional test report including:
-
All 4 reference outputs verified for accuracy (±0.01%)
-
Temperature drift test (< 3ppm/°C)
-
Load regulation test (< 0.005%)
-
Isolation verification
-
Long-term stability test (if available)
-
-
Spare Strategy: Keep one spare GE DS3800DVRC1A1 on-site if regular analog board calibrations are performed. For critical sites, consider NIST-traceable external calibrator as backup.